INSP-Final | 2/20/2019 | 2/21/2019 | 2/21/2019 | P | PART |
Troy Cobbley
|
|
|
A temporary for life safety is ok with Boise Fire approval until the fire sprinkler is added at the base of the stairs and a possible riser monitoring system is installed. Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by Dave
|
INSP-Final | 2/19/2019 | 2/20/2019 | 2/20/2019 | A | FAIL |
Troy Cobbley
|
|
|
Provide indicators on the two new doors, provide sticker on the two new doors, repair rear exit door exit sign, provide verification of need of sprinkler protection at bottom of stairs in front of new tenant door. May need a fire sprinkler monitoring system (I spoke to Ron on this)
Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by General
|
INSP-Final | 2/13/2019 | 2/19/2019 | 2/19/2019 | A | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by Dave Inspection cancelled via mobile web on Tuesday, February 19, 2019.
|
INSP-Final | 2/13/2019 | 2/14/2019 | 2/13/2019 | A | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2082834604 >> Inspection requested via mobile web by Dave Inspection cancelled via mobile web on Wednesday, February 13, 2019.
|