Fee Review-notes | 8/29/2001 | 8/29/2001 | 1/29/2002 | | DONE |
|
|
|
matt-###-####
|
BLD-Final | 10/2/2001 | 10/3/2001 | 10/3/2001 | A | PASS |
Russ Owen
|
|
|
###-####. ok permanent occupancy. 10/3/2001 10:17:59 AM
|
Permanent Occupancy | | 10/3/2001 | 10/3/2001 | | DONE |
|
|
|
|
Permanent occupancy | | | 10/3/2001 | | DONE |
|
|
|
Perm. Occ. Cert. #8851 issued 10-3-01 to Jack in the Box.
|
BLD-Final | 9/12/2001 | 9/13/2001 | 9/13/2001 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 09/12/2001 at 13:29:42. Contact: ###-####. need s-i final letter need to support cantilevered projection above front counter,need to fire tap 1 hr shafts. all other signatures have been signed for permanent oc. wright brothers is contact ###-####. 9/13/2001 11:11:11 AM
|
BLD-Final | 9/12/2001 | 9/13/2001 | 9/13/2001 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 09/12/2001 at 13:29:42. Contact: ###-####. need s-i final letter need to support cantilevered projection above front counter,need to fire tap 1 hr shafts. all other signatures have been signed for permanent oc. wright brothers is contact ###-####. 9/13/2001 11:11:11 AM
|
Temporary occupancy | | | 9/4/2001 | | PART |
|
|
|
Temp. Occ. Cert. #4588 issued 9-4-01 to Jack in the Box.
|
BLD-Final | 8/31/2001 | 8/31/2001 | 8/31/2001 | P | PART |
Russ Owen
|
|
|
###-####ok temp oc c/n posted for other items. 8/31/2001 3:54:22 PM
|
BLD-Conference | 8/31/2001 | 8/31/2001 | 8/31/2001 | P | CANC |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/31/2001 at 08:39:10. Contact: ###-####.
|
FIRE-Final Inspection | 8/31/2001 | 8/31/2001 | 8/31/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 8/31/2001 3:22:22 PM
|
FIRE-Final Inspection | 8/30/2001 | 8/30/2001 | 8/30/2001 | P | CANC |
Joe Tawney
|
|
|
fire fn - cathy ###-#### Cancel Reschedule 8/30/2001 5:13:49 PM
|
FIRE-Final Inspection | 8/29/2001 | 8/29/2001 | 8/29/2001 | P | FAIL |
Joe Tawney
|
|
|
Reinsp Fail C/N issued 8/29/2001 2:07:39 PM
|
BLD-Conference | 8/28/2001 | 8/28/2001 | 8/28/2001 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/28/2001 at 10:53:58. Contact: ###-####. kitchen grid. 8/28/2001 2:09:49 PM
|
BLD-Conference | 8/26/2001 | 8/27/2001 | 8/27/2001 | A | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/26/2001 at 20:17:39. Contact: ###-####. kitchen grid. 8/27/2001 11:34:57 AM
|
FIRE-Alarm Testing | 8/24/2001 | 8/27/2001 | 8/27/2001 | A | FAIL |
Joe Tawney
|
|
|
###-#### matt Final Fail Hoods tested OK. Need air bal report. Not ready on other issues 8/27/2001 11:14:48 AM
|
BLD-Conference | 8/24/2001 | 8/24/2001 | 8/24/2001 | P | CANC |
Joe Tawney
|
|
|
Cancel 8/24/2001 1:27:39 PM
|
BLD-Conference | 8/20/2001 | 8/21/2001 | 8/21/2001 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/20/2001 at 21:49:57. Contact: ###-####.front dining grid ok. 8/21/2001 4:05:32 PM
|
BLD-Conference | 8/15/2001 | 8/16/2001 | 8/16/2001 | A | CANC |
Tom Arcoraci
|
|
|
###-####
|
BLD-Framing/Rough-in | 8/16/2001 | 8/16/2001 | 8/16/2001 | P | FAIL |
Tom Arcoraci
|
|
|
grid ceiling Matt ###-#### GRID INCOMPLETE MADE VERBAL TO SUPER WILL NEED TO RECALL 8/16/2001 3:06:56 AM
|
BLD-Conference | 8/9/2001 | 8/9/2001 | 8/9/2001 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/09/2001 at 07:35:05. Contact: ###-####.. need to sheetrock above shafts, built as per detail, NOTE: detail porly drawn at roof penetration of shafts now constructed But constructed as per plans. 8/9/2001 4:25:04 PM
|
BLD-Conference | 8/7/2001 | 8/7/2001 | 8/7/2001 | P | PART |
Russ Owen
|
|
|
###-#### MATT
. working on shafts for grease hoods, 8/7/2001 3:46:32 PM
|
BLD-Framing/Rough-in | 7/24/2001 | 7/25/2001 | 7/25/2001 | A | PART |
Russ Owen
|
|
|
Matt ###-####ok to sheetrock ,still needs a draft stop at inside attic and need 1 hour shafts inspected. 7/25/2001 10:56:42 AM
|
BLD-Framing/Rough-in | 7/23/2001 | 7/24/2001 | 7/24/2001 | A | NR |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/23/2001 at 17:28:53. Contact: ###-####.
|
BLD-Framing/Rough-in | 7/23/2001 | 7/23/2001 | 7/23/2001 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/23/2001 at 09:55:29. Contact: ###-####.c/n posted ok to insulate. 7/23/2001 3:41:13 PM
|
BLD-Wall cover | 7/23/2001 | 7/23/2001 | 7/23/2001 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/23/2001 at 09:57:06. Contact: ###-####.c/n posted ,ok to insulate. 7/23/2001 3:40:50 PM
|
BLD-Framing/Rough-in | 7/12/2001 | 7/12/2001 | 7/12/2001 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/12/2001 at 10:54:49. Contact: ###-####. 7/13/2001 8:48:05 AM. need to construct some of the roof area mansard as per the structural details as shown on plans,i have gone over these areas with contractor,will recall before covering. 7/13/2001 8:52:45 AM
|
BLD-Framing/Rough-in | 7/9/2001 | 7/10/2001 | 7/10/2001 | A | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/09/2001 at 14:21:27. Contact: ###-####.c/n posted. 7/10/2001 11:58:18 AM
|
BLD-Footing | 6/21/2001 | 6/22/2001 | 6/22/2001 | A | PASS |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/21/2001 at 13:22:13. Contact: ###-####.
|
BLD-Foundation | 6/21/2001 | 6/22/2001 | 6/22/2001 | A | PASS |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/21/2001 at 13:22:50. Contact: ###-####.
|
BLD-Foundation | 6/21/2001 | 6/21/2001 | 6/21/2001 | P | CANC |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/21/2001 at 08:05:19. Contact: ###-####.
|
BLD-Footing | 6/21/2001 | 6/21/2001 | 6/21/2001 | P | CANC |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/21/2001 at 08:06:13. Contact: ###-####.
|
BLD-Footing | 6/19/2001 | 6/20/2001 | 6/20/2001 | P | FAIL |
Russ Owen
|
|
|
###-#### verbal c/n with contractor from wright brothers, front wall req 2 bars top and bottom also 6 in wider footing at the front entry also inst shear footings require a 6 in raise above the slab,also clearance to earth at several locations, not this is a mono pour for footing and slab. 1/20/2002 5:18:37 PM
|
(F) Reprint permit | | | 5/14/2001 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 5/11/2001 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 5/2/2001 | | 5/4/2001 | | |
|
|
|
|
Routing - PLANNING | 5/4/2001 | | 5/4/2001 | | PASS |
|
|
|
Approved per CUP00-158 (Dave Abo), and per DRH01-29 (Marty Santoyo).
|
Routing - PLAN CHECK | 5/4/2001 | | 5/4/2001 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/4/2001 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 5/4/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 5/4/2001 | | DONE |
|
|
|
|
Telephone call | | | 5/4/2001 | | DONE |
|
|
|
talked to rick to verify plans are ready
|
Plan assigned to (JCM) | 3/9/2001 | | 5/4/2001 | | PASS |
John Menard
|
|
|
5/4/01 13:44:57 JCM - activity updated through activity BLDA022 from case BLD01-00588.
|
Routing - PLANNING | 3/14/2001 | | 5/3/2001 | | PEND |
|
|
|
Pending Design Review approval.
|
Routing - PUBLIC WORKS | 5/1/2001 | | 5/2/2001 | | PASS |
|
|
|
|
Routing - PLANNING | 5/2/2001 | | 5/2/2001 | | FAIL |
|
|
|
Plans do not comply with CU conditions; please note requirement for cross-access agreements.
|
Routing - PLAN CHECK | 4/27/2001 | | 5/1/2001 | | |
|
|
|
|
Routing - FIRE | 4/27/2001 | | 4/27/2001 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 4/5/2001 | | 4/27/2001 | | |
|
|
|
|
Plan resubmittals received | | | 4/12/2001 | | DONE |
|
|
|
Received plan resubmittals from BRS, Rick Toews, small documents and two sets of sheet A3.0. 4/12/01 DAR
|
Routing - FIRE | 4/2/2001 | | 4/5/2001 | | FAIL |
|
|
|
hydrant?
|
Plan Review Completed(1st rev) | | | 4/5/2001 | | FAIL |
|
|
|
|
Plan resubmittals requested | | | 4/2/2001 | | FAIL |
|
|
|
Mailed the architect of record a copy of the comment list requesting revisions. JCM
|
Routing - PLAN CHECK | 3/21/2001 | | 4/2/2001 | | |
|
|
|
|
Routing - PLUMBING | 3/16/2001 | | 3/21/2001 | | PASS |
|
|
|
premis backflow preventor must be a 2", fixture schedule calls for a 1 1/2". ceiling space may be a return air plenum, if so , all material in the ceiling must be approved for use in a plenum, verify
|
Routing - PUBLIC WORKS | 3/9/2001 | | 3/14/2001 | | FAIL |
|
|
|
Requires drainage plan revision pretreat. per Brian M. KMM
|
Application received | | | 3/9/2001 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 3/9/2001 | | DONE |
|
|
|
|
Received Certificate of Value | | | 3/9/2001 | | DONE |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 3/9/2001 | | DONE |
|
|
|
|