BLD-Final | 12/21/2001 | 12/21/2001 | 12/21/2001 | P | PASS |
Russ Owen
|
|
|
Added by Inspector: 407 On 12/21/2001 12:06:43 PM ok perm oc work completed.
|
Fee Review-notes | 11/8/2000 | 11/8/2000 | 5/24/2001 | | DONE |
|
|
|
|
Letter of compliance | | | 5/23/2001 | | DONE |
|
|
|
Letter of Compliance #21510 issued 5-23-01.
|
BLD-Final | 5/15/2001 | 5/15/2001 | 5/15/2001 | P | PASS |
Joe Tawney
|
|
|
Added by Inspector: 406 On 5/15/2001 3:50:17 PM Reinsp OK for certificate of completion
|
FIRE-Final Inspection | 3/14/2001 | 3/15/2001 | 3/15/2001 | A | PART |
Joe Tawney
|
|
|
###-#### Reinsp OK to occupy control areas 3 # 4 3/15/2001 1:17:19 PM
|
BLD-Final | 3/14/2001 | 3/15/2001 | 3/15/2001 | P | PART |
Russ Owen
|
|
|
###-####ok to occupy cont room 3/4 waiting for new door from ext building to new const. 3/15/2001 2:52:26 PM
|
FIRE-Sprinkler Rough-in | 3/13/2001 | 3/14/2001 | 3/14/2001 | A | FAIL |
Joe Tawney
|
|
|
###-#### Reinsp Fail Doors not latching 3/14/2001 12:32:29 PM
|
FIRE-Final Inspection | 3/12/2001 | 3/13/2001 | 3/13/2001 | A | FAIL |
Joe Tawney
|
|
|
###-#### Final Fail smoke seals and adj closers. Install new rated door 3/13/2001 1:00:13 PM
|
BLD-Framing/Rough-in | 2/16/2001 | 2/20/2001 | 2/20/2001 | A | PART |
Russ Owen
|
|
|
###-####partial insp of theshaft above control room #4. 2/20/2001 1:53:03 PM
|
BLD-Framing/Rough-in | 2/7/2001 | 2/8/2001 | 2/8/2001 | A | PART |
Russ Owen
|
|
|
FR JEFF ###-#### shaft over control room,will recall for another insp 2/8/2001 1:33:23 PM
|
Plan resubmittals received | | | 1/25/2001 | | DONE |
|
|
|
Received a Plan Change Bulletinfrom BRS, forwarded same to Dan Stuart. 1/25/01 DAR
|
BLD-Framing/Rough-in | 1/3/2001 | 1/4/2001 | 1/4/2001 | A | PART |
Russ Owen
|
|
|
fr jeff ###-####. inspections of control rooms 3&4 .work started w-out insp,sheetrock not inplace at ext side of control room #4 built against adjoinig room, will need submital for 1hr constuction at one side only, room #3 has 6 in pvc pipe in wall needs 1hr prot, also note both rooms req, 1hr metal fab shaft assemblys per er rpt #5301. c/ns noted with contractor. 1/4/2001 12:18:20 PM 1/4/2001 12:19:11 PM
|
Issue PAID IN FULL permit | | | 12/28/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 12/22/2000 | | DONE |
|
|
|
|
Print Occupancy Form | | | 12/22/2000 | | DONE |
|
|
|
|
Telephone call | | | 12/22/2000 | | DONE |
|
|
|
Called Mike permit ready for pickup ###-####
|
Routing - PLAN CHECK | 12/19/2000 | | 12/21/2000 | | PASS |
|
|
|
Resubmittal inserted into plans. Approved as noted and attached. Approved use of ER#5301, METAL-FAB MODEL IPIC-4G, NO-CHASE GREASE DUCT SYTEM AS AN EQUIVALENT FOR 1-HOUR SHAFT / OCCUPANCY SEPARATION REQUIRED AROUND THE VENTILATION SYSTEM, FROM THE CONTROL ROOM OCCUPANCY SEPARATION TO THE EXTERIOR, TO PROVIDE CONTINUOUS RUNNING VENTILATION AS ALLOWED IN UFC EXCEPTION, SECTION 7902.1.5, TO ELIMINATE NEED FOR EXPLOSION CONTROL CONSIDERATION.
|
Plan resubmittals received | | | 12/21/2000 | | DONE |
|
|
|
Received plan resubmittals from BRS Architects two of sheet IPA-2. Forwarded same to Dan Stuart. 12/21/00 DAR
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/21/2000 | | PASS |
|
|
|
ROUTING TO PERMIT DESK FOR ISSUANCE.
|
Plan assigned to (DRS) | 11/14/2000 | | 12/21/2000 | | PASS |
Dan Stuart
|
|
|
12/21/2000 18:24:03 DRS - activity updated through activity BLDA022 from case BLD00-03372.
|
Routing - FIRE | 12/14/2000 | 12/19/2000 | 12/19/2000 | | PASS |
Bill Alexander
|
|
|
|
Plan Review Completed(1st rev) | | | 12/19/2000 | | FAIL |
|
|
|
|
Plan resubmittals requested | | | 12/14/2000 | | |
|
|
|
FAXED AND MAILED COPY OF PLAN REVIEW CORRECTION SHEETS TO ARCHITECT, MIKE CAPSHAW.
|
Routing - PLAN CHECK | 11/14/2000 | | 12/14/2000 | | FAIL |
|
|
|
Plans do not indicate existing wall construction to meet 1- hour occupancy separation requirements; Plans do no indicate the construction or location of two 1-hour shafts for use at the two new control rooms that propose to have 1-hour walls with 1-hour tunnel type floor/ceiling assembly to enclose the exhaust system for the IPA Storage & collection areas that cannot have a fire damper located in the exhaust duct for a hazardous product. Routing to fire code analyst for review. Plan review correction comments faxed & mailed to Mike Capshaw.
|
Pending Assignment by MYS | 11/14/2000 | | 11/14/2000 | | DONE |
Marlene Southard
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 11/9/2000 | | DONE |
|
|
|
|
Received Certificate of Value | | | 11/8/2000 | | DONE |
|
|
|
|
Application received | | | 11/8/2000 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 11/8/2000 | | DONE |
|
|
|
|