Permit Information
Permit NumberMEC19-02561
StatusFinaled
Name CFM HEATING & AIR INC
Site Address 10577 W FAIRVIEW AVE
Project Name 
Customer Numberpending
ePlanReviewNo
Description
New: New HVAC System with RTU A/C units, exhaust fans, kitchen hood, ductwork, air outlets, No gas piping
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/6/20202/6/20202/6/2020PPASS
DetailsBrian Scoles
Roger Graves has a copy of the air balance report on site. Phone #: ###-#### Inspection requested via web by Doug Madsen- final ok- air balance ok- equipment under hood set- card signed
Final1/10/20201/13/20201/13/2020APART
DetailsBrian Scoles
Roger Graves the site superintendent will be the onsite contact his phone number is ###-####. Phone #: ###-#### Inspection requested via web by Doug Madsen
1- oven needs set under hood to check clearances
2- air balance on EF 2 for hood onsite
3- R/A in storage room needs R6 flex duct installed
4- need approved fittingand ducting to class 2 hood and sealed- has make shift ducting to hood need to replace

Roof is good- call in final when all equipment and corrections made and air balance report onsite
Rough-in12/3/201912/4/201912/4/2019APASS
DetailsBrian Scoles
Roger Phone #: ###-####- R/I ok- hard lids ok for cover- insulation ok- ok for ceiling grid- class 2 exhaust approved via engineer for running in galvanized
Rough-in11/22/201911/25/201911/25/2019APART
DetailsBrian Scoles
Roger Graves is the job site contact ###-#### Phone #: ###-#### Inspection requested via web by Doug Madsen- seal on all ducting ok- need to finish insulation on all ducting above hard lids- all register cans need installed in bathrooms and flex for hard lid cover- call in R/I inspection when these are completed- need engineer approval on galv duct for class 2 hood shows to run in aluminum