Information based on query as of Tuesday, April 30, 2024.
Permit Information
Permit NumberFIR20-00066
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7340 N LUCY ROSE LN
Project NameEAGLE HAWK APTS. BLD 6
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13R FIRE SPRINKLER SYSTEM IN THIS NEW APARTMENT BUILDING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/17/20206/18/20206/18/2020PPASS
DetailsJim Page
Final fire sprinkler inspection is complete.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/8/20204/9/20204/9/2020PDONE
DetailsJim Page
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.

Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in3/19/20203/20/20203/20/2020APASS
DetailsJim Page
Previously noted items have been corrected, all tenting in place at time of inspection, cover is approved. Approval sticker has been placed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in3/19/20203/19/20203/19/2020PFAIL
DetailsJim Page
Open 1 1/2 outlet and 1 inch outlet open above finish ceiling, inspection stopped.

Overhead rough ; tenting, call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello