Permit Information
Permit NumberBLD01-00955
StatusFinaled
Name PAM OIL CO / ROB STAPLEY
Site Address 1051 W BOEING ST
Project Name 
Customer Number 
ePlanReviewNo
Description
*PAM OIL CO.* To install Steel Storage Racking within existing warehouse per engineered details. Being installed in conjunction with BLD99-00711, Tenant Improvement for purpose of obtaining a Certificate of Occupancy when both permits (racks & T.I.) have been finaled. Install plaques per code / engineering, to identify allowable maximum loads for each load storage rack unit. Location and installation to be per floor plan layout by Matt Rhees, Cole | Assoc. architect, and the structural engineering, Sal E. Fateen, Seizmic Material Handling Engineering; Bryce Stapley, Stapley Engineering (copy attached). A " Letter of Completion / Compliance" required as evidence of having received final inspection and approval for racking installation. Height of specific products for storage to maintain "S1" occupancy classification SHALL be maintained per the T.I. plan currently under review & Jim Call, F.P.E. call out per Fire Code. NOTE: Hazardous Materials SHALL NOT exceed quantities allowed per Tbls. 3-D & 3-E, 1997 UBC & per 1997 UFC. PC#01-323/drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (BLD)  9/7/2016 DONE
Case Summary (BLD)  9/7/2016 DONE
BLD-Final9/27/20019/27/20019/27/2001PPASS
DetailsJim Storey
###-#### final ok cathy to issue l/c. 9/27/2001 2:16:32 PM
FIRE-Final Inspection8/30/20018/30/20018/30/2001PPASS
DetailsRick Jackson
Added by Inspector: 409 On 8/30/2001 3:54:46 PM
BLD-Final8/30/20018/30/20018/30/2001PPART
DetailsJim Storey
Added by Inspector: 301 On 8/30/2001 3:58:10 PM temp ok no use of non compliant stair and racks in blocked off area only one area. stair and end gaurds ordered.
FIRE-Final Inspection8/23/20018/24/20018/24/2001AFAIL
DetailsJoe Tawney
###-#### rob Final Fail racks not installed per approved plan 8/24/2001 12:30:28 PM
BLD-Framing/Rough-in8/23/20018/23/20018/23/2001PFAIL
DetailsJim Storey
1. (Stairway rise and run) The rise of steps and stairs shall not be less than 4 inches nor more than 7 inches. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch. Except as permitted for circular, winding, and spiral stairways, the run shall not be less than 11 inches as measured horizontally between the vertical planes of the furthermost projection of adjacent treads or nosings. Stair treads shall be of uniform size and shape, except the largest tread run within any flight of stairs shall not exceed the smallest by more than 3/8 inch. (1997 UBC 1003.3.3.3) Note the exception to tread and riser dimensions for private stairways and stairways to unoccupied roofs and. Also, note the exception to dimensions of risers adjoining a sloping public way. need per pln on one stair approved by planreview not per ubc. 2 3/8 anchor bolts must be replaced to 1/2 x 3 1/2 per engineering 4. saftey clips required on beams.5.barrior post protection at ends of racks in forklift route 6. handrail 34 to 38. 6. fire insp required. 8/23/2001 3:16:51 PM
BLD-Aging Inspection8/16/20018/16/20018/16/2001 PASS
DetailsJim Storey
wip 8/23/2001 3:19:03 PM
Issue PAID IN FULL permit  5/15/2001 DONE
Routing - FIRE5/8/20015/8/20015/8/2001 PASS
DetailsBill Alexander
Routing - PLAN CHECK5/8/20015/8/20015/8/2001 PASS
Received rack plans from fire code analyst. Approved as noted & attached.
Plan assigned to (DRS)3/29/20013/29/20015/8/2001 PASS
DetailsDan Stuart
5/8/2001 10:05:13 DRS - activity updated through activity BLDA022 from case BLD01-00955.
PLANS/APPL TAKEN TO FRONT DESK  5/8/2001 PASS
To permit desk to process for permit.
Print Occupancy Form  5/8/2001 DONE
Inspection Record Card- Bld  5/8/2001 DONE
Telephone call  5/8/2001 DONE
called permit ready
Telephone call  4/17/2001 DONE
Called Rob Stapley, PAM Oil local manager to see if Jim Call, Fire Protection Engineer had told him when we might expect his recent site inspection report (4/12/01) on current quantities of hazardous materials in relation to his 13 point proposal of 1/20/00 that was to be used to bring the quantities of hazardous materials to be within the allowable limits of Tables 3-D & 3-E as an "S-1" occupancy for which the plans and application had been initially submitted. If the quantities are not met in this report the facility will be re-classified as an "H" occupancy and plans returned to the architect of record and action taken toward the tenant to alleviate the situation until the code requirements are met. NOTE: Steve Keuter, Fire Captan, has notified the tenant that on May 15, 2001 he will be by to see if the permits are issued for performing the necessary work to obtain a C.O. or if the work has been completed and a C.O. has been issued.
Application received  4/14/2001  
Additional plans submitted  4/9/2001  
Received copies of structural analysis & design for new racks, Interlake, proposed for the project and for the existing double tier mezzanine shelving, E-Z Rect (E-Z Rack on Architects plan). Plans for the Penco Double Tier (Rivet-Rite style) proposed new shelv storage units were presented 3/29/01. Structural analysis of the existing Interlake racks were presented Nov 27, 2000 plan submittals for T.I. by Stapley Engineering to accompany the architects floor plan layout.
Received Certificate of Value  4/3/2001  
Received copy of certificate of value for $27,000.00
Routing - PLAN CHECK3/30/20013/30/20013/30/2001  
Notified the manager, Rob Stapley, that all the rack engineering was not presented for the different rack configuations indicated on the architects plans. I had received Bryce Stapley, structural engineer, report for a portion of the existing racking stating the the design loads and method of attachment to the floor and his comment that he had reviewed the connection to the floor for the racks and they were completed per his design. This still needs to be verified in the filed by structural inspectors once the permit is issued. The submittal of plans on the 29 of March were for one set of shelving with a catwalk at 8 feet (mezzanine). Another set is existing for which an analysis is required to show evidence of code compliance. I also need a completed certificate of value. Plan on hold pending resubmital.
Plan resubmittals requested  3/30/2001 FAIL
Ask for all engineering design calcs for the existing racks that have been installed without permit & for any additional racks proposed for replacement of racks that engineering design or non-code compliance is not available. Rob Stapley will provide information. Also need a completed certificate of value for rack permit.
Waiting for Cert. of Value  3/30/2001  
Certificate of value was not completed when application brought in. Applicant told to complete and fax back to me.
Plan Reviewer's activity  3/22/2001  
Received notice from Stev Keuter, Fire Dept. Captain, that he was sending out notification to all Boeing Street Warehouse's, #7, #8, & #9 (includes Pam Oil @ 1051 Boeing) tenant's that he will be by the 15th of May to see if they have obtained their C.O. or to issue a citation to appear in court if they have not.