Permit Information
Permit NumberBLD01-00294
StatusExpired
Name QWEST
Site Address 619 W BANNOCK ST
Project NameAT&T BLDG-6TH FLR
Customer Number 
ePlanReviewNo
Description
*QWEST* 6th Floor Office Space Demolition. To demolish an 11,070 sq. ft. portion of the existing 15,530 sq. ft. 6th floor, previously finished for use as office space. To remove all interior ceiling grid & components; remove smoke detectors mounted on ceiling tile surface (smoke detectors above the existing ceiling grid to remain in place and active); to remove floor finishes & trim; remove mechanical duct branch lines, diffusers & controls; remove light fixtures, conduit & wiring within rooms 601 & 602 designated on plans; remove partion walls as indicated on plans and maintain the existing fire alarm and sprinkler systems within the entire 6th area, protecting against damage and keeping fully functional during the demolition phase to maintain fire / life safety. NOTE: NO NEW CONSTRUCTION OR USE OF THIS FLOOR AREA IS ALLOWED WITHIN THE SCOPE OF THIS PERMIT. Separate plans and application for remodel of the space for future occupancy and use are required. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection5/30/20035/30/20035/30/2003 DONE
DetailsCarl Dependahl
demo w/ larger project 5/30/2003 9:22:10 AM
DOC - Permit Expired5/30/20035/30/20035/30/2003APASS
DetailsCarl Dependahl
Expired by inspector at 5/30/2003 9:22:13 AM
Inspection Record Card- Bld  2/9/2001 DONE
Telephone call  2/9/2001 DONE
called talked to annette gave dollar amount
Issue PAID IN FULL permit  2/9/2001 DONE
Plan assigned to (DRS)2/6/20012/6/20012/8/2001 PASS
DetailsDan Stuart
2/8/2001 11:42:47 DRS - activity updated through activity BLDA022 from case BLD01-00294.
PLANS/APPL TAKEN TO FRONT DESK  2/8/2001 PASS
DEMO PERMIT IN PREPARATION FOR FUTURE T.I. SEPARATE PLANS AND APPLICATION REQUIRED FOR REVIEW AND APPROVAL FOR T.I.
Plan Review Report  2/8/2001  
COPY OF CONDITION FAXED AND MAILED TO ARCHITECT AFTER REVIEW BY THE FIRE CODE ANALYST, BILL ALEXANDER & SAM ROGERS.
Plan Reviewer's activity  2/7/2001  
NOTIFIED THE FIRE DEPARTMENT THAT AN APPLICATION FOR DEMOLITION OF A MAJOR PORTION OF THE 6TH FLOOR HAS BEEN APPLIED FOR. THE REMODEL OF THE 6TH FLOOR FOR OFFICE USE IN 1992 TRIGGERED THE REQUIREMENTS FOR UPGRADE OF THE BUILDING AS AN EXISTING HIGH RISE FACILITY AND THE SPECIFIC REQUIREMENTS WERE ESTABLISHED BY AN 'APPEALS BOARD HEARING'. THERE APPEAR TO BE DIFFERENT FEELINGS WITHIN THE FIRE DEPARTMENT AT THIS TIME IN REGARDS TO THE OMMISSION OF SPRINKLER SYSTEM IN ANY PART OF THE BUILDING AND THIS WILL NEED TO BE ADDRESSED WITH THE FIRE DEPARTMENT AS PART OF THE PLAN SUBMITTAL FOR THE REMODEL OF THIS 6TH FLOOR AREA.
Telephone call  2/7/2001 DONE
CALLED BOB SMITH, ARCHITECT FOR QWEST TO INFORM HIM THAT THE REMODEL OF THIS 6TH FLOOR FROM THE OFFICE USE APPROVED UNDER THE 1992 LETTER OF AGREEMENT ON FILE MAY REQUIRE THE NEW PROPOSED TELEPHONE EQUIPMENT EXCHANGE USE TO BE FULLY SPRINKLED RATHER THAN ALLOWING THE CONDITIONS OF SECTION 904.4 (3804, 1991 UBC) TO APPLY. THIS WILL BE DETERMINED THROUGH AGREEMENT AND PROPOSALS WITH THE FIRE & BUILDING DEPARTMENTS AT TIME OF PLAN SUBMITTALS. THE FEELING AT THIS TIME IS THAT THE SPRINKLER SYSTEM WILL HAVE TO BE INSTALLED UNDER FIRE FLOW REQUIREMENTS OF APPENDIX CHAPTER III-A 1997 UFC.
Plan Reviewer's activity  2/7/2001  
FAXED COPIY OF ORIGINAL LETTER OF AGREEMENT SIGNED BY ALL PARTIES ORIGINALLY INVOLVED AND THE SPECIFIC AGREEMENT CONDITIONS ESTABLISHED TO BOB SMITH AT HIS REQUEST.
Application received  2/6/2001