Fee Review-notes | 7/26/2000 | 7/26/2000 | 4/17/2002 | | DONE |
|
|
|
|
Permanent occupancy | | | 3/11/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9060 issued 3-11-02 to Micron for their two story facilities maintenance shop.
|
Permanent Occupancy | | 3/4/2002 | 3/4/2002 | | DONE |
|
|
|
|
BLD-Final | 3/1/2002 | 3/4/2002 | 3/4/2002 | A | PASS |
Jim Storey
|
|
|
Scheduled by Inspector: 407 On 3/1/2002 11:26:04 AM final ok for c.o. 3/4/2002 2:52:12 PM
|
BLD-Final | 2/28/2002 | 3/1/2002 | 3/1/2002 | A | CANC |
Russ Owen
|
|
|
###-#### John ,I called left message to call me back I have set this back up for am monday.1/2002 11:51:03 AM 3/1/2002 11:54:03 AM
|
BLD-Final | 2/20/2002 | 2/21/2002 | 2/21/2002 | A | FAIL |
Jim Storey
|
|
|
###-#### DON fire stopping needed at plm. 2/21/2002 9:20:13 AM
|
FIRE-Final Inspection | 1/31/2002 | 2/1/2002 | 2/1/2002 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/31/2002 at 08:03:29. Contact: ###-####.
|
BLD-Final | 1/31/2002 | 2/1/2002 | 2/1/2002 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 01/31/2002 at 08:04:18. Contact: ###-####. recieved engineers approval letter and special insp approval. ok for temp. 2/1/2002 2:41:28 PM
|
Temporary occupancy | | | 2/1/2002 | | PART |
|
|
|
Temp. Occ. Cert. #4716 issued 2-1-02 to Micron Technology, Bldg. #35.
|
FIRE-Final Inspection | 1/17/2002 | 1/17/2002 | 1/17/2002 | A | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 1/17/2002 11:01:35 AM need exit signs on second floor; sprinkler certification paperwork; tested alarms - okay with monor corections
|
BLD-Conference | 11/15/2001 | 11/16/2001 | 11/16/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 11/15/2001 at 10:55:35. Contact: ###-####. fire shudder test req/ fire stop top of corridor walls south east exit. pending all other trades. need engineers sign off and special insp. final letter. 11/16/2001 11:02:24 AM
|
BLD-Conference | 11/15/2001 | 11/19/2001 | 11/15/2001 | A | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 11/15/2001 at 10:34:15. Contact: . Disp set to [CANC] by a contractor via Hello! on 11/15/2001 at 10:54:16.
|
BLD-Final | 10/30/2001 | 11/5/2001 | 11/1/2001 | A | CANC |
Jim Storey
|
|
|
###-#### Disp set to [CANC] by a contractor via Hello! on 11/01/2001 at 14:37:43.
|
FIRE-Final Inspection | 10/29/2001 | 11/1/2001 | 11/1/2001 | A | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/29/2001 at 14:46:09. Contact: ###-####. will reschedule 10/31/2001 5:07:37 PM
|
BLD-Conference | 10/18/2001 | 10/19/2001 | 10/19/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/18/2001 at 14:46:29. Contact: ###-####.
|
BLD-Other | 9/17/2001 | 9/18/2001 | 9/18/2001 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/17/2001 at 12:59:16. Contact: ###-####. 2 nd floor ceilling/ need speader bars. 9/18/2001 10:40:59 AM
|
BLD-Other | 9/5/2001 | 9/7/2001 | 9/7/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/05/2001 at 15:22:43. Contact: ###-####. south 1/2 ceilling ok. 9/10/2001 5:54:47 PM
|
BLD-Framing/Rough-in | 8/8/2001 | 8/9/2001 | 8/9/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/08/2001 at 09:42:32. Contact: ###-####. hard ceilling at west dock beams protccted and support grid ok for cover/ grid ceilling 2 nd floor work in progess no problems. 8/9/2001 11:39:12 AM
|
(F) Reprint permit | | | 8/3/2001 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 7/9/2001 | 7/10/2001 | 7/10/2001 | A | PASS |
Jim Storey
|
|
|
Jualo ###-####
|
BLD-Framing/Rough-in | 5/16/2001 | 5/17/2001 | 5/17/2001 | A | PASS |
Jim Storey
|
|
|
Hulo ###-#### 1 & 2nd floor framing ok for cover / arch to address west stair for opening protection. 5/17/2001 9:50:16 AM
|
BLD-Framing/Rough-in | 5/10/2001 | 5/14/2001 | 5/14/2001 | A | PASS |
Jim Storey
|
|
|
###-#### 2nd floor ok for cover. 5/14/2001 4:34:15 PM
|
BLD-Framing/Rough-in | 5/3/2001 | 5/8/2001 | 5/8/2001 | A | FAIL |
Jim Storey
|
|
|
Jullo ###-#### c/n for rfi to arch. 5/8/2001 1:03:24 PM
|
BLD-Framing/Rough-in | 5/1/2001 | 5/3/2001 | 5/3/2001 | A | PART |
Steven Webb
|
|
|
julio-- ###-#### fr Partial--Building 35-2nd floor offices at east and west end. 5/3/2001 9:55:27 AM
|
BLD-Framing/Rough-in | 4/16/2001 | 4/16/2001 | 4/16/2001 | P | PART |
Jim Storey
|
|
|
###-#### fur out walls ok for cover / c/n for out standing special insp. issues. 4/16/2001 6:31:30 PM
|
BLD-Framing/Rough-in | 3/14/2001 | 3/15/2001 | 3/15/2001 | A | PART |
Jim Storey
|
|
|
###-#### diaphram roof welds ok south end. reviewed col/fire assemblie/ 3/15/2001 4:37:51 PM
|
BLD-Framing/Rough-in | 3/12/2001 | 3/13/2001 | 3/13/2001 | A | FAIL |
Jim Storey
|
|
|
WELDING ON ROOF AND FLOOR DECKING\\###-#### missing welds and botton punching on roof and 2 nd floor / special insp need to verify when corected. 3/13/2001 10:18:49 AM
|
BLD-Other | 2/28/2001 | 2/28/2001 | 2/28/2001 | | FAIL |
Jim Storey
|
|
|
special insp report feb 16 2001. tilt panels 14,15,16,20,22,23 air spec. 4% to 7% test results were 2% need engineer of record to justify not meetting freeze protection provision and design spec.
|
BLD-Foundation | 1/18/2001 | 1/18/2001 | 1/18/2001 | P | PART |
Jim Storey
|
|
|
re-bar julio ###-#### placed with special insp. pending report. 1/18/2001 4:14:29 PM
|
BLD-Framing/Rough-in | 1/4/2001 | 1/5/2001 | 1/5/2001 | P | PART |
Jim Storey
|
|
|
REBAR JULIO-- ###-#### placed with special insp. pending report. 1/8/2001 7:57:48 AM
|
BLD-Other | 12/29/2000 | 12/29/2000 | 12/29/2000 | A | FAIL |
Bill VanDegrift
|
|
|
Added by Inspector: 330 On 12/29/2000 3:57:54 PM left correction notice - secure a permit for sewer and water lines relocated outside the building, provide documentation from micron reguarding testing and inspection for determination of code compliance, - secure a licensed plumbing contractor to permit 10" storm drain under the building apply test and call for inspection- do not lay asphalt over exterior piping or concrete over interior storm drain untill all waor has been approved for cover.
|
BLD-Footing | 12/21/2000 | 12/22/2000 | 12/22/2000 | A | PART |
Carl Dependahl
|
|
|
Garry ###-####; pend spec. insp reports 12/22/2000 10:14:24 AM
|
BLD-Footing | 12/14/2000 | 12/15/2000 | 12/15/2000 | A | NR |
Jim Storey
|
|
|
###-####
|
BLD-Foundation | 12/13/2000 | 12/13/2000 | 12/13/2000 | P | PART |
Jim Storey
|
|
|
###-#### REBAR placed with special insp. 12/13/2000 4:43:04 PM
|
BLD-Foundation | 12/5/2000 | 12/5/2000 | 12/5/2000 | P | PART |
Jim Storey
|
|
|
###-#### work in progess covered with s/i 12/5/2000 3:34:36 PM
|
FIRE-Final Inspection | 11/27/2000 | 11/28/2000 | 11/28/2000 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/27/2000 at 14:55:29. Contact: ###-####.//// entered by contractor in error 11/28/2000 3:22:58 PM
|
BLD-Footing | 11/27/2000 | 11/28/2000 | 11/28/2000 | P | PART |
Jim Storey
|
|
|
###-#### p/w/s/i/ pending report. 11/28/2000 3:49:21 PM
|
(F) Reprint permit | | | 10/16/2000 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/13/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 10/13/2000 | | DONE |
|
|
|
|
Telephone call | | | 10/13/2000 | | DONE |
|
|
|
emailed permit ready
|
Issue & PRINT permit | | | 10/13/2000 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/12/2000 | | DONE |
|
|
|
RECEIVED TWO COPIES OF REVISED SHEETS O, C1.1, C2.0, A0.2, A0.3, A2.1.3, A3.2.1, A4.3.1 ROUTED TO JOHN M. KMM
|
Plan Reviewer's activity | | | 10/12/2000 | | PASS |
|
|
|
REVIEWED AND APPROVED FINAL PLAN RESUBMITTALS. JCM
|
Routing - FIRE | 10/12/2000 | | 10/12/2000 | | PASS |
|
|
|
Resubmittal acceptable
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/12/2000 | | PASS |
|
|
|
|
Plan assigned to (JCM) | 7/27/2000 | | 10/12/2000 | | PASS |
John Menard
|
|
|
10/12/00 16:02:25 JCM - activity updated through activity BLDA022 from case BLD00-02170.
|
Routing Off Site - STRUCTURAL | 8/25/2000 | | 10/12/2000 | | PASS |
|
|
|
ROUTED REVISED PLANS TO OUTSIDE ENG. KMM RECEIVED AN E-MAIL FROM THE CONSULTING STRUCTURAL ENGINEER APPROVING THE STRUCTURAL RESUBMITTALS. JCM
|
Routing - FIRE | 10/10/2000 | | 10/11/2000 | | FAIL |
|
|
|
|
Plan resubmittals received | | | 10/11/2000 | | DONE |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM ZGA ARCHITECTS SMALL DOCUMENTS AND TWO SETS OF SHEET C1.1 AND C2.0, FORWARDED SAME TO JOHN MENARD. 10/11/00 DAR
|
Routing - PLAN CHECK | 10/9/2000 | | 10/10/2000 | | |
|
|
|
|
Routing - FIRE | 10/5/2000 | | 10/9/2000 | | FAIL |
|
|
|
Resubmittal does not address the 9/15/2000 Fire Review comments. Spoke with Frank Kvapil and Jared Hetherington 10/9. They will fax a written response and will re-submit C2.0 showing gate at NE corner to provide required access.
|
Plan resubmittals requested | | | 10/5/2000 | | |
|
|
|
REVIEWED RESUBMITTED PLAN SHEETS AND MAILED RON MOSS AT ZGA A LETTER REQUESTING ADDITIONAL REVISIONS. JCM
|
Routing - PLAN CHECK | 9/18/2000 | | 10/5/2000 | | |
|
|
|
|
Plan resubmittals received | | | 10/3/2000 | | DONE |
|
|
|
RECEIVED PLAN RESUBMITTALS FROM ZGA , FORWARDED SAME TO JOHN MENARD. 10/3/00 DAR
|
Plan Reviewer's activity | | | 9/22/2000 | | FAIL |
|
|
|
REVIEWED RESPONSE LETTER FROM ARCHITECT OF RECORD AND RESPONSED WITH A LETTER TO THE ARCHITECT AGAIN REQUESTING THE REQUIRED RESUBMITTALS. JCM
|
Plan Review Completed(1st rev) | | | 9/15/2000 | | FAIL |
|
|
|
Not approved by Bldg and failed Fire review.
|
Routing - FIRE | 9/8/2000 | | 9/15/2000 | | FAIL |
|
|
|
faxed comments to architect
|
Plan resubmittals received | | | 9/14/2000 | | DONE |
|
|
|
RECEIVED TWO COPIES OF RESPONSE TO PLAN REVIEW. NONE OF THE COMMENTS HAVE DRAWING REVISIONS. ALL RESPONSES ARE IN WRITTEN FORM. ROUTED TO JOHN M. KMM
|
Routing - PLAN CHECK | 8/25/2000 | | 9/8/2000 | | FAIL |
|
|
|
|
Plan resubmittals requested | | | 9/8/2000 | | |
|
|
|
MAILED THE ARCHITECT OF RECORD A COPY OF THE COMMENT LIST REQUESTING REVISIONS. JCM
|
Plan resubmittals received | | | 8/25/2000 | | |
|
|
|
1 COPY OF STRUCTURAL PLAN REVIEW RESPONSE LETTER
3 COPIES STRUCTURAL CALCULATION-SUPPLEMENT
3 COPIES STRUCTURAL DRAWINGS-REVISED S2.1 S2.2 S2.3 S3..1 S3.2 S4.1 S4.2 S5.1 S5.2 S5.2.1 S5.5 S5.6 S6.7/TAKEN TO JOHN M
|
Routing - PLUMBING | 8/18/2000 | | 8/25/2000 | | PASS |
|
|
|
per plans and 97 upc
|
Routing Off Site - STRUCTURAL | 7/27/2000 | | 8/18/2000 | | FAIL |
|
|
|
CONTACTED PDQ TO TAKE PLANS TO OUTSIDE ENG. KMM RECEIVED COMMENT LIST FROM CONSULTING STRUCTURAL ENGINEER REQUESTING REVISIONS. JCM
|
Plan resubmittals requested | | | 8/18/2000 | | |
|
|
|
FAXED A COPY OF THE CONSULTING ENGINEER'S COMMENT LIST TO FRANK KVAPIL AND PAUL MARCOLINA REQUESTING REVISIONS. JCM
|
Routing - PLANNING | 8/3/2000 | | 8/18/2000 | | PASS |
|
|
|
NO DESIGN REVIEW REQUIRED PER T-2 ORDINANCE
|
Plan resubmittals received | | | 8/10/2000 | | |
|
|
|
RECIVED 5 COPIES OF RIVISED P2.1.2. BLUELINES 8/10/2000/PE
|
Routing - PUBLIC WORKS | 7/27/2000 | | 8/3/2000 | | PASS |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 7/27/2000 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/27/2000 | | DONE |
|
|
|
DID NOT RECEIVE DRAINAGE CALCS. LET BRIAN DEAL WITH IT. KMM
|
Received Certificate of Value | | | 7/27/2000 | | DONE |
|
|
|
|
Application received | | | 7/26/2000 | | |
|
|
|
|