Fee Review-notes | 12/15/2000 | 12/15/2000 | 2/10/2004 | | DONE |
|
|
|
|
Fee Review-notes | 7/2/2003 | 7/2/2003 | 7/2/2003 | | DONE |
|
|
|
Additional values from subcontractors.
|
Permanent Occupancy | | 6/18/2003 | 6/18/2003 | | DONE |
|
|
|
|
BLD-Final | 6/17/2003 | 6/18/2003 | 6/18/2003 | A | PASS |
Tony Young
|
|
|
###-#### bill ceiling grid corrections in kitchen & dressing rooms
ok for perm. occ. 6/18/2003 11:24:32 AM
|
First Notice | | 6/18/2003 | 6/18/2003 | | DONE |
|
|
|
|
Permanent occupancy | | | 6/18/2003 | | DONE |
|
|
|
Perm. Occ. Cert. #9695 issued 6-18-03 to Pierce Park Baptist Church.
|
Permanent occupancy | | | 6/16/2003 | | PASS |
|
|
|
Inspection noted questioned area has sprinkler system and it has been seeded. Compliance met.
|
BLD-Final | 5/23/2003 | 5/23/2003 | 5/23/2003 | P | PART |
Tony Young
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Annette Moore
c/n posted on ceiling grid,,, ok for temp.. occ. 5/23/2003 3:37:43 PM
|
Code Occupancy Approval | 5/23/2003 | 5/23/2003 | 5/23/2003 | A | FAIL |
Wm. Michael Meloy
|
|
|
Inspection noted that "island area" in rear parking does not have the necessary grass/sod/or hydroseed. I spoke with Bill ###-####, and told him that if he wants a temp, he needs to bond. I approved $1,000 as a bond for the project. 5/23/2003 11:11:34 AM
|
Temporary occupancy | | | 5/23/2003 | | DONE |
|
|
|
Temp. Occ. Cert. #4955 issued 5-23-03 to the Pierce Park Baptist Church.
|
PubWorks Occupancy Approval | 5/21/2003 | 5/21/2003 | 5/21/2003 | | DONE |
|
|
|
Drainage project complete, signed permanent occupancy 5/21/03. D.Erskine
|
FIRE-Final Inspection | 5/21/2003 | 5/21/2003 | 5/21/2003 | P | PASS |
Rick Jackson
|
|
|
BILL; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
BLD-Framing/Rough-in | 4/30/2003 | 4/30/2003 | 4/30/2003 | P | PASS |
Tony Young
|
|
|
###-####
window in sep. wall,, infill 4/30/2003 4:58:48 PM
|
BLD-Conference | 4/25/2003 | 4/25/2003 | 4/25/2003 | P | DONE |
Jim Storey
|
|
|
bill; Phone #: ###-#### Internet Inspection Request from: Annette Moore need to remove cassing in occ. septration wall and frame out to rated wall before to close opening in office. 4/25/2003 2:44:58 PM
|
BLD-Conference | 4/7/2003 | 4/8/2003 | 4/8/2003 | A | PASS |
Tony Young
|
|
|
conf. on schedule, etc.
wip, ok,, slow progress 4/8/2003 9:23:47 AM
|
BLD-Aging Inspection | 4/7/2003 | 4/7/2003 | 4/7/2003 | | PASS |
Tony Young
|
|
|
|
BLD-Conference | 2/4/2003 | 2/4/2003 | 2/4/2003 | P | PASS |
Tony Young
|
|
|
###-#### needs ext.,,,,,,,, ok 2/4/2003 4:15:18 PM
|
BLD-Aging Inspection | 1/9/2003 | 1/9/2003 | 1/9/2003 | | PART |
Tony Young
|
|
|
wip 1/13/2003 2:24:13 PM
|
FIRE-Conference | 8/20/2002 | 8/21/2002 | 8/21/2002 | A | DONE |
Troy Cobbley
|
|
|
building has been built 8' south than the original plan shows thus narrowing one of the fire dept access roads. I told contractor that he needs to converse with Richard Dailey to verify if the narrower road will be OK. 8/21/2002 9:27:57 AM
|
BLD-Final | 3/11/2002 | 3/12/2002 | 3/12/2002 | A | NR |
Tony Young
|
|
|
fn ###-####- bill--
framing inspection only, not final, framing ok to cover 3/12/2002 9:47:18 AM
|
BLD-Framing/Rough-in | 3/12/2002 | 3/12/2002 | 3/12/2002 | A | PASS |
Tony Young
|
|
|
Added by Inspector: 415 On 3/12/2002 9:44:36 AM
|
BLD-Framing/Rough-in | 3/7/2002 | 3/8/2002 | 3/8/2002 | A | PART |
Dave Hannah
|
|
|
###-#### BILL all but two items completed need to seal holes in drsft stop in attic need to fire caulk holes in top and bottom plates 3/8/2002 12:16:28 PM
|
BLD-Foundation | 2/25/2002 | 2/25/2002 | 2/25/2002 | P | CANC |
Tony Young
|
|
|
###-####
|
BLD-Framing/Rough-in | 2/25/2002 | 2/25/2002 | 2/25/2002 | P | PART |
Tony Young
|
|
|
bill 602--0369 2/25/2002 2:40:00 PM
c/n posted,,,ok to insulate 2/25/2002 4:26:04 PM
|
BLD-Conference | 1/23/2002 | 1/24/2002 | 1/24/2002 | A | PASS |
Tony Young
|
|
|
firedoor issues 1/23/2002 4:51:29 PM
|
BLD-Conference | 1/23/2002 | 1/23/2002 | 1/23/2002 | P | PASS |
Tony Young
|
|
|
write on plans about fire doors 1/23/2002 10:13:12 AM
|
BLD-Conference | 1/17/2002 | 1/22/2002 | 1/22/2002 | A | PART |
Tony Young
|
|
|
for conf--###-#### bill
conf. on fire doors, need to review 1/22/2002 4:02:20 PM
|
BLD-Conference | 1/22/2002 | 1/22/2002 | 1/22/2002 | P | PART |
Tony Young
|
|
|
update on fire doors 1/22/2002 11:25:57 AM
reviewed plans w/ 340 and 325 and determined that ext. glass doors do not need to be rated doors as noted on plans as long as exit corridors are maintained through other exits 1/23/2002 11:29:08 AM
|
BLD-Aging Inspection | 1/1/2002 | 1/1/2002 | 1/1/2002 | | PART |
Tony Young
|
|
|
wip 1/2/2002 8:53:52 AM
|
BLD-Framing/Rough-in | 11/1/2001 | 11/1/2001 | 11/1/2001 | P | PART |
Tony Young
|
|
|
###-####9
exterior firewall ok to cover, 11/1/2001 3:59:46 PM
|
BLD-Conference | 10/4/2001 | 10/5/2001 | 10/5/2001 | A | PASS |
Tony Young
|
|
|
fire dampers 10/4/2001 3:42:56 PM
met w/ carl 340, fire dampers reqd. in all ceilings 5 /1 hr const. reqmts 10/5/2001 10:30:46 AM
|
BLD-Conference | 10/2/2001 | 10/3/2001 | 10/3/2001 | A | CANC |
Tony Young
|
|
|
check on smoke/fire dampers, where? 10/2/2001 2:52:40 PM
|
BLD-Conference | 9/27/2001 | 9/28/2001 | 9/28/2001 | P | CANC |
Tony Young
|
|
|
9/27/2001 5:08:24 PM
|
BLD-Conference | 9/28/2001 | 9/28/2001 | 9/28/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/28/2001 11:53:28 AM w/ Bill, supt re 1hr const, dampers & firestops.
|
BLD-Conference | 9/10/2001 | 9/11/2001 | 9/11/2001 | P | PASS |
Tony Young
|
|
|
go over fire blocking w/ Bill, and what material 9/11/2001 11:02:47 AM
|
BLD-Framing/Rough-in | 9/10/2001 | 9/10/2001 | 9/10/2001 | P | PART |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 09/10/2001 at 10:23:15. Contact: .
walk through only, conf. on attic venting 9/10/2001 4:30:26 PM
|
BLD-Aging Inspection | 8/6/2001 | 8/6/2001 | 8/6/2001 | | PASS |
Tony Young
|
|
|
wip 8/7/2001 12:16:28 PM
|
BLD-Foundation | 5/31/2001 | 6/1/2001 | 6/1/2001 | A | PASS |
Dave Hannah
|
|
|
###-#### POURING AT 10
|
BLD-Foundation | 5/29/2001 | 5/29/2001 | 5/29/2001 | P | PART |
Tony Young
|
|
|
around 3:00 Bill ###-####
|
BLD-Footing | 5/24/2001 | 5/25/2001 | 5/25/2001 | A | PART |
Tony Young
|
|
|
Bill Wall ###-####
wip, natural soil ok 5/25/2001 9:27:05 AM
|
BLD-Conference | 5/22/2001 | 5/22/2001 | 5/22/2001 | P | PASS |
Tony Young
|
|
|
Bill ###-####
ftg soil compaction, etc. 5/22/2001 4:19:37 PM
|
BLD-Footing | 5/21/2001 | 5/21/2001 | 5/21/2001 | P | PART |
Tony Young
|
|
|
bill ###-####
ok after compaction test is passed, pending report//wip, verbal corrections 5/21/2001 1:53:41 PM
|
BLD-Footing | 5/17/2001 | 5/18/2001 | 5/18/2001 | A | PART |
Carl Dependahl
|
|
|
ft insp -- ###-####- bill...int ftgs, some of north fnd wall 5/18/2001 8:50:26 AM
|
Inspection Record Card- Bld | | | 5/17/2001 | | DONE |
|
|
|
|
BLD-Footing | 5/15/2001 | 5/16/2001 | 5/16/2001 | A | PART |
Tony Young
|
|
|
###-####
looked @ north 1/2 of ftgs, ok w/ verbal corrections, mti on the way, ? on if a s.i. was needed but architect said design is 2500 psi 5/16/2001 11:53:40 AM
|
(F) Reprint permit | | | 5/9/2001 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 5/8/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 5/4/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 5/4/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/4/2001 | | DONE |
|
|
|
left mess for jerrie wolfe that permit is ready
|
Plan resubmittals received | | | 5/3/2001 | | DONE |
|
|
|
Received one copy of revsied sheet E-2. Routed to mike o. KMM
|
Routing - PLAN CHECK | 5/3/2001 | | 5/3/2001 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/3/2001 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/3/2001 | | DONE |
|
|
|
Received two copies of revised sheets M-1, P-1. Routed to Mike O. KMM
|
Plan assigned to (MLO) | 12/15/2000 | | 5/3/2001 | | PASS |
Mike Otto
|
|
|
5/3/2001 14:44:39 MLO - activity updated through activity BLDA022 from case BLD00-03643.
|
Plan resubmittals received | | | 4/26/2001 | | DONE |
|
|
|
Received plan resubmittals from Jerrie Wolfe and Associates, A, M and E sheets plus small attached documents. 4/26/01 DAR
|
Routing Off Site - STRUCTURAL | 4/16/2001 | | 4/18/2001 | | FAIL |
|
|
|
Contacted PDQ to take plans to outside eng. KMM Corrections mailed to architect.
|
Routing - PLAN CHECK | 4/16/2001 | | 4/18/2001 | | FAIL |
|
|
|
corrections mailed to architect
|
Plan resubmittals requested | | | 4/18/2001 | | FAIL |
|
|
|
UBC corrections
|
Plan resubmittals received | | | 4/13/2001 | | DONE |
|
|
|
Received plan resubmittals two setsof A-1 through A-7 and small documents, forwarded same to Mike Otto. 4/13/01 DAR
|
Routing - FIRE | 2/26/2001 | | 2/26/2001 | | PASS |
|
|
|
|
Routing - PLUMBING | 1/26/2001 | | 1/30/2001 | | PASS |
|
|
|
|
Plan resubmittals received | | | 1/22/2001 | | DONE |
|
|
|
Received plan resubmittals from Jerrie Wolfe Architects. Three sets of Sheet P-1 forwarded same to Mike Otto. 1/22/01 DAR
|
Plan Review Completed(1st rev) | | | 1/18/2001 | | FAIL |
|
|
|
|
Routing - FIRE | 1/12/2001 | | 1/18/2001 | | FAIL |
|
|
|
faxed to architect
|
Routing Off Site - STRUCTURAL | 12/18/2000 | | 1/12/2001 | | FAIL |
|
|
|
contacted PDQ to take plans to outside eng. KMM CORRECTIONS SENT TO ARCHITECT
|
Plan resubmittals requested | | | 1/12/2001 | | FAIL |
|
|
|
UBC AND STRUCTURAL CORRECTIONS
|
Routing - PLAN CHECK | 12/27/2000 | | 1/12/2001 | | FAIL |
|
|
|
CORRECTIONS SENT TO ARCHITECT. MLO
|
Routing - PLUMBING | 12/22/2000 | | 12/27/2000 | | FAIL |
|
|
|
|
Routing - PUBLIC WORKS | 12/15/2000 | | 12/22/2000 | | PASS |
|
|
|
|
Routing - PLANNING | 12/22/2000 | | 12/22/2000 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 12/15/2000 | | DONE |
|
|
|
|
Application received | | | 12/15/2000 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 12/15/2000 | | DONE |
|
|
|
|
Routing Off Site - STRUCTURAL | 5/1/2001 | | | | |
|
|
|
|