Final | 8/7/2019 | 8/7/2019 | 8/7/2019 | P | PASS |
Brian Scoles
|
|
|
CONTACT JASON TUPPER ###-#### FOR ACCESS, PLEASE Phone #: ###-#### Inspection requested via web by Andrea Creek
|
Final | 7/26/2019 | 7/30/2019 | 7/30/2019 | A | FAIL |
Brian Scoles
|
|
|
CONTACT JASON TUPPER 208 936 1215 FOR ACCESS Phone #: ###-#### Inspection requested via web by Andrea Creek- need to insulate supply plenum below coil at furnace location- need to hook up flue for water heater- need to seal gas line penetration at meter location where penetrates into building weather tight
|
Rough-in | 4/17/2019 | 4/18/2019 | 4/18/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- R/I ok
|
Pressure Test | 4/17/2019 | 4/18/2019 | 4/18/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- 60lb gas pass tagged meter location- 20lb gas pass- 5lb flue x 2 pass
|
Rough-in | 4/16/2019 | 4/17/2019 | 4/17/2019 | A | FAIL |
Brian Scoles
|
|
|
Thanks, Brian ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek- R/A insulation in attic needs to be R-6 and remove batting insulation installed on one side and and wrap with vapor barrier insulation- need stamped and approved manual j onsite- transfers in bedroom dont match man j sizing and might interfere with doors- dryer vent needs ran in 5.5 inch wall not 3.5 inch wall need to fir out- talked with general contractor onsite- left correction notice front window
|
Pressure Test | 4/16/2019 | 4/17/2019 | 4/17/2019 | A | FAIL |
Brian Scoles
|
|
|
Thanks, Brian ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek- 60lb gas test failed below 60psi- 20lb gas pass- 5lb flue test pass
|