Case Summary (BLD) | | | 12/19/2008 | | |
|
|
|
|
Case Summary (BLD) | | | 11/10/2005 | | |
|
|
|
|
Fee Review-notes | 6/6/2000 | 6/6/2000 | 8/30/2002 | | DONE |
|
|
|
|
Letter of compliance | | | 8/2/2002 | | DONE |
|
|
|
Letter of Compliance #22555 issued 8-2-02.
|
BLD-Final | 8/1/2002 | 8/1/2002 | 8/1/2002 | | PASS |
Carl Dependahl
|
|
|
All work appears complete, rooftop screen in place, rails installed, ok for perm. occ. (L/C?)
|
CHANGE STATUS TO (ISS) | | | 8/22/2001 | | DONE |
|
|
|
CHANGED TO ISSUED STATUS-ALREADY PD
|
BLD-Conference | 6/8/2001 | 6/8/2001 | 6/8/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/8/2001 2:35:12 PM ok for t/o, keep c/n
|
Inspection Record Card- Bld | | | 6/7/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/7/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/7/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Receive PAYMENT IN FULL PRINT | | | 6/7/2001 | | DONE |
|
|
|
|
BLD-Conference | 6/5/2001 | 6/5/2001 | 6/5/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/5/2001 9:47:00 AM w/ kim re other oks
|
Case Summary (BLD) | | | 6/5/2001 | | DONE |
|
|
|
|
Routing - PUBLIC WORKS | 6/1/2001 | | 6/5/2001 | | DONE |
|
|
|
Plan modification of 6/1/01
|
Plan assigned to (R_H) | 6/1/2001 | | 6/5/2001 | | PASS |
|
|
|
Plan Modification.
|
Plans ACCEPTED BY PLAN TECH | | | 6/1/2001 | | DONE |
|
|
|
Plan modification
|
Waiting for Cert. of Value | | | 6/1/2001 | | DONE |
|
|
|
Plan modification
|
Plan routing begun/TENANTS | | | 6/1/2001 | | DONE |
|
|
|
plan modification:
|
BLD-Final | 5/30/2001 | 5/31/2001 | 5/31/2001 | P | PART |
Carl Dependahl
|
|
|
###-####; keep c/n, ok for t/o only 5/31/2001 11:25:57 AM
|
Temporary occupancy | | | 5/31/2001 | | PART |
|
|
|
Temp. Occ. Cert. #4553 issued 5-31-01 to the Adelmann Bldg. shell & core.
|
Plan Modification Accepted | | | 5/31/2001 | | DONE |
|
|
|
|
CHANGE STATUS TO (PND) | | | 5/31/2001 | | DONE |
|
|
|
PLAN MOD
|
BLD-Final | 5/29/2001 | 5/30/2001 | 5/30/2001 | A | FAIL |
Carl Dependahl
|
|
|
Kim ###-####, need achd, complete previous items...handrails, firestops, etc. 5/30/2001 1:38:02 PM
|
BLD-Final | 5/25/2001 | 5/29/2001 | 5/29/2001 | A | NR |
Carl Dependahl
|
|
|
need verify bond or p&z ok for roof top equip. 5/30/2001 9:14:19 AM
|
BLD-Final | 5/24/2001 | 5/25/2001 | 5/25/2001 | P | NR |
Carl Dependahl
|
|
|
early afternoon Tim ###-#### this was the test you can cancl this insp. you talked to kim fri. 5/25/2001 2:26:28 PM...nr, recall 5/25/2001 2:46:10 PM
|
FIRE-Final Inspection | 5/18/2001 | 5/18/2001 | 5/18/2001 | P | FAIL |
Rick Jackson
|
|
|
1:30 ###-#### duct detectors for damper control not tied to system; backflow peventer cycling; c/n issued 5/21/2001 7:11:28 AM
|
BLD-Conference | 5/18/2001 | 5/18/2001 | 5/18/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/18/2001 1:12:19 PM w/ Tempra, need resolve historical issues
|
BLD-Final | 5/17/2001 | 5/18/2001 | 5/18/2001 | A | FAIL |
Carl Dependahl
|
|
|
###-####, need fire, eng's ok letter, complete ha 5/18/2001 1:17:05 PM ndrails as need, etc, recall 5/18/2001 1:17:24 PM
|
BLD-Conference | 5/17/2001 | 5/17/2001 | 5/17/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/17/2001 12:34:20 PM w/ Kim, call for insp of shafts, rails
|
BLD-Conference | 5/17/2001 | 5/17/2001 | 5/17/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/17/2001 4:59:43 PM w/325 & Tim H. re p& z ok
|
FIRE-Conference | 5/17/2001 | 5/17/2001 | 5/17/2001 | P | PASS |
Rick Jackson
|
|
|
###-#### discussed requirements for final inspection with contractor and Carl D. 5/17/2001 3:16:32 PM
|
BLD-Framing/Rough-in | 5/17/2001 | 5/17/2001 | 5/17/2001 | P | PART |
Carl Dependahl
|
|
|
###-#### ok to close hvac shaft at bsmt; posted do not occupy...need p&z ok re rooftop 5/17/2001 4:58:16 PM
|
BLD-Conference | 3/21/2001 | 3/21/2001 | 3/21/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 3/21/2001 10:54:27 AM w/ supt...repair of crack at north side..need eng's spec
|
BLD-Framing/Rough-in | 3/5/2001 | 3/6/2001 | 3/6/2001 | A | PART |
Carl Dependahl
|
|
|
for drain insp-- kim ###-#### ; drain at stairs ok; keep c/n for struct items; need proper assembly for dropped ceiling at 2nd fl. & verification of "wall finish" per specs 3/6/2001 9:00:20 AM
|
BLD-Conference | 3/5/2001 | 3/5/2001 | 3/5/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 3/5/2001 3:31:24 PM w/ Ron re submittal for int finish.
|
BLD-Conference | 3/2/2001 | 3/2/2001 | 3/2/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 3/2/2001 9:13:52 AM w/ Ron Hill re eng's notes & reports...awaiting resolution to new issues: cracks found at old masonry apparently not anticipated or noted...
|
BLD-Framing/Rough-in | 2/27/2001 | 2/27/2001 | 2/27/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/27/2001 3:08:53 PM wip. need omplete 1hr lid & wrap at 1hr stair enclosure & part bsmt lid...chk riser/mech room reqs at bsmt
|
Plan resubmittals received | | | 2/23/2001 | | DONE |
|
|
|
Received Small documents from Bruce Poe, forwarded same to Ron Hill. 2/23/01 DAR
|
BLD-Conference | 2/20/2001 | 2/20/2001 | 2/20/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/20/2001 10:53:22 AM w/ Ron H... met w/ arch, rec'd eng's insp reports as req'd, need verify in field for modifications
|
BLD-Conference | 2/12/2001 | 2/12/2001 | 2/12/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/12/2001 4:50:07 PM w/ Ron...need eng's reports
|
BLD-Conference | 2/7/2001 | 2/7/2001 | 2/7/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/7/2001 4:22:50 PM w/ contractor & Ron Hill onsit, verbal c/n : submit eng's & spec. insp. reports; need report for framing substitutions timberstrand for M>Lams, fasten joists added at south portion of bsmt
|
BLD-Conference | 1/22/2001 | 1/22/2001 | 1/22/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/22/2001 2:47:22 PM shell of Adelmann bldg, questions re: eng's reports (not sent?) configuration of select framing at basement/2nd fl...verify; need special insp reports for conc, etc
|
BLD-Foundation | 12/7/2000 | 12/8/2000 | 12/8/2000 | A | PART |
Carl Dependahl
|
|
|
reenforcing steel ###-####...south portion of reinforced slab; keyway & bar ok. abuts new ext fdn wall. 12/8/2000 10:52:23 AM
|
BLD-Foundation | 10/24/2000 | 10/24/2000 | 10/24/2000 | P | PART |
Jim Storey
|
|
|
Jim ###-#### rebaR OK FOUR CORNERS OF BASEMENT PENDING SPECIAL INSP. AND REPORT. 10/24/2000 4:52:08 PM
|
BLD-Footing | 9/14/2000 | 9/14/2000 | 9/14/2000 | P | PART |
|
|
|
FT INSP--TIM -###-#### fot the elevator shaft footing 9/14/2000 11:31:38 AM
|
BLD-Footing | 9/7/2000 | 9/8/2000 | 9/8/2000 | A | PART |
|
|
|
###-#### footings placed at this time ok to pour pending sp insp blessing 9/8/2000 10:47:51 AM
|
(F) Reprint permit | | | 9/6/2000 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 7/28/2000 | | 8/21/2000 | | PASS |
Ron Hill
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/21/2000 | | PASS |
Ron Hill
|
|
|
|
Inspection Record Card- Bld | | | 8/21/2000 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/21/2000 | | DONE |
|
|
|
|
Telephone call | | | 8/21/2000 | | DONE |
|
|
|
called Jim Cambell at ###-####
|
Issue PAID IN FULL permit | | | 8/21/2000 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 6/26/2000 | | 8/21/2000 | | PASS |
|
|
|
8/21/2000 09:05:41 RMH - activity updated through activity BLDA022 from case BLD00-01631.
|
Plan resubmittals received | | | 8/7/2000 | | DONE |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM COLE AND ASSOCIATES, BRUCE POE, SMALL DOCUMENTS AND A,S, P, AND E SHEETS. FORWARDED SAME TO RON HILL. 8/7/00 DAR
|
Routing - FIRE | 7/24/2000 | 7/27/2000 | 7/27/2000 | | PASS |
Bill Alexander
|
|
|
|
Plan Review Completed(1st rev) | | | 7/27/2000 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 7/17/2000 | | 7/24/2000 | | FAIL |
Ron Hill
|
|
|
ROUTE TO FIRE DEPARTMENT
|
Routing - PLAN CHECK | 7/18/2000 | | 7/24/2000 | | PEND |
|
|
|
|
Plan Reviewer's activity | | | 7/24/2000 | | FAIL |
Ron Hill
|
|
|
FAXED REQUIREMENTS TO ARCHITECT, ROUTE TO FIRE DEPARTMENT.
|
Routing Off Site - STRUCTURAL | 6/26/2000 | | 7/18/2000 | | PEND |
|
|
|
ROUTED REVISED DRAWING RECEIVED ON 6/26/00 TO OUTSIDE ENG. KMM
|
Routing - PLUMBING | 7/11/2000 | | 7/14/2000 | | PASS |
|
|
|
per plans and 97 upc
|
Plan resubmittals received | | | 7/13/2000 | | DONE |
|
|
|
RECEIVED THREE COPIES OF REVISED SHEETS S-0 AND S-3. THREE COPIES OF RESPONSE LETTER. ROUTED TO RON HILL. KMM
|
Routing - PLANNING | 6/28/2000 | | 7/11/2000 | | PASS |
|
|
|
Approved per building permit plans and as noted on sheet A.2 (P & Z note states that proposed guard rail is not approved and a new design must be reviewed and approved prior to occupancy).
|
Routing - PUBLIC WORKS | 6/26/2000 | | 6/28/2000 | | PASS |
|
|
|
|
Plan routing begun/TENANTS | | | 6/26/2000 | | DONE |
|
|
|
Route to PUBLIC WORKS, PLANNING, PLUMBING, PLAN CHECK and FIRE. Route to outside engineering.
|
Pending Assignment by MYS | 6/26/2000 | | 6/26/2000 | | DONE |
Marlene Southard
|
|
|
|
Plan resubmittals received | | | 6/26/2000 | | DONE |
|
|
|
RECEIVED THREE REVISED SETS OF PLANS WITH PLUMBING SHEETS P1.0 AND P2.0. ROUTED ONE COPY TO OUTSIDE ENG. AND TWO COPIES TO MARLENE. KMM
|
Plans ACCEPTED BY PLAN TECH | | | 6/26/2000 | | PEND |
|
|
|
STILL MISSING SOILS REPORT
|
Plans ACCEPTED BY PLAN TECH | | | 6/9/2000 | | HOLD |
|
|
|
REQUIRES 1. SOILS REPORT LISTED IN STRUCT. CALCS.
2. STAMPED AND SIGNED PLUMB. PLANS TWO COPIES
3. FULLY DIMENSIONED PLANS.
4. BUILDING CODE DATA
PLANS IN HOLD BOX. FAXED INFORMATION TO BRUCE POE. KMM
6/12/2000 SPOKE WITH BRUCE ABOUT ABOVE INFORMATION. KMM
|
Application received | | | 6/6/2000 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | | | |
|
|
|
|
Routing Off Site - STRUCTURAL | 6/9/2000 | | | | |
|
|
|
CONTACTED PDQ TO TAKE TO OUTSIDE ENG. KMM
|
Routing - PLAN CHECK | | | | | |
|
|
|
Plan Modification of 6/1/01
|