Permit Information
Permit NumberBLD00-03372
StatusFinaled
Name SCP GLOBAL TECHNOLOGIES
Site Address 8455 W WESTPARK ST
Project NameSCP GLOBAL TECH-#456
Customer Number 
ePlanReviewNo
Description
To divide existing building into 4 control areas, by construction of 1-hour occupancy separation walls between the designated areas, per footnote #1, Table's 3-D & 3-E, 1997 UBC. This is being done to allow the existing declared occupancy use groups to remain because each designated control area has been declared as having hazardous quantities of IPA (Isopropyl Alcohol @ 90 - 100 % concentration) within the exempt quantities of product allowed by UBC Table 3-D and 3-E, as per approved plans on file. Work to include upgrade of existing walls or construction of new walls, roof/ceiling or floor/ceiling, U.L. listed (or equal) 1-hour assemblies to create the required 1-hour occupancy separation to create the four control areas. Openings & penetrations W/I the occupancy separations SHALL have an equivalent fire resistive rating of 1-hour or greater. NOTE: This building is fully fire sprinklered for allowable area increase, considered to be one building of Type V-N construction, "B, S-1, F-1" Occupancies, 60 feet of open yard all around per Section 505.2 '97 UBC. (P.C.#958-00)/drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/21/200112/21/200112/21/2001PPASS
DetailsRuss Owen
Added by Inspector: 407 On 12/21/2001 12:06:43 PM ok perm oc work completed.
Fee Review-notes11/8/200011/8/20005/24/2001 DONE
Letter of compliance  5/23/2001 DONE
Letter of Compliance #21510 issued 5-23-01.
BLD-Final5/15/20015/15/20015/15/2001PPASS
DetailsJoe Tawney
Added by Inspector: 406 On 5/15/2001 3:50:17 PM Reinsp OK for certificate of completion
FIRE-Final Inspection3/14/20013/15/20013/15/2001APART
DetailsJoe Tawney
###-#### Reinsp OK to occupy control areas 3 # 4 3/15/2001 1:17:19 PM
BLD-Final3/14/20013/15/20013/15/2001PPART
DetailsRuss Owen
###-####ok to occupy cont room 3/4 waiting for new door from ext building to new const. 3/15/2001 2:52:26 PM
FIRE-Sprinkler Rough-in3/13/20013/14/20013/14/2001AFAIL
DetailsJoe Tawney
###-#### Reinsp Fail Doors not latching 3/14/2001 12:32:29 PM
FIRE-Final Inspection3/12/20013/13/20013/13/2001AFAIL
DetailsJoe Tawney
###-#### Final Fail smoke seals and adj closers. Install new rated door 3/13/2001 1:00:13 PM
BLD-Framing/Rough-in2/16/20012/20/20012/20/2001APART
DetailsRuss Owen
###-####partial insp of theshaft above control room #4. 2/20/2001 1:53:03 PM
BLD-Framing/Rough-in2/7/20012/8/20012/8/2001APART
DetailsRuss Owen
FR JEFF ###-#### shaft over control room,will recall for another insp 2/8/2001 1:33:23 PM
Plan resubmittals received  1/25/2001 DONE
Received a Plan Change Bulletinfrom BRS, forwarded same to Dan Stuart. 1/25/01 DAR
BLD-Framing/Rough-in1/3/20011/4/20011/4/2001APART
DetailsRuss Owen
fr jeff ###-####. inspections of control rooms 3&4 .work started w-out insp,sheetrock not inplace at ext side of control room #4 built against adjoinig room, will need submital for 1hr constuction at one side only, room #3 has 6 in pvc pipe in wall needs 1hr prot, also note both rooms req, 1hr metal fab shaft assemblys per er rpt #5301. c/ns noted with contractor. 1/4/2001 12:18:20 PM 1/4/2001 12:19:11 PM
Issue PAID IN FULL permit  12/28/2000 DONE
Inspection Record Card- Bld  12/22/2000 DONE
Print Occupancy Form  12/22/2000 DONE
Telephone call  12/22/2000 DONE
Called Mike permit ready for pickup ###-####
Routing - PLAN CHECK12/19/2000 12/21/2000 PASS
Resubmittal inserted into plans. Approved as noted and attached. Approved use of ER#5301, METAL-FAB MODEL IPIC-4G, NO-CHASE GREASE DUCT SYTEM AS AN EQUIVALENT FOR 1-HOUR SHAFT / OCCUPANCY SEPARATION REQUIRED AROUND THE VENTILATION SYSTEM, FROM THE CONTROL ROOM OCCUPANCY SEPARATION TO THE EXTERIOR, TO PROVIDE CONTINUOUS RUNNING VENTILATION AS ALLOWED IN UFC EXCEPTION, SECTION 7902.1.5, TO ELIMINATE NEED FOR EXPLOSION CONTROL CONSIDERATION.
Plan resubmittals received  12/21/2000 DONE
Received plan resubmittals from BRS Architects two of sheet IPA-2. Forwarded same to Dan Stuart. 12/21/00 DAR
PLANS/APPL TAKEN TO FRONT DESK  12/21/2000 PASS
ROUTING TO PERMIT DESK FOR ISSUANCE.
Plan assigned to (DRS)11/14/2000 12/21/2000 PASS
DetailsDan Stuart
12/21/2000 18:24:03 DRS - activity updated through activity BLDA022 from case BLD00-03372.
Routing - FIRE12/14/200012/19/200012/19/2000 PASS
DetailsBill Alexander
Plan Review Completed(1st rev)  12/19/2000 FAIL
Plan resubmittals requested  12/14/2000  
FAXED AND MAILED COPY OF PLAN REVIEW CORRECTION SHEETS TO ARCHITECT, MIKE CAPSHAW.
Routing - PLAN CHECK11/14/2000 12/14/2000 FAIL
Plans do not indicate existing wall construction to meet 1- hour occupancy separation requirements; Plans do no indicate the construction or location of two 1-hour shafts for use at the two new control rooms that propose to have 1-hour walls with 1-hour tunnel type floor/ceiling assembly to enclose the exhaust system for the IPA Storage & collection areas that cannot have a fire damper located in the exhaust duct for a hazardous product. Routing to fire code analyst for review. Plan review correction comments faxed & mailed to Mike Capshaw.
Pending Assignment by MYS11/14/2000 11/14/2000 DONE
DetailsMarlene Southard
Plans ACCEPTED BY PLAN TECH  11/9/2000 DONE
Received Certificate of Value  11/8/2000 DONE
Application received  11/8/2000  
Recd Pcfee & Taken To Pln CK  11/8/2000 DONE