Case Summary (BLD) | | | 11/10/2005 | | |
|
|
|
|
Case Summary (BLD) | | | 2/18/2003 | | |
|
|
|
|
Permanent occupancy | | | 10/15/2001 | | DONE |
|
|
|
Perm. Occ. Cert. #8872 issued 10-15-01 to Quizno's.
|
BLD-Final | 10/11/2001 | 10/12/2001 | 10/12/2001 | A | PART |
Carl Dependahl
|
|
|
ok for c/o pending all other signatures... 10/12/2001 11:35:25 AM
|
Permanent Occupancy | | 10/12/2001 | 10/12/2001 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 10/11/2001 | | DONE |
|
|
|
pd in full -changed status/mls
|
BLD-Conference | 6/8/2001 | 6/8/2001 | 6/8/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/8/2001 2:36:16 PM ok for t/o keep c/n...shell & rooftop issues
|
Inspection Record Card- Bld | | | 6/7/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/7/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/7/2001 | | DONE |
|
|
|
left mess that permit is ready
|
CHANGE STATUS TO (FEE) | | | 6/7/2001 | | DONE |
|
|
|
|
CHANGE STATUS TO (R) | | | 6/7/2001 | | DONE |
|
|
|
|
Receive PAYMENT IN FULL PRINT | | | 6/7/2001 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 6/1/2001 | | 6/5/2001 | | PASS |
|
|
|
Plan modification
|
Case Summary (BLD) | | | 6/5/2001 | | DONE |
|
|
|
|
Plan routing begun/TENANTS | | | 6/1/2001 | | DONE |
|
|
|
plan modification. kmm
|
Plans ACCEPTED BY PLAN TECH | | | 6/1/2001 | | DONE |
|
|
|
Plan modification
|
BLD-Final | 5/31/2001 | 5/31/2001 | 5/31/2001 | P | PART |
Carl Dependahl
|
|
|
Kim ###-####; ok for t/o only, c/n w bld00-01631 5/31/2001 11:28:36 AM
|
Plan Modification Accepted | | | 5/31/2001 | | DONE |
|
|
|
|
CHANGE STATUS TO (PND) | | | 5/31/2001 | | DONE |
|
|
|
PLAN MOD
|
Received Certificate of Value | | | 5/31/2001 | | DONE |
|
|
|
Plan modification
|
Case Summary (BLD) | | | 5/31/2001 | | DONE |
|
|
|
|
BLD-Conference | 5/30/2001 | 5/30/2001 | 5/30/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/30/2001 1:25:57 PM need all shell issues( OBTAIN T/O) for t/i final
|
BLD-Final | 5/25/2001 | 5/29/2001 | 5/29/2001 | A | FAIL |
Carl Dependahl
|
|
|
need shell ok'd, 5/30/2001 1:38:35 PM
|
Plan resubmittals received | | | 5/29/2001 | | DONE |
|
|
|
Received plan resubmittals from Cole Architects 4 sheets of A1.0 and two sheets of A2.0, forwarded same to Ron Hill. 5/29/01 DAR
|
BLD-Conference | 5/24/2001 | 5/24/2001 | 5/24/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/24/2001 8:00:10 AM w/ bldr re final...chk w/ mgmt...
|
BLD-Conference | 5/21/2001 | 5/21/2001 | 5/21/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/21/2001 2:25:50 PM left red tag, do not occupy til p&z ok
|
BLD-Final | 4/27/2001 | 4/27/2001 | 4/27/2001 | P | NR |
Carl Dependahl
|
|
|
###-####
|
BLD-Framing/Rough-in | 3/28/2001 | 3/28/2001 | 3/28/2001 | P | PASS |
Jim Storey
|
|
|
ceiling grid-- kim ###-####
|
BLD-Framing/Rough-in | 2/26/2001 | 2/27/2001 | 2/27/2001 | A | PART |
Carl Dependahl
|
|
|
###-####, pend specinsp report re new opening in exist masonry..appears ok. ok to cover walls at kitch./ dining pend other insps 2/27/2001 3:05:56 PM
|
BLD-Conference | 2/21/2001 | 2/22/2001 | 2/22/2001 | A | PASS |
Carl Dependahl
|
|
|
re 1hr demising wall at existing tenant, ok to leave window if 1hr const. is continuous behind at "corridor" 2/22/2001 12:26:39 PM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/16/2001 | | PASS |
Ron Hill
|
|
|
|
Routing - PLAN CHECK | 12/15/2000 | | 2/15/2001 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 12/7/2000 | | 2/15/2001 | | PASS |
|
|
|
2/15/2001 14:42:23 RMH - activity updated through activity BLDA022 from case BLD00-02390.
|
Plan Review Report | | | 2/6/2001 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 2/6/2001 | | DONE |
|
|
|
|
Plan Reviewer's activity | | | 2/5/2001 | | PEND |
Ron Hill
|
|
|
Routed to public works for the additional seating added. RMH
|
Plan resubmittals received | | | 2/1/2001 | | |
|
|
|
|
BLD-Conference | 1/10/2001 | 1/10/2001 | 1/10/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/10/2001 3:44:30 PM c/n re shaft/ s.f. dampers
|
BLD-Framing/Rough-in | 12/28/2000 | 12/29/2000 | 12/29/2000 | A | PASS |
Bob Archibald
|
|
|
Previos corrections made ok.
|
BLD-Framing/Rough-in | 12/28/2000 | 12/28/2000 | 12/28/2000 | P | FAIL |
Carl Dependahl
|
|
|
Framing in kitchen area, tenant demising wall, and furr out along east wall require fireblocking and firestopping before cover.
|
Routing - FIRE | 12/11/2000 | | 12/15/2000 | | PASS |
Ron Hill
|
|
|
Plan nodification. Approved with no change to original review dated 9/22/000.
|
Plan Reviewer's activity | | | 12/11/2000 | | FAIL |
Ron Hill
|
|
|
Plan modification failed need structural Calculations. Route to fire department for review. Faxed requirements to the architect.
|
Case Summary (BLD) | | | 12/11/2000 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 12/7/2000 | | 12/11/2000 | | FAIL |
Ron Hill
|
|
|
PLAN MODIFICATION
|
Routing - PUBLIC WORKS | 12/7/2000 | | 12/7/2000 | | PASS |
|
|
|
PLAN MODIFICATION
|
CHANGE STATUS TO (PND) | | | 12/4/2000 | | DONE |
|
|
|
ACCPETED PLAN MODIFICATION FEE $500 12-4-00
|
Print Occupancy Form | | | 9/26/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 9/26/2000 | | DONE |
|
|
|
|
Telephone call | | | 9/26/2000 | | DONE |
|
|
|
called permit ready and fees due
|
Issue PAID IN FULL permit | | | 9/26/2000 | | DONE |
|
|
|
|
CHANGE ISSUED DATE | | | 9/26/2000 | | |
|
|
|
|
Plan assigned to (R_H) | 8/23/2000 | | 9/25/2000 | | PASS |
|
|
|
9/25/2000 09:59:47 RMH - activity updated through activity BLDA022 from case BLD00-02390.
|
Routing - PLAN CHECK | 9/22/2000 | | 9/25/2000 | | PASS |
Ron Hill
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/25/2000 | | PASS |
Ron Hill
|
|
|
|
Routing - FIRE | 9/20/2000 | | 9/22/2000 | | PASS |
Ron Hill
|
|
|
|
Plan Review Completed(1st rev) | | | 9/22/2000 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 9/20/2000 | | PASS |
Ron Hill
|
|
|
No Correctons Required, Route to fire department for approvals
|
Routing - PLAN CHECK | 8/29/2000 | | 9/20/2000 | | PEND |
Ron Hill
|
|
|
|
Routing - PLUMBING | 8/24/2000 | | 8/29/2000 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 8/23/2000 | | 8/24/2000 | | PASS |
|
|
|
|
Pending Assignment by MYS | 8/23/2000 | | 8/23/2000 | | DONE |
Marlene Southard
|
|
|
|
Plan routing begun/TENANTS | | | 8/23/2000 | | DONE |
|
|
|
Route to PUBLIC WORKS, PLUMBING, PLAN CHECK and FIRE.
|
Plans ACCEPTED BY PLAN TECH | | | 8/16/2000 | | DONE |
|
|
|
|
Received Certificate of Value | | | 8/10/2000 | | DONE |
|
|
|
|
Application received | | | 8/10/2000 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 8/10/2000 | | DONE |
|
|
|
|
Routing - PUBLIC WORKS | 6/1/2001 | | | | |
|
|
|
Plan modification
|
Routing - PLAN CHECK | | | | | |
|
|
|
Plan modification. kmm
|