Case Summary (BLD) | | | 7/18/2002 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 7/18/2002 | | DONE |
|
|
|
|
(F) Reprint permit | | | 7/18/2002 | | DONE |
|
|
|
|
Permanent occupancy UNPAID FEE | | | 3/12/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9064 issued 3-12-02 to Micron Technology, Inc. Bldgs. #24D & #24E.
|
BLD-Final | 3/11/2002 | 3/11/2002 | 3/11/2002 | P | PASS |
Jim Storey
|
|
|
Added by Inspector: 301 On 3/11/2002 3:04:52 PM final ok
|
Permanent Occupancy | | 3/11/2002 | 3/11/2002 | | DONE |
|
|
|
|
BLD-Conference | 3/5/2002 | 3/6/2002 | 3/6/2002 | A | PART |
Jim Storey
|
|
|
walk through list of c/n idems and sign offs required. 3/6/2002 2:48:22 PM
|
FIRE-Final Inspection | 2/20/2002 | 2/20/2002 | 2/20/2002 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 2/20/2002 4:18:37 PM
|
Conference | 2/12/2002 | 2/12/2002 | 2/12/2002 | | DONE |
|
|
|
Temp. Occ. Cert. ext. thru 4-11-02 per Tim Hogland.
|
BLD-Conference | 1/3/2002 | 1/4/2002 | 1/4/2002 | A | PART |
Jim Storey
|
|
|
###-#### e 1st fl. restarooms,lockerrm/synthesis rm and clean bench ok for temp occ. 1/7/2002 9:36:10 AM
|
Temporary occupancy | | | 12/26/2001 | | PART |
|
|
|
Temp. Occ. Cert. #4692 issued 12-26-01 to Micron Technology, Inc.
|
BLD-Conference | 12/17/2001 | 12/18/2001 | 12/18/2001 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 12/17/2001 at 13:37:22. Contact: ###-####. basement ok fire stop at grade level west ele penatations. 12/19/2001 11:33:52 AM
|
BLD-Final | 11/10/2001 | 11/10/2001 | 11/10/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by Inspector: 301 On 11/10/2001 8:33:22 AM temp occ. ok for area of modified scope of work on file. must maintain egress coridors for opening protection and width for egress. per agreement for occ.on file with city with plan review. 11/10/2001 10:19:51 AM
|
FIRE-Final Inspection | 11/13/2001 | 11/10/2001 | 11/10/2001 | A | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/13/2001 7:15:11 AM okay to occupy bldg 24D only; Micron to finsish work in gas bunker
|
BLD-Wall cover | 11/7/2001 | 11/7/2001 | 11/7/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 11/07/2001 at 07:21:35. Contact: ###-####. wip 11/8/2001 3:59:14 PM
|
(F) Reprint permit | | | 11/7/2001 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 11/5/2001 | 11/6/2001 | 11/6/2001 | P | PASS |
Jim Storey
|
|
|
###-#### HUGO ARCHITECTURAL FIRE fire stopping ok at 2 hr and 4 hr process piping penatrations. 11/8/2001 3:56:52 PM
|
FIRE-Conference | 11/5/2001 | 11/5/2001 | 11/5/2001 | A | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 11/5/2001 10:39:52 AM checked operation of blast doors at bunker; all shipping screws removed and tested the operation - all okay
|
BLD-Conference | 11/2/2001 | 11/5/2001 | 11/5/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 11/02/2001 at 09:53:47. Contact: ###-####. wip. 11/6/2001 12:52:02 PM
|
FIRE-Final Inspection | 11/1/2001 | 11/2/2001 | 11/2/2001 | A | CANC |
Rick Jackson
|
|
|
###-#### HUGO wrong type of inspection called in 11/2/2001 10:00:09 AM
|
FIRE-Conference | 11/2/2001 | 11/2/2001 | 11/2/2001 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/02/2001 at 06:21:50. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 11/02/2001 at 06:23:53.
|
FIRE-Conference | 11/2/2001 | 11/2/2001 | 11/2/2001 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/02/2001 at 06:29:58. Contact: ###-####. talked to hugo and he said to disregard this request 11/2/2001 10:00:35 AM
|
BLD-Conference | 10/31/2001 | 11/1/2001 | 11/1/2001 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 10/31/2001 at 14:38:52. Contact: ###-####. 4hr wall penetration needs 1/4 strip past sheetrock. 11/2/2001 8:22:26 AM
|
BLD-Final | 11/1/2001 | 11/1/2001 | 11/1/2001 | P | PART |
Russ Owen
|
|
|
###-#### hugo. 4hr wall missing collar at west side . location basement. 11/2/2001 11:02:13 AM
|
BLD-Wall cover | 10/30/2001 | 10/30/2001 | 10/30/2001 | A | NR |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 10/30/2001 at 05:53:31. Contact: ###-####. Above restroom 3 pipes req fire stoping will verify by access above retroom ceiling pipes approx 5 from access hatch. 10/30/2001 11:05:20 AM
|
BLD-Wall cover | 10/29/2001 | 10/29/2001 | 10/29/2001 | A | PART |
Russ Owen
|
|
|
Scheduled by Inspector: 407 On 10/29/2001 10:51:17 AM . Ok to place ceiling tile at main floor only. 10/29/2001 10:54:16 AM
|
BLD-Wall cover | 10/26/2001 | 10/26/2001 | 10/26/2001 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 10/26/2001 at 06:32:16. Contact: ###-####.. Will recall. 10/26/2001 1:49:32 PM
|
FIRE-Conference | 10/25/2001 | 10/25/2001 | 10/25/2001 | P | PART |
Rick Jackson
|
|
|
FIRE STOPS PENATRATION HUGO ###-#### okay to proceed with cover; insulation installed 10/25/2001 4:10:28 PM
|
FIRE-Conference | 10/24/2001 | 10/24/2001 | 10/24/2001 | P | PART |
Jim Storey
|
|
|
fire penatration wall hazzards bunk walk hugo ###-#### 1/2 of assemblie ok to proceed with closer. 10/24/2001 2:42:40 PM
|
BLD-Conference | 10/23/2001 | 10/23/2001 | 10/23/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/23/2001 at 07:15:14. Contact: ###-####. c/n posted. 10/23/2001 5:00:52 PM
|
BLD-Wall cover | 10/23/2001 | 10/23/2001 | 10/23/2001 | P | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/23/2001 at 11:02:16. Contact: ###-####.
|
BLD-Other | 10/23/2001 | 10/23/2001 | 10/23/2001 | A | PART |
Jim Storey
|
|
|
Added by Inspector: 301 On 10/23/2001 11:58:52 AM chem tray fire stopping assemblies at fab/ basement chem distrution rooms ok./ pending 4 hr north / fab west stainless steel at cat walk assemblie ok to continue.
|
BLD-Conference | 10/16/2001 | 10/17/2001 | 10/17/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/16/2001 at 09:38:20. Contact: ###-####. stair inclosers to have all other idems incapsulated from this inviroment. 10/17/2001 3:18:13 PM
|
Inspection Record Card- Bld | | | 10/16/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/16/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/16/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/15/2001 | | |
|
|
|
|
BLD-Conference | 10/9/2001 | 10/9/2001 | 10/9/2001 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/09/2001 at 07:39:40. Contact: ###-####. c/n posted. 10/10/2001 3:38:11 PM
|
BLD-Wall cover | 10/5/2001 | 10/5/2001 | 10/5/2001 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/05/2001 at 08:51:26. Contact: ###-####. east hpm corridor ok for ceilling 4 hr north to drum unload rm. 10/5/2001 4:26:57 PM
|
BLD-Framing/Rough-in | 10/3/2001 | 10/3/2001 | 10/3/2001 | P | PART |
Jim Storey
|
|
|
tony ###-#### r/i conf to review fire stopping assemblies and insp. 10/4/2001 3:56:03 PM
|
BLD-Wall cover | 10/2/2001 | 10/2/2001 | 10/2/2001 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 10/02/2001 at 06:09:10. Contact: ###-####. dock stair well to fan deck need horrizontal bar welded before cover. 10/2/2001 3:00:18 PM
|
BLD-Wall cover | 9/26/2001 | 9/27/2001 | 9/27/2001 | A | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/26/2001 at 07:21:02. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 09/27/2001 at 05:07:57.
|
BLD-Wall cover | 9/27/2001 | 9/27/2001 | 9/27/2001 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/27/2001 at 05:06:22. Contact: ###-####. basement ceilling/ south fur out wall north side. 9/27/2001 6:27:05 PM
|
BLD-Framing/Rough-in | 9/24/2001 | 9/25/2001 | 9/25/2001 | A | PART |
Jim Storey
|
|
|
r/i- xenon-- ###-#### reviewed fire stopping of areas to be done by YMC work to begin soon. 9/25/2001 4:50:28 PM
|
BLD-Wall cover | 9/21/2001 | 9/24/2001 | 9/24/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/21/2001 at 14:43:02. Contact: ###-####. occ wall at sub-fab into ele room openings not protected/ h3 drum unload floor openings unprotcted. 9/24/2001 4:09:16 PM
|
BLD-Wall cover | 9/14/2001 | 9/17/2001 | 9/17/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/14/2001 at 12:43:19. Contact: ###-####. ceilling at gas bunker corridor ok to start./ tenp power fan deck and di water 4 hr wall hold those areas as well as floor safe assemblie/west wall ok for cover fab level/south 4 hr patch in ok for cover above gas rm corridor south side. 9/17/2001 1:03:37 PM
|
BLD-Wall cover | 9/13/2001 | 9/13/2001 | 9/13/2001 | A | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/13/2001 at 07:11:30. Contact: ###-####.
|
BLD-Wall cover | 9/11/2001 | 9/12/2001 | 9/12/2001 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/11/2001 at 13:56:44. Contact: ###-####.
|
BLD-Wall cover | 9/7/2001 | 9/7/2001 | 9/7/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/07/2001 at 06:12:25. Contact: ###-####. done prevously 9/7/2001 1:52:47 PM
|
BLD-Wall cover | 9/6/2001 | 9/6/2001 | 9/6/2001 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/06/2001 at 09:12:32. Contact: ###-####. 2 hr grade chem rm north. 9/7/2001 1:52:15 PM
|
BLD-Wall cover | 9/5/2001 | 9/5/2001 | 9/5/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 09/05/2001 at 06:46:29. Contact: ###-####. c/n 9/5/2001 12:55:18 PM Scheduled by a c/ncontractor via Hello! on 09/05/2001 at 06:46:29. Contact: ###-####. c/n 9/5/2001 12:55:18 PM 9/5/2001 3:11:00 PM
|
BLD-Conference | 8/28/2001 | 8/28/2001 | 8/28/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/28/2001 at 06:17:16. Contact: ###-####. working on fire door listing. 8/28/2001 4:36:08 PM
|
BLD-Conference | 8/27/2001 | 8/27/2001 | 8/27/2001 | P | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/27/2001 at 09:18:28. Contact: ###-####.
|
BLD-Wall cover | 8/16/2001 | 8/17/2001 | 8/17/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/16/2001 at 08:51:14. Contact: ###-####. c/n posted on site/ damper in basement ok at 2 hr chem rm wall configuation resolved ok for cover. 8/17/2001 12:30:42 PM
|
BLD-Wall cover | 8/16/2001 | 8/16/2001 | 8/16/2001 | P | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/16/2001 at 08:47:40. Contact: ###-####.
|
BLD-Wall cover | 8/15/2001 | 8/15/2001 | 8/15/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/15/2001 at 06:21:34. Contact: ###-####. 2 hr wall at 36 cafateria to fab tube steel incapsulated c/n this idem ok/ basement fire collors at chem room 2-2'' emt instalation ok c/n idem ok. 8/15/2001 11:45:32 AM
|
BLD-Wall cover | 8/10/2001 | 8/10/2001 | 8/10/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/10/2001 at 05:35:11. Contact: ###-####. pipe penatrations basement not per listing8/10/2001 4:55:44 PM 8/10/2001 4:55:58 PM
|
BLD-Wall cover | 8/8/2001 | 8/8/2001 | 8/8/2001 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/08/2001 at 07:52:42. Contact: ###-####. basement chem rooms firestopping ok pending engineered judgments for 2 locations/ 8/9/2001 10:49:19 AM
|
BLD-Conference | 8/7/2001 | 8/7/2001 | 8/7/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/07/2001 at 06:37:37. Contact: ###-####. approved detail for corridor 100 door frame to enped into wall with gyp return and fire chalking perimitor. 8/7/2001 9:57:02 AM
|
(F) Reprint permit | | | 8/3/2001 | | DONE |
|
|
|
|
(F) Reprint permit | | | 8/3/2001 | | DONE |
|
|
|
|
BLD-Conference | 8/2/2001 | 8/2/2001 | 8/2/2001 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/02/2001 at 09:06:39. Contact: ###-####. conf. 8/3/2001 10:08:38 AM
|
BLD-Wall cover | 7/31/2001 | 8/1/2001 | 8/1/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 07/31/2001 at 15:03:28. Contact: ###-####. basement exsust duct wrap ok. 8/1/2001 11:15:21 AM
|
BLD-Wall cover | 7/26/2001 | 7/30/2001 | 7/30/2001 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 07/26/2001 at 07:40:54. Contact: ###-####. fire stopping cof. 7/30/2001 4:34:28 PM
|
BLD-Wall cover | 7/27/2001 | 7/27/2001 | 7/27/2001 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 07/27/2001 at 05:48:34. Contact: ###-####. sub fab interior wall ok for cover wip 7/27/2001 12:39:00 PM
|
BLD-Conference | 7/16/2001 | 7/16/2001 | 7/16/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 07/16/2001 at 06:08:46. Contact: ###-####.
|
Plan resubmittals received | | | 7/16/2001 | | DONE |
|
|
|
Received one copy of letter from Bob Bowen regarding to pryro;honic room w/attachments. routed to john m. kmm
|
BLD-Wall cover | 6/29/2001 | 7/2/2001 | 7/2/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 06/29/2001 at 14:42:04. Contact: ###-####. ele panels no envlelop at top at back/ colums need box rating / fire door need listing for fram. 7/6/2001 11:32:20 AM
|
BLD-Conference | 6/27/2001 | 6/28/2001 | 6/28/2001 | A | PASS |
Jim Storey
|
|
|
Chris ###-####
|
FIRE-Conference | 6/27/2001 | 6/27/2001 | 6/27/2001 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 06/27/2001 at 08:10:54. Contact: ###-####. request made by mistake 6/27/2001 2:43:18 PM
|
BLD-Wall cover | 6/21/2001 | 6/21/2001 | 6/21/2001 | P | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 06/21/2001 at 07:54:19. Contact: ###-####. rm#101 2hr wall tpo track/fds/beam framing/cut back to maintane assembly. stair 10# fire stop emt an beams./ fan deck 2 inch pvc collor. 6/21/2001 5:16:52 PM
|
Plan resubmittals received | | | 5/18/2001 | | DONE |
|
|
|
Received two copies of letter with description of phased occupancy and two copies of phased occupancy plans. Sheets A2.1.0X & A2.2.0X. Routed to John M.
|
BLD-Wall cover | 5/15/2001 | 5/16/2001 | 5/16/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/15/2001 at 15:41:17. Contact: ###-####. 1/2 east wall of fab ok for cover/ 5/16/2001 10:46:44 AM
|
BLD-Wall cover | 5/14/2001 | 5/14/2001 | 5/14/2001 | A | NR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/14/2001 at 06:43:03. Contact: ###-####.
|
BLD-Wall cover | 5/7/2001 | 5/8/2001 | 5/8/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/07/2001 at 17:17:02. Contact: ###-####.
|
BLD-Wall cover | 5/7/2001 | 5/7/2001 | 5/7/2001 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/07/2001 at 10:07:51. Contact: ###-####.
|
BLD-Wall cover | 4/26/2001 | 4/27/2001 | 4/27/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 04/26/2001 at 12:30:38. Contact: ###-####. 4 hr wall ok to procced/ coridor ok at south fan deck. 4/27/2001 1:26:26 PM
|
BLD-Wall cover | 4/16/2001 | 4/16/2001 | 4/16/2001 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 04/16/2001 at 07:33:10. Contact: ###-####. chem rm in basement duct s/f still not installed corectly/ fan deck coridor ok all but room to tunel hold this area until fixed. 4/16/2001 6:29:59 PM
|
BLD-Wall cover | 3/27/2001 | 3/28/2001 | 3/28/2001 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 03/27/2001 at 14:01:40. Contact: ###-####. fab and north 4 hr ok. 3/28/2001 9:11:50 AM
|
BLD-Wall cover | 3/19/2001 | 3/19/2001 | 3/19/2001 | A | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 03/19/2001 at 07:19:33. Contact: ###-####.
|
BLD-Wall cover | 3/16/2001 | 3/16/2001 | 3/16/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 03/16/2001 at 06:28:44. Contact: ###-####.
|
BLD-Wall cover | 3/13/2001 | 3/13/2001 | 3/13/2001 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 03/13/2001 at 05:48:00. Contact: ###-####. c/n pending. 3/13/2001 12:54:35 PM
|
BLD-Wall cover | 3/6/2001 | 3/7/2001 | 3/7/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 03/06/2001 at 14:48:44. Contact: ###-####. sub faB CORRIDORS C1 AND WEST WALL OK FOR COVER.C/N FOR DETAIL OF PIPI RACKING AT ROOF FAN DECK HANGER SPACING/ LATERAL BAR SPACING AND ATCHMENT OVER HEIGHT STUDS. 3/7/2001 5:33:46 PM
|
BLD-Wall cover | 2/20/2001 | 2/21/2001 | 2/21/2001 | A | NR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 02/20/2001 at 17:23:06. Contact: ###-####.
|
BLD-Framing/Rough-in | 2/16/2001 | 2/20/2001 | 2/20/2001 | A | NR |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 02/16/2001 at 10:27:32. Contact: ###-####.
|
BLD-Framing/Rough-in | 2/12/2001 | 2/12/2001 | 2/12/2001 | P | PART |
Jim Storey
|
|
|
Added by Inspector: 301 On 2/12/2001 1:06:26 PM c2/27 stair beam must maintane 6ft 8 in. headroom will require engineering and resubmital for design.previous c/n idems ok pending 1. deflection of fab wall at beam for intagraty of assembly.
|
BLD-Framing/Rough-in | 2/12/2001 | 2/12/2001 | 2/12/2001 | P | PASS |
Jim Storey
|
|
|
Added by Inspector: 301 On 2/12/2001 1:13:09 PM basement ok ro cover of walls rm# 001k,1l,1m,1n,0h,oc
|
BLD-Wall cover | 2/9/2001 | 2/9/2001 | 2/9/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 02/09/2001 at 05:46:22. Contact: ###-####. ceilling ok will check on final fo primetor wires/ tennet walls need protection. 2/9/2001 3:26:12 PM
|
BLD-Framing/Rough-in | 2/5/2001 | 2/5/2001 | 2/5/2001 | P | FAIL |
Jim Storey
|
|
|
Added by Inspector: 301 On 2/5/2001 10:20:35 PM c/n isued 1# 307.1.4 h-3 area over 150 sq/ft required to have min 2 hr wall. aproved plan has a 1 hr wall designation a3.6/e&k27a refrance to floor plan 2.0.3 at grid lines a9 - c8 and 27 - 30.
2# doors in these walls requied to be 1 1/2 hr rated.
3# chemical exsust duct passing from one h-3 occ to h-6 occ and into another h-3 occ rm. will need to be protected to meet ubc 1202.2.5 2hr protection.
4# walls 28/c2,c8 and 29/c2.c8 struc. I beam restricks 2hr wall configration for gyp. attchament provide wall and listing design.
5# bottom fo beams on grid line c2 and c8 missing 1 layer of gyp. protection.
6#I beams perpendickular to 2hr and 1 hr walls requier wall stud framing into web for screw sch. of listing for gyp. atchment.
7# bottom track pin to slab and track to gyp. must be per plan and gyp. assemblie listing.
8#fab ground level walls at grid line c2 and 29 must have detail submitted for collums incapsaluated with in the 1hr corridor assemblie this is a full height wall struc. frame conections and deflection for height to be addressed.
9# ele. boxes less than 24 inches must be procted two locations 2hr walls basement.
10# all trades must submit fire stopping listings to address there idems for insp.
11#fab wall must have horrisontal bar for steel stud framing height of wall.
|
BLD-Framing/Rough-in | 2/5/2001 | 2/5/2001 | 2/5/2001 | P | PASS |
Jim Storey
|
|
|
Added by Inspector: 301 On 2/5/2001 9:45:21 PM recieved resubmital for top of the wall head-joint to replace the approved plan detail and listing on 3.6 / 3.6.1 . listed ul/cul no.hw-d-0077system #. this listing is april 21, 2000 and meets the new std. for fire stopping as a class II movement capabilies = 17% comp or extention. submital approved and archived to documents with city plan.
|
(F) Reprint permit | | | 12/21/2000 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 12/18/2000 | | 12/20/2000 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/20/2000 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 12/20/2000 | | DONE |
|
|
|
|
Print Occupancy Form | | | 12/20/2000 | | DONE |
|
|
|
|
Telephone call | | | 12/20/2000 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Issue & PRINT to be Invoiced | | | 12/20/2000 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 9/29/2000 | | 12/20/2000 | | PASS |
John Menard
|
|
|
12/20/00 11:01:10 JCM - activity updated through activity BLDA022 from case BLD00-02920.
|
Plan resubmittals requested | | | 12/19/2000 | | |
|
|
|
FAXED AND MAILED THE ARCHITECT OF RECORD A LETTER REQUESTING ADDITIONAL INFORMATION. JCM
|
Routing - FIRE | 11/14/2000 | 12/18/2000 | 12/18/2000 | | PASS |
Bill Alexander
|
|
|
Note: Received UBC note files 12/14/2000 from J.M.
|
Plan Review Completed(1st rev) | | | 12/18/2000 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 12/13/2000 | | DONE |
|
|
|
Received two copies of revised sheets A2.0.0X, A2.0.0, A2.0.03, A2.2.0, A2.2.1, A2.2.2, A2.2.3, A2.2.4, A2.2.5 (CP-2B), A2.2.5, (CP-4) A2.2.6, A2.6.1, A3.2, A3.3, A3.4, A3.5, A3.6, A3.7, A4.3, A4.7, A4.9, A4.10, A4.11, A6.3, (CP-2B), A9.2.0, A9.2.5, A9.3.0. One copy of response to comments dated 12/12/2000. One copy of letter dated 12/1/00 comments dated 11/30/00. Product information - Acoustical panels, surface mounted corner guards, USG info on 1 hour condition at roof/ceiling construction. Routed to John M. KMM
|
Plan resubmittals requested | | | 11/28/2000 | | FAIL |
|
|
|
MAILED A COPY OF THE COMMENT LIST TO THE ARCHITECT OF RECORD REQUESTING REVISIONS. JCM
|
Plan resubmittals received | | | 11/22/2000 | | DONE |
|
|
|
Received two copies of plans from HDR. One copy of cover letter and listing of revised sheets. Routed to John M. KMM
|
Routing - PLAN CHECK | 10/26/2000 | | 11/14/2000 | | |
|
|
|
|
Routing Off Site - STRUCTURAL | 11/8/2000 | | 11/10/2000 | | PASS |
|
|
|
Sent revised plans to the consultanting engineer via PDQ. 11/8/00 DAR
|
Plan resubmittals received | | | 11/8/2000 | | DONE |
|
|
|
Received three copies of revised sheets S0.1, S1.0.1, S1.3.1 and one copy of responses to comments dated 10.25.2000, routed to John M. KMM
|
Plan resubmittals received | | | 11/3/2000 | | DONE |
|
|
|
Received two copies of revised sheet A2.0.0X. One copy of letter to John M. from Thomas A. Ray. Routed all to John M. KMM
|
Additional plans submitted | | | 11/2/2000 | | DONE |
|
|
|
Received two sets of additional plans from Bob Bowen, ER + HDR, forwarded same to John Menard. 11/2/00 DAR
|
Routing - PLUMBING | 10/17/2000 | | 10/26/2000 | | PASS |
|
|
|
no data was provided for the hot water heat exchanger, it must be double wall with leak detection, all emergency shower eye wash stations not in close proximity to a drain must be provided with a pan connected to the waste system.
|
Plan resubmittals requested | | | 10/25/2000 | | |
|
|
|
FAXED FRANK KVAPIL A COPY OF THE COMMENT LIST FOR THE PIPE BRIDGE FROM THE CONSULTING STRUCTURAL ENGINEER REQUESTING REVISIONS. JCM
|
Routing - PLAN CHECK | 10/10/2000 | | 10/17/2000 | | |
|
|
|
|
Plan resubmittals received | | | 10/13/2000 | | DONE |
|
|
|
RECEIVED PLAN R3ESUBMITTALS FROM ER + HDR, THREE SETS, FORWARDED SAME TO JOHN MENARD. 10/13/00 DAR
|
Routing - PLUMBING | 10/3/2000 | | 10/10/2000 | | FAIL |
|
|
|
no review, need resubmittals of ew/es drainage and all iw drainage
|
Routing - PUBLIC WORKS | 9/29/2000 | | 10/3/2000 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/29/2000 | | DONE |
|
|
|
|
Application received | | | 9/28/2000 | | |
|
|
|
|