Fee Review-notes | 7/8/2003 | 7/8/2003 | 7/8/2003 | | DONE |
|
|
|
|
Permanent Occupancy | | 11/30/2001 | 11/30/2001 | | DONE |
|
|
|
|
Fee Review-notes | 4/24/2001 | 4/24/2001 | 11/30/2001 | | DONE |
|
|
|
called john keen left mesg lh
|
Permanent occupancy | | | 11/30/2001 | | DONE |
|
|
|
perm occ #8923 issued 11/30/01 to the Red Lobster aml
|
BLD-Final | 11/26/2001 | 11/27/2001 | 11/27/2001 | A | PART |
Russ Owen
|
|
|
SHANE ###-#### . ok needs plumbing for perm oc. 11/27/2001 11:50:27 AM
|
Temporary occupancy | | | 11/14/2001 | | PART |
|
|
|
Temp. Occ. Cert. #4641 issued 11-14-01 to the Red Lobster.
|
BLD-Final | 11/7/2001 | 11/8/2001 | 11/8/2001 | A | PART |
Russ Owen
|
|
|
###-####. Needs revised exterior exit system for out door dining , plan shows panic hardware at gates and also they have gated area constructed different from plans. Gates have been removed for temporary oc, also need dead bolt removed from office. Also has waitress booths in close prox to exit doors they were shown on fixture plans to be at present location ,main floor plan does no show them at all, contractor will be having new smaller one made. Ok for temporary oc only at this time. 11/8/2001 11:34:45 AM
|
Code Occupancy Approval | | | 11/8/2001 | | PASS |
|
|
|
FINAL SIGNED OFF, THERE IS STILL SMALL SIDEWALK WORK WITH LAND SCAPE NEED NO NORTH WEST CORNER BY DRIVEWAY
|
FIRE-Final Inspection | 11/7/2001 | 11/7/2001 | 11/7/2001 | P | PASS |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 11/7/2001 3:07:58 PM Fire/life safety is finaled. OK for perm occ
|
Code Occupancy Approval | | | 11/7/2001 | | FAIL |
|
|
|
THERE IS A SMALL AMOUNT OF LANDSCAPE NOT COMPLETED AT DRIVEWAY TO NORTH DUE TO REPLACEMENT OF SIDEWALK, I SIGNED TEMP OCCUPANCY WITH NO BOND.
|
BLD-Final | 11/1/2001 | 11/1/2001 | 11/1/2001 | P | NR |
Russ Owen
|
|
|
###-####. needs all other signatures. 11/1/2001 4:12:14 PM
|
BLD-Framing/Rough-in | 10/25/2001 | 10/26/2001 | 10/26/2001 | A | PART |
Russ Owen
|
|
|
CELLING GRID ###-#### SHANE Found 3 lights in kitchen with no slack wires, contractor not on site. no c/n posted.. 10/26/2001 9:50:14 AM
|
BLD-Framing/Rough-in | 10/23/2001 | 10/23/2001 | 10/23/2001 | P | PASS |
Tom Arcoraci
|
|
|
###-#### shaft inspection shaft ok 10/23/2001 2:40:38 PM
|
BLD-Framing/Rough-in | 10/2/2001 | 10/2/2001 | 10/2/2001 | P | PART |
Russ Owen
|
|
|
###-#### 2 layer wrap on duct above grease hoods,still needs top of hood protection. 10/2/2001 3:41:36 PM
|
BLD-Energy code compliance | 9/19/2001 | 9/20/2001 | 9/20/2001 | A | PASS |
Tom Arcoraci
|
|
|
###-#### SHANE ok to cover walls 9/20/2001 9:21:25 AM
|
BLD-Energy code compliance | 9/17/2001 | 9/18/2001 | 9/18/2001 | A | PART |
Russ Owen
|
|
|
###-#### SHANE ok to sheetrock kitchen/restrooms. front dining area ok subject to ele inspection. 9/18/2001 11:03:10 AM
|
BLD-Framing/Rough-in | 9/14/2001 | 9/17/2001 | 9/17/2001 | P | PART |
Russ Owen
|
|
|
###-#### SHANE only items left are a-35 at soffit and fire blocking c/n in office. 9/17/2001 2:03:02 PM
|
BLD-Framing/Rough-in | 9/13/2001 | 9/14/2001 | 9/14/2001 | P | PART |
Russ Owen
|
|
|
###-#### SHANE. rear kitchen and restroom areas only c/n posted. 9/14/2001 4:04:31 PM
|
BLD-Framing/Rough-in | 9/7/2001 | 9/10/2001 | 9/10/2001 | A | PART |
Tom Arcoraci
|
|
|
SHEER PANEL ###-#### SHANE
|
BLD-Framing/Rough-in | 9/6/2001 | 9/7/2001 | 9/7/2001 | A | FAIL |
Russ Owen
|
|
|
shear panel and a hd holddowns shane ###-####. hold -downs ok, shear nailing incomplete. recall. 9/7/2001 11:48:37 AM
|
BLD-Conference | 8/28/2001 | 8/29/2001 | 8/29/2001 | A | PART |
Russ Owen
|
|
|
###-####. need details from engineer for rear wall connection to parapet,also still needs inspection of entire exterior shear questions only today. 8/29/2001 11:05:46 AM
|
BLD-Framing/Rough-in | 7/13/2001 | 7/16/2001 | 7/16/2001 | A | PASS |
Russ Owen
|
|
|
Shane ###-####conduit removed and replaced with steel,also walls ok. 7/16/2001 12:23:26 PM
|
BLD-Foundation | 7/11/2001 | 7/12/2001 | 7/12/2001 | P | PART |
Russ Owen
|
|
|
Robert ###-####c/n posted for area with pvc eletrical condiut in footing, engineer has allowed steel schedual 40,will replace and recall. 7/13/2001 8:56:04 AM
|
BLD-Footing | 7/9/2001 | 7/10/2001 | 7/10/2001 | P | FAIL |
Russ Owen
|
|
|
ft insp robert- ###-#### c/n posted for electrical conduit in footing. 7/10/2001 4:37:10 PM
|
(F) Reprint permit | | | 7/6/2001 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 7/5/2001 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/26/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/26/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/26/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/26/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/26/2001 | | DONE |
|
|
|
|
Plan assigned to (MLO) | 4/24/2001 | | 6/26/2001 | | PASS |
Mike Otto
|
|
|
6/26/2001 11:19:21 MLO - activity updated through activity BLDA022 from case BLD01-01032.
|
Routing - PLAN CHECK | 6/25/2001 | | 6/25/2001 | | PASS |
|
|
|
|
Routing - PLANNING | 6/19/2001 | | 6/25/2001 | | PASS |
|
|
|
Approved per DRH01-46 and as noted on sheet L-1.
|
Routing Off Site - STRUCTURAL | 6/13/2001 | | 6/20/2001 | | PASS |
|
|
|
Sent resubs to structural engineer via PDQ.6/12/01 DAR
|
Routing - PLUMBING | 6/19/2001 | 6/19/2001 | 6/19/2001 | | PASS |
|
|
|
all floor sinks and indirect waste receptors must be exposed and in full view, roof scuppers must be a max. of 2" above roof drains.
|
Routing - PLUMBING | 6/12/2001 | | 6/18/2001 | | FAIL |
|
|
|
all floor sinks and indirect waste receptors must be exposed and in full view, provide secondary roof drainage system.
|
Plan resubmittals received | | | 6/5/2001 | | |
|
|
|
|
Plan resubmittals received | | | 6/5/2001 | | |
|
|
|
|
Plan resubmittals received | | | 6/5/2001 | | DONE |
|
|
|
Received three sets of resubmittals from ajc architects plus small documents. Forwarded same to Mike Otto. 6/5/01 DAR
|
Routing - FIRE | 5/23/2001 | | 5/29/2001 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 5/29/2001 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 5/15/2001 | | 5/23/2001 | | FAIL |
|
|
|
corrections faxed and mailed to architect
|
Routing Off Site - STRUCTURAL | 4/26/2001 | | 5/23/2001 | | FAIL |
|
|
|
Sent plans to consulting engineer via PDQ. 4/26/01 DAR corrections faxed and mailed to architect.
|
Plan resubmittals requested | | | 5/23/2001 | | FAIL |
|
|
|
UBC and structural corrections
|
Routing - PLUMBING | 5/11/2001 | | 5/15/2001 | | FAIL |
|
|
|
TOOK TO PLUMBING grease interceptor vent must be a min. of 3", all indirect waste receptors must be exposed, in full view, accessable, provide secondary roof drainage system, west boise sewer dist. must approve trash area drainage prior to plumbing approval. ###-####
|
Routing - PLANNING | 5/4/2001 | | 5/11/2001 | | FAIL |
|
|
|
Design Review conditions not met. There is also a pending Design Review appeal.
|
Routing - PUBLIC WORKS | 4/24/2001 | | 5/4/2001 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 4/24/2001 | | DONE |
|
|
|
Requested full set of plans for consulting structural engineer plus structual caculations and a project manual. 4/24/01 DAR
|
Application received | | | 4/24/2001 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/24/2001 | | DONE |
|
|
|
|