Permit Information
Permit NumberBLD01-00234
StatusFinaled
Name ST LUKES REGIONAL MEDICAL CTR
Site Address 190 E BANNOCK ST
Project NameST LUKES-EAST TOWER
Customer NumberSTL98-228
ePlanReviewNo
Description
(ST LUKES-EAST TOWER EXPANSION)(ED/NICU-1ST & 2ND FLR NEW TENANT BUILD-OUT & FINISH TO SHELL & CORE) To perform Tenant Improvement Construction of a 19,315 sq. ft. 1st floor for a new Emergency Department (ED) and 21,205 sq. ft. on the 2nd floor for Neonatal Intensive Care Unit (NICU). Construction to be of non-combustible framing with fire-resistive sheetrock covering to create 1-hour rated exit corridors, reception, lobbies & waiting areas; sleeping, exam, & treatment rooms; support area for associated staff and equipment; to install suspended ceiling grid system; electrical, mechanical & plumbing systems to satisy adopted city, state & federal requirements for this occupancy group; to divide patient sleeping & treatment areas into suites with 1-hour occupancy separation per code, each with required exit access systems to serve their particular area without exiting through another. All per approved plans, and attached plan review conditons by City of Boise Plan Review Agencies. Note : This building is fully fire sprinklered as a condition of the "I" occupancy classification. A CERTIFICATE OF OCCUPANCY IS REQUIRED FOR EACH NEW TENANT USE. PC#01-086/drs DRH#00-52
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Fee Review-notes11/21/200211/21/200211/21/2002 DONE
Permanent occupancy  7/22/2002 DONE
Perm. Occ. Cert. #9266 issued 7-22-02 to St. Luke's Hospital.
BLD-Final7/17/20027/18/20027/18/2002APASS
DetailsCarl Dependahl
###-####; ok for perm occ. 7/18/2002 11:43:31 AM
Permanent Occupancy 7/18/20027/18/2002 DONE
Details
BLD-Final7/17/20027/17/20027/17/2002PNR
DetailsCarl Dependahl
need verify all shell reqs... 7/17/2002 8:21:53 PM
BLD-Final7/15/20027/16/20027/16/2002ANR
DetailsCarl Dependahl
BLD-Final7/16/20027/16/20027/16/2002PCANC
DetailsCarl Dependahl
wendall ###-####
BLD-Conference7/16/20027/16/20027/16/2002PNR
DetailsCarl Dependahl
wendell 8668492
FIRE-Conference7/10/20027/10/20027/10/2002PPART
DetailsRick Jackson
wendel ###-#### told wendelll to get the occ cards turned in to Cathy 7/10/2002 2:41:21 PM
BLD-Conference6/25/20026/26/20026/26/2002APASS
DetailsCarl Dependahl
Wendell ###-#### w/ Rick j...re final status 6/26/2002 4:12:39 PM
BLD-Conference6/24/20026/25/20026/25/2002PPART
DetailsCarl Dependahl
wendell ###-#### hvac not finalled 6/25/2002 5:09:05 PM ? fire?? 6/25/2002 5:09:30 PM
BLD-Conference6/19/20026/20/20026/20/2002ANR
DetailsCarl Dependahl
wendel ###-#### need verify status w/ fire; keep c/n & temp status til resolved. 6/20/2002 11:22:08 AM
BLD-Conference6/19/20026/20/20026/20/2002PPART
DetailsCarl Dependahl
wendel ###-#### need to confirm fire insp status prior to perm occ... 6/24/2002 1:38:29 PM
BLD-Conference6/17/20026/18/20026/18/2002APASS
DetailsCarl Dependahl
###-#### wendell need verify all project permits as ok for final 6/17/2002 5:52:52 PM
BLD-Conference6/17/20026/18/20026/18/2002PPASS
DetailsCarl Dependahl
###-#### need verify other finals...complete expansion joint firestop install?? other finals? 6/18/2002 6:11:15 PM
FIRE-Final Inspection3/25/20023/26/20023/26/2002PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 03/25/2002 at 17:36:59. Contact: ###-####. checked all of the new dampers installed as part of the airbalancing problem; all funtioned under zone "a" alarm 3/26/2002 2:56:03 PM
BLD-Final3/19/20023/20/20023/20/2002PNR
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 03/19/2002 at 17:17:08. Contact: ###-####.
BLD-Final3/6/20023/7/20023/7/2002APART
DetailsCarl Dependahl
fn wendell ###-####--pending fire insp; ok for t/o; keep c/n. 3/7/2002 1:58:50 PM
FIRE-Final Inspection3/6/20023/7/20023/7/2002APASS
DetailsRick Jackson
wendell- ###-####
BLD-Conference3/6/20023/6/20023/6/2002PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 3/6/2002 4:50:17 PM w/ Rick J &supt...keep c/n , need fire final.
BLD-Final3/4/20023/5/20023/5/2002ANR
DetailsCarl Dependahl
###-#### WENDELL FOR OCCUPANCY need fire, glass spec's, complete prior c/n 3/5/2002 11:30:53 AM
FIRE-Final Inspection3/4/20023/5/20023/5/2002AFAIL
DetailsRick Jackson
###-#### WENDELL FOR OCCUPANCY standpipe in south stair obstructed by gaurdrail 3/6/2002 7:27:04 AM
BLD-Final3/5/20023/5/20023/5/2002AFAIL
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 3/5/2002 11:30:00 AM wendell ###-####; c/n need fire, achd, stairs, firestops,rails, etc. 3/5/2002 5:48:18 PM
FIRE-Final Inspection3/1/20023/4/20023/4/2002AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 03/01/2002 at 16:52:45. Contact: ###-####. stair enclosure doors not latching 3/4/2002 4:48:08 PM
BLD-Final3/1/20023/4/20023/4/2002AFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 03/01/2002 at 16:53:38. Contact: ###-####. Partial insp only, c/n; LISTING FOR EXPANSION JOINT, GYP INSTALL AT SHAFTS, NEED LISTING FOR 2HR GLASS BLOCK ASSY, COMPLETE PRIOR C/N... 3/4/2002 1:44:53 PM
BLD-Final3/4/20023/4/20023/4/2002PNR
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 3/4/2002 11:59:49 AM kee 3/4/2002 4:55:46 PM p c/n 3/4/2002 4:56:14 PM
FIRE-Final Inspection2/27/20022/28/20022/28/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 02/27/2002 at 17:55:20. Contact: ###-####. items not complete from previous c/n 2/28/2002 4:43:44 PM
FIRE-Alarm Testing2/19/20022/20/20022/20/2002AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 2/19/2002 4:26:16 PM Scheduled by Inspector: 409 On 2/19/2002 4:24:35 PM smokes in bathrooms on second floor to heat detectors; some dampers not closing 2/20/2002 11:42:18 AM
FIRE-Conference2/15/20022/19/20022/19/2002PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 02/15/2002 at 13:40:37. Contact: ###-####. tested alarms; got to the third floor; need detectors at exhaust dampers on 4th floor; NAC on 4th floor not reporting battery loss trouble 2/19/2002 4:25:46 PM
FIRE-Alarm Testing2/14/20022/15/20022/15/2002AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 02/14/2002 at 15:11:06. Contact: ###-####. See FIR01-00435 for notes 2/15/2002 12:35:47 PM
BLD-Framing/Rough-in2/14/20022/15/20022/15/2002APART
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 2/14/2002 4:32:46 PM wendell 8668492; OK to place tiles at grid 1st & 2nd fl; Rec'd 2hr. glass block ass'y for occupancy separation wall at ambulance bay...will review w/ plan chk. Still req's spec. insp's affidavit for occupancy 2/19/2002 1:14:06 PM
BLD-Wall cover2/14/20022/14/20022/14/2002PNR
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 02/14/2002 at 10:20:03. Contact: ###-####....need listing for glass block at 2hr wall 2/14/2002 4:37:02 PM
BLD-Framing/Rough-in2/11/20022/12/20022/12/2002AFAIL
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 2/11/2002 4:19:02 PM wendell 8668492,c/n: verify/justify glazed block at 2hr wall at ambulance bay at north ext; complete firestops, chk stair rails... 2/12/2002 6:17:26 PM
BLD-Wall cover2/11/20022/11/20022/11/2002PNR
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 02/11/2002 at 08:33:23. Contact: ###-####.
BLD-Framing/Rough-in1/31/20021/31/20022/4/2002PPART
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 1/31/2002 12:13:08 PM ###-####, wip, keep c/n. complete firestops at rated const. 2/4/2002 9:15:08 AM
BLD-Conference1/31/20022/1/20022/1/2002APASS
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 1/31/2002 5:55:22 PM , complete c/n prior to grid tile 2/1/2002 4:59:35 PM
BLD-Framing/Rough-in1/30/20021/31/20021/31/2002APART
DetailsCarl Dependahl
WENDEL ###-####; w 1/31/2002 5:35:11 PM ip, keep c/n 1/31/2002 5:40:40 PM
BLD-Framing/Rough-in1/14/20021/14/20021/14/2002PFAIL
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 1/14/2002 9:03:07 AM ###-#### c/n, firestops at walls , floors, grid clg, dampers, exit enclosures, etc. 1/14/2002 1:41:41 PM
BLD-Framing/Rough-in1/8/20021/9/20021/14/2002ANR
DetailsCarl Dependahl
Scheduled by Inspector: 340 On 1/8/2002 4:36:06 PM ###-####, need fire ok 1/14/2002 9:03:45 AM
FIRE-Alarm Testing1/7/20021/8/20021/8/2002ANR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 01/07/2002 at 14:59:07. Contact: ###-####. no alarm test; walked through building with Stan and Wendell; numerous penetrations 1/8/2002 11:34:25 AM
BLD-Framing/Rough-in1/8/20021/8/20021/8/2002PNR
DetailsCarl Dependahl
###-#### complete firestopping thru-out, recall. no insp performed. 1/8/2002 5:57:36 PM
BLD-Framing/Rough-in12/21/200112/24/200112/24/2001APART
DetailsRuss Owen
Scheduled by Inspector: 340 On 12/21/2001 7:07:32 PM ###-####...St Lukes; sorry, couldn't get to it Friday...c/n issued do not place grid seal penetrations in firewalls and smoke barriers. 12/24/2001 12:16:10 PM
BLD-Wall cover12/20/200112/21/200112/21/2001ANR
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 12/20/2001 at 10:28:08. Contact: ###-####. unable to contact at this time. 12/21/2001 7:07:59 PM
BLD-Framing/Rough-in12/19/200112/20/200112/20/2001ANR
DetailsCarl Dependahl
###-#### WENDLE ...recall 12/20/2001 3:04:08 PM
BLD-Aging Inspection12/12/200112/12/200112/12/2001 NR
DetailsCarl Dependahl
st lukes NICU; wip 12/18/2001 3:49:32 PM
Fee Review-notes2/1/20012/1/200112/12/2001 DONE
no cert information call for final value
BLD-Framing/Rough-in10/11/200110/12/200110/12/2001ANR
DetailsCarl Dependahl
Scheduled by Inspector: 408 On 10/11/2001 1:37:37 PM taken by 408. 10/12/2001 11:36:01 AM
BLD-Framing/Rough-in10/12/200110/12/200110/12/2001APART
DetailsTom Arcoraci
Scheduled by Inspector: 408 On 10/12/2001 10:37:47 AM 2nd floor plumbing pents ok for cover in walls section c and d 10/12/2001 11:10:28 AM
BLD-Wall cover10/10/200110/11/200110/11/2001ANR
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 10/10/2001 at 12:28:39. Contact: ###-####.
BLD-Framing/Rough-in9/12/20019/12/20019/12/2001PPART
DetailsCarl Dependahl
Added by Inspector: 340 On 9/12/2001 1:53:39 PM soiled linen rm 1st fl, int penetrations ok...need chk dampers.
BLD-Framing/Rough-in9/7/20019/7/20019/7/2001PPART
DetailsCarl Dependahl
###-#### penetrations of med gas & elec ok at E-W 1st fl firewall ok. (corridor) 9/12/2001 1:52:27 PM
BLD-Conference9/7/20019/7/20019/7/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 9/7/2001 3:33:40 PM ok to use 3m pads at med gas teminations at rated walls
BLD-Wall cover8/20/20018/20/20018/20/2001PNR
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 08/20/2001 at 07:37:52. Contact: ###-####....need listing for gas outlet firestops, complete med gas r/i 8/21/2001 11:52:59 AM
BLD-Framing/Rough-in8/8/20018/8/20018/8/2001PFAIL
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 08/08/2001 at 07:31:59. Contact: ###-####. c/n firestops, 1st fl areas c&d. ok to continue or begin wall cover. 8/9/2001 1:01:19 PM
BLD-Conference8/8/20018/8/20018/8/2001PPASS
DetailsCarl Dependahl
Added by Inspector: 340 On 8/8/2001 4:42:11 PM w/ Wendall at site, re stair & elev shafts; complete r/i's for cover of other areas
Issue & PRINT to be Invoiced  7/24/2001 DONE
Inspection Record Card- Bld  7/23/2001 DONE
Print Occupancy Form  7/23/2001 DONE
Telephone call  7/23/2001 DONE
called Stan Brown at ###-####
Routing - FIRE7/18/20017/18/20017/20/2001 PASS
Routing - PLAN CHECK7/20/2001 7/20/2001 PASS
Approved as noted on plans with the plan review comments / conditions attached by reviewing agencies considered a part of the approved plans requiring full compliance before final approval and occupancy certificate can be issued.
PLANS/APPL TAKEN TO FRONT DESK  7/20/2001 PASS
Approved as noted and attched. Routing for issuance of permit.
Plan assigned to (DRS)2/5/2001 7/20/2001 PASS
DetailsDan Stuart
7/20/2001 14:49:12 DRS - activity updated through activity BLDA022 from case BLD01-00234.
Routing - PLAN CHECK7/16/20017/16/20017/18/2001 PEND
INSERTED RESUBMITTALS INTO ORIGINAL PLANS, REVIEWED FOR CODE COMPLIANCE WITH CONDITIONS REQUESTED AT PRELIMINARY REVIEW. WAITING FOR FURTHER CLARIFICATION ON ALLOWED GLAZING AN PROPER TESTING FOR USE OF GREATER THAN 100 SQ. INCHES AS REQUIRED BY CODE WHEN DOOR IS RATED AT 60 MINUTES OR GREATER. HAVE E-MAILED OR FAXED FOR ADDITIONAL PROOF OF CODE COMPLIANCE FROM CURRIES DOOR MANUFACTURE AND FIRELIGHT GLAZING TO SEE IF SUBMITTED DETAILS CAN BE PRESENTED TO BUILDING OFFICIAL FOR APPROVAL AS ALTERNATE. ROUTING PLANS TO FIRE CODE ANALYST FOR RE-REVIEW.
Routing - PLAN CHECK7/3/2001 7/5/2001 PEND
RECEIVED RE-SUBMITTALS TO PRELIMINARY COMMENTS. PLANS ON HOLD UNTIL RETUN FROM VACATION ON 7/16/01
Plan resubmittals received  7/5/2001 DONE
Received plan resubmittals from ZGA Architects, forwarded same to Dan Stuart. 7/5/01 DAR
Routing - FIRE6/29/2001 7/3/2001 FAIL
gas storage room questions
Routing - PLAN CHECK6/20/20016/20/20016/29/2001 FAIL
Corrections required. Copy faxed & mailed to architect. Routing to fire for review.
Plan resubmittals requested  6/28/2001  
Faxed copy of plan review corrections to architect. Had previously reviewed questions on door schedule with architect by phone.
Routing - PLUMBING6/5/2001 6/14/2001 PASS
if coffee makers are supplied with a potable water connection the provissions of section 603 shall apply, the plans call foe solid covers on the cabinets, if so , extend hub drain above counter top, Hill-Rom medaes medical gas and vacuum sizing information has been accepted for this project design, however verification of flow requirements for owner supplied equipment is essectial and must be met. per resubmitted plans dated 6/8/01
Routing - PLAN CHECK6/14/2001 6/14/2001 PEND
took to dan s 6/14/2001. Received plans from plumbing plan review - approved. Preparing to review next.
Plan resubmittals received  6/12/2001 DONE
Received plan resubmittals from ZGA in the form of small documents, forwarded same to Dan Stuart. 6/12/01 DAR
Plan resubmittals received  6/8/2001 DONE
Plan resubmittals received from ZGA for Bill Vandergrift, One set of resubmittals, forwarded same to Dan Stuart. 06/8/01 DAR
Routing - PLAN CHECK2/28/2001 6/5/2001 FAIL
Plans routed back to plumbing plan reviewer for re-review of resubmitals for med gas and water system requirements.
Routing - PLUMBING2/9/2001 2/27/2001 FAIL
please provide your water sizing calculations, include fixture unit loading for each pipe size, branches look undersized. provide a floor sink at all areas where an r.p. is provided for a coffee maker or ice mechine do not locate with in a cabinet, supply medical gas and vacuum piping serving trama rooms 1EE108 and 1EE109 as prescribed in section 4.3.1.2.2.d.4 NFPA99. each room requires its own emergency shutoff valves, waste anesthetic gas disposal system riser diagram page M4.2 shows connection to medical air plant, is this correct?, please provide a copy of your medical gas and vacuum calculations for review per section 1304.2 of the 1997 upc.
Pending Assignment by MYS2/5/2001 2/5/2001 DONE
DetailsMarlene Southard
Plans ACCEPTED BY PLAN TECH  2/2/2001 DONE
Received Certificate of Value  2/1/2001 DONE
Application received  2/1/2001  
Routing - PUBLIC WORKS2/5/2001 2/9/2000 PASS