Final | 7/24/2019 | 7/25/2019 | 7/25/2019 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok- card signed
|
Final | 7/22/2019 | 7/23/2019 | 7/23/2019 | P | PART |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- need to remove stucco from around gas piping and seal weather tight- rest is good- recall in when correction made
|
Pressure Test | 5/17/2019 | 5/17/2019 | 5/17/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass whole system- tagged meter location
|
Rough-in | 5/17/2019 | 5/17/2019 | 5/17/2019 | P | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok- fire damper shown on prints has been talked to with engineer ok to omit by Justin Beaucannon with KB associates per document onsite 5-17-19
|
Rough-in | 5/13/2019 | 5/14/2019 | 5/14/2019 | A | FAIL |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- outside air needs to be 8" round to each unit per prints and cannot tie in R/A register can needs to tie into plenum both are ran in 6" to 8" wye at wall- print M-1 shows 2 firedampers in chase first floor none are installed- electric heater in 1st floor stairwell needs installed- missing supply and transfer in closet SW corner 1st floor per prints- whos doing gas line ?- left correction notice front window
|