Case Summary (BLD) | | | 11/10/2005 | | |
|
|
|
|
Case Summary (BLD) | | | 2/23/2005 | | DONE |
|
|
|
|
BLD-Final | 11/5/2001 | 11/6/2001 | 11/6/2001 | A | PASS |
Carl Dependahl
|
|
|
###-#### call first; ok per plan modification. 11/6/2001 2:27:53 PM
|
Permanent Occupancy | | 11/6/2001 | 11/6/2001 | | DONE |
|
|
|
|
Permanent occupancy UNPAID FEE | | | 11/6/2001 | | DONE |
|
|
|
Perm. Occ. Cert. #8896 issued 11-6-01 to the Manhattan Grill Restaurant.
|
Fee Review-notes | 7/13/2000 | 7/13/2000 | 6/26/2001 | | DONE |
|
|
|
|
BLD-Final | 6/8/2001 | 6/8/2001 | 6/8/2001 | P | FAIL |
Carl Dependahl
|
|
|
temp occ-- kim ###-####--per carl put in for pm; c/n: signag 6/8/2001 2:36:58 PM , complete finish, shell & rooftop issues. ok for t/o, card to bldr modification6/8/2001 2:37:46 PM 6/8/2001 3:08:23 PM
|
FIRE-Final Inspection | 6/8/2001 | 6/8/2001 | 6/8/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 6/8/2001 1:59:54 PM
|
Temporary occupancy | | | 6/8/2001 | | PART |
|
|
|
Temp. Occ. Cert. #4556 issued 6-8-01 to the Manhattan Grill.
|
Inspection Record Card- Bld | | | 6/7/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/7/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/7/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/7/2001 | | DONE |
|
|
|
|
CHANGE STATUS TO (R) | | | 6/7/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/7/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Receive PAYMENT IN FULL PRINT | | | 6/7/2001 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 6/7/2001 | | DONE |
|
|
|
|
BLD-Final | 6/1/2001 | 6/5/2001 | 6/5/2001 | A | NR |
Carl Dependahl
|
|
|
Kim ###-####; need complete handrails, fire , etc. recall 6/5/2001 4:16:10 PM
|
FIRE-Final Inspection | 6/1/2001 | 6/5/2001 | 6/5/2001 | A | FAIL |
Rick Jackson
|
|
|
###-#### tested hood system okay; occupant load signs and extinguishers 6/5/2001 11:31:20 AM
|
Case Summary (BLD) | | | 6/5/2001 | | |
|
|
|
|
Plan Review Report | | | 6/5/2001 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 6/1/2001 | | 6/5/2001 | | PASS |
|
|
|
Plan modification of 6-1-01
|
Plans ACCEPTED BY PLAN TECH | | | 6/1/2001 | | DONE |
|
|
|
Plan modification
|
Override - Parcel Holds | | | 6/1/2001 | | |
|
|
|
|
Plan routing begun/TENANTS | | | 6/1/2001 | | DONE |
|
|
|
Plan modification. KMM
|
Override - Parcel Holds | | | 6/1/2001 | | |
|
|
|
|
Received Certificate of Value | | | 5/31/2001 | | DONE |
|
|
|
Plan modification
|
Plan Modification Accepted | | | 5/31/2001 | | DONE |
|
|
|
|
CHANGE STATUS TO (PND) | | | 5/31/2001 | | DONE |
|
|
|
PLAN MOD
|
BLD-Framing/Rough-in | 3/12/2001 | 3/12/2001 | 3/12/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 3/12/2001 3:09:18 PM wall panels ok...keep c/n re lid at bar
|
BLD-Framing/Rough-in | 3/9/2001 | 3/9/2001 | 3/9/2001 | P | PART |
Carl Dependahl
|
|
|
###-#### scene art wall panels ok; provide non comb backing at celing at bar 3/9/2001 4:49:56 PM
|
BLD-Framing/Rough-in | 3/5/2001 | 3/5/2001 | 3/5/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 3/5/2001 3:29:38 PM c/n re fireblocking & support at furred clg and prefab wall panels...submit info on mat'ls per plans. install 3/16 plywood over n.comb. matl...
|
BLD-Framing/Rough-in | 2/21/2001 | 2/21/2001 | 2/21/2001 | P | PART |
Carl Dependahl
|
|
|
###-#### extend shaft at bsmt, dampers to be installed; seal second "future" shaft. at bottom 2/22/2001 12:28:34 PM
|
BLD-Framing/Rough-in | 1/18/2001 | 1/18/2001 | 1/18/2001 | P | PART |
Carl Dependahl
|
|
|
###-#### SHAFT/ front of hvac shaft by elevator ok to cover; keep c/n re shaft at east side...need detail or dampers... 1/18/2001 2:23:56 PM
|
BLD-Framing/Rough-in | 1/10/2001 | 1/10/2001 | 1/10/2001 | P | FAIL |
Carl Dependahl
|
|
|
###-####, c/n for fireblocks at existing shaft, new shaft & lack of damper at penetrations 1/10/2001 3:42:27 PM
|
FIRE-Sprinkler Rough-in | 1/3/2001 | 1/3/2001 | 1/3/2001 | P | PART |
Rick Jackson
|
|
|
FIRE R/I KIM ###-#### 2nd floor okay 1/4/2001 7:59:42 AM
|
BLD-Framing/Rough-in | 1/2/2001 | 1/2/2001 | 1/2/2001 | P | PART |
Jim Storey
|
|
|
###-#### ok for cover pending reinsp on shafts and fire blk at ceilling line of unusable space at west wall. 1/2/2001 3:22:25 PM
|
FIRE-Conference | 12/22/2000 | 12/26/2000 | 12/26/2000 | A | PART |
Rick Jackson
|
|
|
KIM 941- 3664 FOR CONF// sprinkler heads required in shafts 12/26/2000 11:31:57 AM
|
BLD-Framing/Rough-in | 12/22/2000 | 12/22/2000 | 12/22/2000 | P | PART |
Carl Dependahl
|
|
|
R/I KIM -- ###-#### MEC CONNECTIONS IN BALLROOM CEILING JOIST ok to cover that area. need fire sprinkler analysis for existing shafts w/ exposed combustibles 12/22/2000 1:44:21 PM
|
BLD-Framing/Rough-in | 12/20/2000 | 12/21/2000 | 12/21/2000 | A | FAIL |
Carl Dependahl
|
|
|
R/I- KIM ###-#### ; need sprinkler r/i at "existing" shafts back of kitchen wall, (hvac from starbucks?) firestop floor/ceiling lines
12/21/2000 11:51:10 AM
|
BLD-Conference | 11/20/2000 | 11/21/2000 | 11/21/2000 | A | FAIL |
Carl Dependahl
|
|
|
###-####; need elec & other for "final" recall...address on Fulton per bldr. 11/21/2000 11:04:07 AM
|
BLD-Conference | 11/16/2000 | 11/17/2000 | 11/17/2000 | A | PART |
Carl Dependahl
|
|
|
KIM ###-#### FOR CONF
|
Telephone call | | | 10/17/2000 | | DONE |
|
|
|
evelyn grimes ###-####
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/11/2000 | | PASS |
Ron Hill
|
|
|
PLAN MODIFICATION TAKEN TO FRONT TO BE ISSUED.
|
Inspection Record Card- Bld | | | 10/11/2000 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/11/2000 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 9/25/2000 | | 10/11/2000 | | PASS |
|
|
|
10/11/2000 10:03:23 RMH - activity updated through activity BLDA022 from case BLD00-02025.
|
Case Summary (BLD) | | | 10/3/2000 | | DONE |
|
|
|
|
Routing - PLUMBING | 9/20/2000 | | 9/29/2000 | | PASS |
|
|
|
PLAN MODIFICATION rout dishwasher drain to grease line
|
Plans ACCEPTED BY PLAN CHECK | | | 9/20/2000 | | DONE |
|
|
|
PLAN MODIFICATION
|
Routing - PUBLIC WORKS | 9/20/2000 | | 9/20/2000 | | PASS |
|
|
|
PLAN MODIFICATION
|
Recd Pcfee & Taken To Pln CK | | | 9/18/2000 | | DONE |
|
|
|
PLAN MODIFICATION
|
Issue PAID IN FULL permit | | | 9/8/2000 | | DONE |
|
|
|
|
CHANGE ISSUED DATE | | | 9/8/2000 | | |
|
|
|
|
Routing - FIRE | 9/7/2000 | 9/7/2000 | 9/7/2000 | | PASS |
Bill Alexander
|
|
|
|
Case Summary (BLD) | | | 9/7/2000 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 9/7/2000 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/7/2000 | | PASS |
Ron Hill
|
|
|
|
Print Occupancy Form | | | 9/7/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 9/7/2000 | | DONE |
|
|
|
|
Telephone call | | | 9/7/2000 | | DONE |
|
|
|
called Evelyn at ###-#### permit ready for pickup
|
Plan assigned to (R_H) | 7/21/2000 | | 9/7/2000 | | PASS |
|
|
|
9/7/2000 14:51:45 RMH - activity updated through activity BLDA022 from case BLD00-02025.
|
Routing - PLAN CHECK | 8/31/2000 | | 9/7/2000 | | PASS |
Ron Hill
|
|
|
|
Plan resubmittals received | | | 9/5/2000 | | DONE |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM BRUCE POE, COLE ASSOCIATES, TWO SETS OF SHEETS A0.0 AND M2.1, FORWARDED SAME TO RON HILL. 9/5/00
|
Routing - FIRE | 8/24/2000 | 8/28/2000 | 8/30/2000 | | FAIL |
Bill Alexander
|
|
|
UFC 1103.3.3, UBC Chapter 8 verification required.
|
Plan Review Completed(1st rev) | | | 8/30/2000 | | FAIL |
|
|
|
|
Plan Reviewer's activity | | | 8/24/2000 | | FAIL |
Ron Hill
|
|
|
Faxed and mailed requirements to the Architect, route to fire department.
|
Routing - PLAN CHECK | 7/26/2000 | | 8/23/2000 | | FAIL |
Ron Hill
|
|
|
route to fire department.
|
Routing - PUBLIC WORKS | 7/21/2000 | | 7/26/2000 | | PASS |
|
|
|
|
Routing - PLUMBING | 7/26/2000 | | 7/26/2000 | | PASS |
|
|
|
|
Plan routing begun/TENANTS | | | 7/21/2000 | | DONE |
|
|
|
Route to PUBLIC WORKS, PLUMBING, PLAN CHECK and FIRE. Previously signed off Carol Johnson, Central District Health.
|
Pending Assignment by MYS | 7/21/2000 | | 7/21/2000 | | DONE |
Marlene Southard
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/17/2000 | | DONE |
|
|
|
|
Routing Off Site - C.D.H | 7/14/2000 | | 7/14/2000 | | PASS |
|
|
|
|
Application received | | | 7/13/2000 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 7/13/2000 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 9/29/2000 | | | | |
|
|
|
PLAN MODIFICATION
|
Routing - PUBLIC WORKS | 6/1/2001 | | | | |
|
|
|
Plan modification
|
Routing - PLAN CHECK | | | | | |
|
|
|
Plan modification.
|