Information based on query as of Thursday, May 9, 2024.
Permit Information
Permit NumberMEC18-03194
StatusFinaled
Name CLOVERDALE PLUMBING CO
Site Address 9492 W EMERALD ST
Project Name 
Customer Number1810-90-98
ePlanReviewNo
Description
New: New Building with Hydronic heating piping and natural gas piping
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/9/20199/10/20199/10/2019PPASS
DetailsBrian Scoles
Please call Pat prior to arrival at ###-#### Phone #: ###-#### Inspection requested via web by Maira Napoles- final ok
Final8/7/20198/8/20198/8/2019PPART
DetailsBrian Scoles
Please call Pat prior to arrival at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Maira Napoles- gas piping on roof ok- pressure tested under other mech permit- hydronic piping and insulation ok meets 25/50 flame smoke spread- need to add drip leg between shuoff valve and regulator on gas piping to boilers- rest is good- will look at this on other mech contractors final for dry side
Mec-Aging Inspection7/15/20197/15/20197/15/2019 FAIL
DetailsBrian Scoles
needs called in for cover inspection
Rough-in4/15/20194/15/20194/15/2019APASS
DetailsBrian Scoles
Please call Patrick prior to arrival at ###-####. Phone #: ###-#### Inspection requested via web by Maira Napoles- 2nd floor 100lb hydronic test pass
Rough-in2/20/20192/21/20192/21/2019APASS
DetailsBrian Scoles
Rough-in on first-floor eastside. Please call Patrick prior to arrival at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Maira Napoles- R/I ok 1st floor- pipe insulation needs to be plenum rated
Pressure Test2/21/20192/21/20192/21/2019APASS
DetailsBrian Scoles
Rough-in on first-floor eastside. Please call Patrick prior to arrival at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Maira Napoles- 1st floor only 100# test on hydronics pass- ok for insulation