Fee Review-notes | 12/21/2000 | 12/21/2000 | 4/3/2002 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 12/26/2000 | | 4/3/2002 | | VOID |
Dan Stuart
|
|
|
< $25,000
|
VOIDED CHANGE STATUS | | | 4/3/2002 | | DONE |
|
|
|
per dan s.
|
Routing - PLUMBING | 9/12/2001 | | 9/17/2001 | | FAIL |
|
|
|
|
Routing - PUBLIC WORKS | 9/17/2001 | | 9/17/2001 | | FAIL |
|
|
|
Public works environmental to review resubmittals when they come in. Per Louise W. kmm
|
Routing - PLAN CHECK | 9/12/2001 | 9/12/2001 | 9/12/2001 | | PEND |
|
|
|
Received corrected sheet a-1 indicating location of oil separator and installation per UPC and a cover letter declaring the ventilation requirments of sec. 1202 were to be design build by mechanical contractor and electrical contractor. The minimum design capablity based on the occupancy use group declared and 15 cfm per occupant was redlined on plans for field verification and approval.
|
Print Pending Permit.LaserJet4 | | | 9/12/2001 | | |
|
|
|
|
Case Summary (BLD) | | | 9/12/2001 | | |
|
|
|
|
Plan resubmittals received | | | 9/12/2001 | | DONE |
|
|
|
Received 3 revised sheets of A-1 and routed to Dan Stuart
|
Plan resubmittals received | | | 9/12/2001 | | |
|
|
|
Architect Cornel Larson provided additional sheet A-1 showing location of oil separator per UBC 311.2.3.1 to be installed per UPC. Routing plans to Public Works and Plumbing Div. for review of Oil Separator compliance.
|
Telephone call | | | 9/12/2001 | | DONE |
|
|
|
Called Walt Baumgartner, PW Environmental Div. to see if specific details are required for oil separator. Walt stated that detail of oil separator from plumbing div. would probalby work. I will route to plumbing for their review and comment and then to PW Environmental where wall will make copy to forward to Bench Sewer District to alert them of upcoming project. The Plumbing Div. will perform the field inspection for code compliance.
|
Telephone call | | | 9/12/2001 | | DONE |
|
|
|
Called Cornel Larson to let him know the oil separator was a code requirement not an option and that it needed to be shown on the plans. Also the need for direction for compliance with the ventilation requirements of section 1202 for the tenant. Cornel will contact owner and tenant and respond.
|
Received Certificate of Value | | | 9/11/2001 | | |
|
|
|
Received new certificate of value adding $5,500.00 for plumbing work and $4,500.00 for mechanical work, for initial values. Added $10,000.00 total to original value = $17,500.00
|
Routing - PLAN CHECK | 9/10/2001 | | 9/11/2001 | | FAIL |
|
|
|
Received resubmittals from architect. Plans failed to indicate the installation of an oil separator or trap per section 311.2.3.1 UBC and did not indicate the specifics for providing required ventilation for the tenant space. A value of 250 CFM exhaust was noted on plan for the area above the nitrous oxide but frash air requirements per section 1202 need to be met. Called Cornel Larson, architect to notify the plans are still incomplete. He said he would talk to the owner and tenant and provide response.
|
Plan resubmittals received | | | 9/11/2001 | | DONE |
|
|
|
Received three copies of revised sheets O, A-1, A-2, one copy of response letter. Routed to Dan Stuart. KMM
|
Routing - FIRE | 9/5/2001 | 9/5/2001 | 9/10/2001 | | PASS |
Bill Alexander
|
|
|
On condtion the UBC issues are resolved.
|
Plan resubmittals requested | | | 9/5/2001 | | FAIL |
|
|
|
Re-wrote items not being clearly answered or no answer from original review comments of March 12, 2001. Items #3, #5, # 6, #7, #8, and #13 needed further response. Copy faxed and mailed to architect.
|
Routing - PLAN CHECK | 3/16/2001 | | 9/5/2001 | | FAIL |
|
|
|
Inserted new plan sheets Ao, A-1 & A-2 into original plans. Reviewed architects cover letter in conjunction with new plan sheets submitted. Response to plan review comments incomplete. Response does not include data on ventilation for a new tenant space to meet code; floor drain system required per section 311.2.3.1 UBC was not addressed; unclear as to location of tenant occupancy separation wall between the "M" & "S3" occupancy of this tenant; new sheet A-2 is not dimension for elevations of fixture's showing compliance with accessibility; plan shows a new tunnel access to the restrooms that were not shown on the original plan submital and reports indicate done without permits or inspection. Further re-submittals are required.
|
Plan resubmittals received | | | 8/28/2001 | | |
|
|
|
received sheets 0, A-1, and A-2. Two copies of each. Routed to Dan Stuart. aml
|
Routing - FIRE | 3/13/2001 | | 3/16/2001 | | FAIL |
|
|
|
Need info on possible hazmat storage & use (N2O)
|
Plan Review Completed(1st rev) | | | 3/16/2001 | | FAIL |
|
|
|
|
BLD-Conference | 3/15/2001 | 3/15/2001 | 3/15/2001 | P | PASS |
Tom Arcoraci
|
|
|
Report of working w/out permits. Plans still under review. notified to stop all work until permit is issued 3/15/2001 2:45:07 PM
|
Plan resubmittals requested | | | 3/13/2001 | | FAIL |
|
|
|
Copy of plan review corrections & clarifications required mailed and faxed to architect.
|
Print Pending Permit.LaserJet4 | | | 3/13/2001 | | |
|
|
|
|
Routing - PLAN CHECK | 12/26/2000 | | 3/13/2001 | | FAIL |
|
|
|
Additional information and clarification required concerning use of reported hazardous products - Nitrous Oxide, and what has been done for heating and electrical before the project was discovered - all work done without permit and the tenant has occupied. Copy of corrections faxed and mailed to the architect for correction and response. Routing plans to fire code analyst for review.
|
Plans ACCEPTED BY PLAN TECH | | | 12/22/2000 | | DONE |
|
|
|
Plans not dimensioned. KMM
|
Received Certificate of Value | | | 12/21/2000 | | DONE |
|
|
|
|
Application received | | | 12/21/2000 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | | | |
|
|
|
|
Routing - PLAN CHECK | 9/19/2001 | | | | |
|
|
|
|