Fee Review-notes | 7/7/2003 | 7/7/2003 | 7/7/2003 | | DONE |
|
|
|
No fire review fees were charged.
|
Case Summary (BLD) | | | 4/2/2003 | | |
|
|
|
|
Permanent occupancy | | | 5/17/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9142 issued 5-17-02 to the River Quarry Apartments II.
|
BLD-Final | 5/11/2002 | 5/13/2002 | 5/13/2002 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/11/2002 at 10:55:53. Contact: ###-####. final ok 5/13/2002 9:55:03 AM
|
BLD-Final | 5/9/2002 | 5/10/2002 | 5/10/2002 | A | FAIL |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/09/2002 at 13:46:32. Contact: ###-####.
|
BLD-Final | 5/3/2002 | 5/6/2002 | 5/6/2002 | A | PART |
Jim Storey
|
|
|
1. inside units ok for final
2. (Guardrail height) The top of guardrails shall not be less than 42" in height. The top of guardrails for stairways, exclusive of their landings, shall be placed not less than 34" above the nosing of stair treads, measured vertically. (1997 UBC 509.2 and Exception #3)
|
BLD-Final | 5/2/2002 | 5/3/2002 | 5/3/2002 | P | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/02/2002 at 16:19:36. Contact: ###-####. out of time. 5/3/2002 5:16:49 PM
|
FIRE-Final Inspection | 5/3/2002 | 5/3/2002 | 5/3/2002 | P | PASS |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 5/3/2002 4:29:28 PM
|
Permanent Occupancy | | 5/3/2002 | 5/3/2002 | | DONE |
|
|
|
|
Code Occupancy Approval | | | 4/26/2002 | | PASS |
|
|
|
|
FIRE-Final Inspection | 4/24/2002 | 4/25/2002 | 4/25/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### sound level in bedrooms below 70 db 4/25/2002 11:27:00 AM
|
BLD-Conference | 1/11/2002 | 1/14/2002 | 1/14/2002 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 01/11/2002 at 13:25:16. Contact: ###-####. 2 hr wall ok for all memprane penatations south side. ok to cover all walls and ceilling. 1/14/2002 2:30:37 PM
|
BLD-Energy code compliance | 1/9/2002 | 1/10/2002 | 1/10/2002 | A | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 01/09/2002 at 11:17:08. Contact: ###-####.
|
BLD-Framing/Rough-in | 1/4/2002 | 1/7/2002 | 1/7/2002 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 01/04/2002 at 11:43:24. Contact: ###-####. patch 2 hr wall/ extened 1 hr behind shower. ok to insulate. 1/7/2002 3:24:25 PM
|
BLD-Framing/Rough-in | 1/3/2002 | 1/4/2002 | 1/4/2002 | P | CANC |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 01/03/2002 at 09:48:21. Contact: ###-####. via called to canc. 1/4/2002 1:53:09 PM
|
BLD-Aging Inspection | 10/15/2001 | 10/15/2001 | 10/15/2001 | | PASS |
Jim Storey
|
|
|
wip 10/15/2001 8:36:35 AM
|
BLD-Concrete | 8/14/2001 | 8/15/2001 | 8/15/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/14/2001 at 12:40:56. Contact: ###-####. placed w/special insp. 8/15/2001 11:58:14 AM
|
BLD-Foundation | 7/24/2001 | 7/25/2001 | 7/25/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 07/24/2001 at 15:01:25. Contact: ###-####. placed with special insp pending report. 7/25/2001 10:18:20 AM
|
BLD-Footing | 6/28/2001 | 6/29/2001 | 6/29/2001 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 06/28/2001 at 11:47:48. Contact: ###-####. placedwith special insp. 6/29/2001 9:13:00 AM
|
Issue PAID IN FULL permit | | | 6/12/2001 | | DONE |
|
|
|
|
Plan Reviewer's activity | | | 6/6/2001 | | PASS |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 6/6/2001 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/6/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/6/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/6/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/6/2001 | | DONE |
|
|
|
PERMIT READY
|
Plan assigned to (M_P) | 3/14/2001 | | 6/6/2001 | | PASS |
Mike Phillips
|
|
|
6/6/2001 10:01:15 M_P - activity updated through activity BLDA022 from case BLD01-00654.
|
Routing - FIRE | 5/14/2001 | 5/15/2001 | 5/15/2001 | | PASS |
Bill Alexander
|
|
|
|
Plan Reviewer's activity | | | 5/14/2001 | | FAIL |
|
|
|
Additional information required for further review
|
Routing - PLAN CHECK | 4/11/2001 | | 5/14/2001 | | FAIL |
|
|
|
Routing to fire.
|
Routing - PLUMBING | 4/6/2001 | | 4/11/2001 | | PASS |
|
|
|
provide a cleanout at the base of each waste or soil stack, 12 unit water system isometric didn't show clothes washers on the 2nd or 3rd floors, 16 page P4.0- use approved material for inside the building, install main water risers in warm wall, pipe water heater drip pan drains to exterior individually, water piping in exterior walls for kitchen sinks must be protedted from freezing
|
Routing - PLANNING | 3/29/2001 | | 4/4/2001 | | FAIL |
|
|
|
|
Routing - PARKS DEPARTME | 3/22/2001 | | 3/29/2001 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 3/20/2001 | | 3/22/2001 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 3/20/2001 | | DONE |
|
|
|
|
Application received | | | 3/14/2001 | | |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 3/14/2001 | | |
|
|
|
|