Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberMEC19-01757
StatusFinaled
Name IDAHO HEATING AND COOLING LLC
Site Address 2401 W TARGEE ST
Project Name 
Customer NumberHawth Cafe
ePlanReviewNo
Description
New: New HVAC equipment, ductwork, kitchen equipment
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/9/201912/9/201912/9/2019PPASS
DetailsJack Reynolds
final ok occ card signed
Final11/25/201911/25/201911/25/2019PPART
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
- TAB report ok. Will sign occ card once corrections are made and two other mech permits from others are finaled
- all equipment needs set in its place and hood should hang not less than 6" beyond edge of equipment. one piece of equipment is outside of hoods edge.
- both hoods need grease reservoirs installed in hood
Final11/14/201911/15/201911/15/2019APART
DetailsJack Reynolds
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
- need TAB report for final
Rough-in11/1/201911/4/201911/4/2019APASS
DetailsJack Reynolds
Ceiling cover. Thank you! Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
- ceiling cover R/I ok
Rough-in10/29/201910/30/201910/30/2019AFAIL
DetailsJack Reynolds
ceiling cover Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
L-1 louvers for make up air to kitcken need ducted into ceiling.
- return tap at ceiling in kitcken needs sealed
- factory grease duct clearances ok
Rough-in7/22/20197/23/20197/23/2019PPART
DetailsJack Reynolds
Hard lid cover. Thank you! Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
- hard lid only R/I cover ok on exhaust and heaters