Fee Review-notes | 7/1/2003 | 7/1/2003 | 7/1/2003 | | DONE |
|
|
|
|
Permanent occupancy | | | 3/29/2001 | | DONE |
|
|
|
Perm. Occ. Cert. #8610 issued 3-29-01 to Bad Boy Burgers.
|
Permanent Occupancy | | 2/23/2001 | 2/23/2001 | | DONE |
|
|
|
|
BLD-Final | 2/22/2001 | 2/23/2001 | 2/23/2001 | A | PASS |
Russ Owen
|
|
|
Walter ###-####ok perm oc by 425. 2/23/2001 11:46:28 AM
|
DOC - Permit Finaled | 2/23/2001 | 2/23/2001 | 2/23/2001 | A | PASS |
Russ Owen
|
|
|
Added by Inspector: 407 On 2/23/2001 11:46:46 AM
|
Temporary occupancy | | | 1/19/2001 | | PART |
|
|
|
Temp. Occ. Cert. #4510 issued 1-19-01 to Bad Boy Burgers.
|
BLD-Final | 1/18/2001 | 1/18/2001 | 1/18/2001 | P | PART |
Tom Arcoraci
|
|
|
Walter ###-#### ok for temp occ cn issued 1/18/2001 3:55:45 PM
|
BLD-Final | 1/16/2001 | 1/17/2001 | 1/17/2001 | A | NR |
Russ Owen
|
|
|
Walter ###-####
|
FIRE-Final Inspection | 1/8/2001 | 1/9/2001 | 1/9/2001 | A | FAIL |
Joe Tawney
|
|
|
Walter ###-#### Reinsp Fail Openings in office 1/9/2001 12:49:32 PM
|
FIRE-Final Inspection | 1/9/2001 | 1/9/2001 | 1/9/2001 | P | PASS |
Joe Tawney
|
|
|
walter ###-#### Reinsp OK for permanant occupancy 1/10/2001 8:10:18 AM
|
FIRE-Final Inspection | 1/2/2001 | 1/3/2001 | 1/3/2001 | A | FAIL |
Joe Tawney
|
|
|
Walter ###-#### Final Fail C/N issued 1/4/2001 8:06:41 AM
|
BLD-Conference | 12/15/2000 | 12/18/2000 | 12/18/2000 | A | PASS |
Tom Arcoraci
|
|
|
###-#### conf for items needed for final 12/18/2000 11:13:34 AM
|
BLD-Conference | 12/18/2000 | 12/18/2000 | 12/18/2000 | A | PART |
Joe Tawney
|
|
|
Added by Inspector: 406 On 12/18/2000 Conf with structural insp and owner on basement use
|
FIRE-Final Inspection | 12/14/2000 | 12/15/2000 | 12/15/2000 | A | FAIL |
Joe Tawney
|
|
|
Walter ###-#### temp occ please Final Fail C/N issued 12/15/2000 12:35:16 PM
|
Print Occupancy Form | | | 12/7/2000 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 12/7/2000 | | DONE |
|
|
|
|
Telephone call | | | 12/7/2000 | | DONE |
|
|
|
called permit ready
|
Issue PAID IN FULL permit | | | 12/7/2000 | | DONE |
|
|
|
|
Routing - FIRE | 12/1/2000 | 12/1/2000 | 12/6/2000 | | PASS |
|
|
|
|
Plan assigned to (DRS) | 11/30/2000 | 11/30/2000 | 12/6/2000 | | PASS |
Dan Stuart
|
|
|
12/6/2000 17:01:28 DRS - activity updated through activity BLDA022 from case BLD00-03525.
|
Routing - PLAN CHECK | 12/6/2000 | | 12/6/2000 | | PASS |
|
|
|
RECEIVED RE-SUBMITTAL & APPLICATION FROM TENANT. ROUTING TO PERMIT DESK FOR ISSUANCE.
|
Plan Review Completed(1st rev) | | | 12/6/2000 | | FAIL |
|
|
|
failed building review
|
Received Certificate of Value | | | 12/6/2000 | | |
|
|
|
CERTIFICATE OF VALUE SHEET BROUGH IN BUT NO VLUES LISTED. I QUESTIONED ALEX PASLIAS CONCERNING AN INITIAL COST. HE ESTIMATED HIS PORTION OF WALL FRAMING, SHEETROCK & LABOR TO BE $1500.OO AND THE PLUMER, SINKS & DRAINS TO COST $1,500.00 - TOTAL $3,000.OO. HE INITIALED ON TOTAL LINE AND I ADDED THE TWO TOGETHER.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/6/2000 | | PASS |
|
|
|
ROUTING TO PERMIT DESK FOR ISSUANCE.
|
Routing - PUBLIC WORKS | 12/1/2000 | | 12/4/2000 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 11/30/2000 | 11/30/2000 | 11/30/2000 | | FAIL |
|
|
|
Plans circulating to PW for fee evaluation, fire code analysts for approval, CDH has approved plans ( Bud Fullerton & Carol Johnson signed for Bud.); Application and C.V. required from architect or tenant before the permit can be completed for issuance after other approvals received.
|
Routing Off Site - C.D.H | 11/30/2000 | 11/30/2000 | 11/30/2000 | | PASS |
|
|
|
Bud Fullerton had signed & dated Sheet A-2 for CDH approval & Carol johnson signed / dated Staff Review Sheet A-1 for Bud.
|
Application received | | | 11/30/2000 | | |
|
|
|
|
Plans ACCEPTED BY PLAN CHECK | | | 11/30/2000 | | PASS |
|
|
|
ACCEPTED BASED ON CONDITION OF WRITTEN NOTICE FROM TENANT STATING HE IS AWARE AND ACCEPTS THE CONDITION FOR NO USE OF THE BASEMENT, OTHER THAN MAXIMUM OF 300 SQ. FT. AREA AS SHOWN ON SHEET A1 OF APPROVED PLANS AS ALLOWED BY SECTION 1004.2.3.3, EXCEPTION #2, FOR ANY PURPOSE BEYOND MECHANICAL & ELECTRICAL EQUIPMENT CURRENTLY EXISTING, TO BE STATED AS SUCH BY ALEX PAFLIAS, KNOWN AS "THE TENANT", TO ACT AS THE ENFORCEMENT PARTY FOR THE AGREEMENT. SEPARATE PLANS (2 COPIES), PREPARED AND STAMPED BY AN IDAHO LICENSED ARCHITECT AND AN APPLICATION SHOWING THE PROPOSED USE(S) OF THE BASEMENT AND THE REQUIRED CODE UPGRADES / CONSTRUCTION TO MEET APPLICABLE BUILDING CODES AND ORDINANCES IN EFFECT AT THE TIME OF SUBMITTAL FOR REVIEW. THE BASEMENT IS TO HAVE ALL DEBRIS REMOVED; THE EXTERIOR NORTH SIDE STAIRWELL TO BE SECURELY COVERED AGAINST ENTRY, REMOVE DOOR HARDWARE AND SECURE DOOR CLOSED. POSSIBLE SERVICE ACCESS ONLY. TO VERIFY EXISTING FRAMING IN BASEMENT TO CREATE A 300 S.F. TOTAL USABLE AREA (OFFICE & MECHANICAL / EQUIPMENT AS ILLUSTRATED BY ARCHITECT ON SHEET A-1. VERIFY INTERIOR ROOM DIMENSIONS OF APPROX. 15' X 19' , AS SHOWN, TOTAL AREA OF USABLE SPACE CANNOT EXCEED 300 SQ. FT. WITHOUT ARCHITECTURAL PLANS FOR THE BASEMNT AREA SHOWING FULL COMPLIANCE WITH CURRENT CODES. PLACE 5/8", TYPE "X" SHEETROCK ON ROOM SIDE OF NEW FRAMED WALLS; CREATE A CRAWL SPACE ACCESS OF SIZE NOTED ON PLANS WITH ACCESS DOOR ASSEMBLY AS NOTED.
|
Plan Reviewer's activity | | | 11/30/2000 | | |
|
|
|
Previous meeting with proposed tenant, Alex Paflias, resulted in a review of the History of the existing facility for past code compliance and an existing Certificate of Occupoancy which moght be transferred into the new tenant 's name - BAD BOYS BURGERS". Ther was no C.O. found and the previous tenant/owner, Taco John, had performed work and occupied portions of the basement W/O having met the requirements of plans & application and the conditions for complying second exit from basement and the need to provide a fire sprinkler system throughout the basement. These deficiencies had been noted with Taco John managers / owners on three different occasions starting in 1991 when a correction notice was issued to the manager after a site inspection was performed as a result of the owner obtaining an occupancy approval review permit that allowed the building department to perform an inspection to determine code upgrade requirements, if any, that needed correction before a certificate of occupancy could be issued. This permit was expired per section 303 (D) of the 1988 UBC. In 1993, another permit was applied for an issued to determine requirements for issuance of a certificate of occupancy. A correction notice was again issued and this resulted in the tenant owner applying for and recieving a permit to reduce the size of the basement usable space to 300 sq. ft. or less per section 3303(a), exception #5, 1991 UBC. This allowed the existing 1- exit from the basement and the remainder to be considered as non-habitable, non-usable crawl space. There were no further calls for inspections or completion of the permitted work. After the 180 days without calls for inspection the permits, per code, expire.
The visit with Mr. Paflias, resulted in the need for obtaining an architect to review the site for code compliance and the proposed tenant / owner and architect determining the course of action they desired to take and submitting plans and application for a permit to perform the work required. This involves the finish of a basement area of 300 sq. ft for tenant use.; the cleaning of the remaining area to 'broom clean' to be known as a crawl space (no occupancy or use); new sink installations; two new floor drains for existing restrooms and a new 8 ft. section of framed, finished wall in the kitchen, per the plans presented on 11/30 00 by Alex Paflias as drawn by Billy Ray Strite, Architect.
|
Telephone call | | | 11/30/2000 | | DONE |
|
|
|
Call to Bill Strite to request the submittal of the application for the permit to accompany plans received earlier in the day from Alex Paflina, new tenant. Alex had stated he had given the application and a letter stating his understanding that the use of the basement are would be limited to a 300 sq. ft. or less room area and he agrees to abide by this understanding and to see his staff also abides by the requirements. Further use of the basement can only occur after architecturally prepared plans (Idaho license), application and details showing how the basement would be brought into code compliance with exits, sprinkler system and occupancy requirements per current adopted codes in force at time of submittal.
|
Waiting for Cert. of Value | | | 11/30/2000 | | |
|
|
|
Certificate of Value for work costs were not included with plan submittals. Alex stated the paper work was with Bill Strite and he would have it sent over.
|