ELE-Final | 10/17/2019 | 10/17/2019 | 10/17/2019 | P | PART |
Rock A. Hudson
|
|
|
Work completed under ELE19-01088. ELE Final ok
|
BLD-Conference | 7/30/2019 | 7/30/2019 | 7/30/2019 | P | CANC |
Mike Jordan
|
|
|
|
MEC-Conference | 7/30/2019 | 7/30/2019 | 7/30/2019 | P | FAIL |
Chad Schwendiman
|
|
|
per Mike J-mec work done w/o permit - TVR installed a new A/C without a permit. I called them and they are going to get one pulled
|
ELE-Conference | 7/30/2019 | 7/30/2019 | 7/30/2019 | P | FAIL |
Rock A. Hudson
|
|
|
ELE and MEC- Newer AC unit on Northwest corner, no permit found for ELE or MEC. Misc electrical issue left when last tenant vacated. All Items found in other areas not in scope of work covered by BLD18-03533. BCC 4-05-32- Code violations not to be retained. Unable to locate mechanical permit for newer AC unit located on northwest corner. 110.3- Double duplex receptacle located in conference room not working. Found wire damaged by others, left damaged in ceiling. 110.12(B)- Repair all open and unsecured conduits. 210.63- A 15 or 20 amp 120 volt receptacle outlet shall be installed with in 25' of newer AC unit. 314.23- Boxes shall be secured to structure. Receptacles and MC hanging laying on top of file cabinet. 408.4- Panel directory for panel 2 shall be complete. 440.14- A disconnecting means shall be provided for newer AC unit located on N.W. corner.
|