Final | 12/14/2018 | 12/17/2018 | 12/17/2018 | A | PASS |
Jack Reynolds
|
|
|
Lock box on light above door on west side of home. Code is 2010. Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek - final ok
|
Final | 12/5/2018 | 12/6/2018 | 12/6/2018 | P | FAIL |
Jack Reynolds
|
|
|
Call Max for door code ###-#### Inspection requested via web by Floyd Floyd Peek - line set insulation in the crawl needs fixed - line set penetration needs to be sealed - one seam on the dryer vent needs sealed in the crawl - need a duct blast report - secondary drain needs wet switch
|
Rough-in | 6/29/2018 | 6/29/2018 | 6/29/2018 | A | PASS |
Jack Reynolds
|
|
|
Cold air return ducts added to bedrooms, Call Max if you need anything ###-#### Inspection requested via web by Floyd Floyd Peek- transfer air into rooms ok
|
Rough-in | 6/28/2018 | 6/28/2018 | 6/28/2018 | A | FAIL |
Jack Reynolds
|
|
|
Thanks, Call Max if you need anything ###-#### Inspection requested via web by Floyd Floyd Peek- need ducted returns in bedrooms or transfer air from rooms to living room where return air is located
|
Rough-in | 6/12/2018 | 6/12/2018 | 6/12/2018 | A | FAIL |
Jack Reynolds
|
|
|
Call Max if you need door code, furnace is in the crawl. ###-#### Inspection requested via web by Floyd Floyd Peek- need Man J. onsite for R/I inspection
|