Permit Information
Permit NumberBLD01-01181
StatusFinaled
Name MASCO INC
Site Address 5450 W GOWEN RD
Project NameMASCO, INC.
Customer Number 
ePlanReviewNo
Description
Masco, Inc. To construct a 20,235 square foot, one story Type VN, fully fire sprinklered building with 6,283 sq. ft. of offices and 12,500 sq. ft. of H-4 repair shop with a 1452 sq ft storage mezzanine. Other work includes all site improvements, paving and landscaping. All work is per approved plans and attachments, DRH00-00256. Fire sprinklers used for area.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent occupancy  6/17/2002 DONE
Perm. Occ. Cert. #9174 issued 6-17-02 to Masco, Inc.
Permanent Occupancy 6/12/20026/12/2002 DONE
Details
Fee Review-notes5/4/20015/4/20011/29/2002 DONE
FIRE-Final Inspection12/4/200112/4/200112/4/2001APASS
DetailsTroy Cobbley
Added by Inspector: 430 On 12/4/2001 11:32:33 AM Fire life/safety finaled. Fire door inspected and checked out OK
Temporary occupancy  12/4/2001 PART
Temp. Occ. Cert. #4673 issued 12-4-01 to Masco, Inc.
BLD-Final11/30/200112/3/200112/3/2001APART
DetailsJim Storey
###-#### LARRY temp occ ok pending p&z and ele perm sign off bond in place for landscaping. 12/3/2001 5:09:20 PM
FIRE-Supply Line Flush11/9/200111/13/200111/13/2001APART
DetailsTroy Cobbley
Supply line flush and hydro OK 11/13/2001 10:39:13 AM
BLD-Framing/Rough-in11/9/200111/13/200111/13/2001APASS
DetailsJim Storey
CEILING GRID ###-#### LARRY ceilling ok for cover. 11/13/2001 8:56:01 AM
BLD-Framing/Rough-in11/5/200111/6/200111/6/2001APART
DetailsJim Storey
###-#### LARRY CEILING GRID perimitor rooms ok for cover main ceilling pending ele approval as wel as approval from fire for all ceilling. 11/6/2001 9:13:19 AM
BLD-Framing/Rough-in11/6/200111/6/200111/6/2001PPART
DetailsJim Storey
overhead inspection ###-#### ceilling ok pending others. 11/7/2001 8:18:25 AM
FIRE-Sprinkler Rough-in11/2/200111/5/200111/5/2001AFAIL
DetailsTroy Cobbley
approved plans not on site 11/5/2001 9:22:37 AM
BLD-Framing/Rough-in11/1/200111/2/200111/2/2001AFAIL
DetailsRuss Owen
###-#### LARRY CEILING GRID. perimeter wires needed and lights not in place. 11/2/2001 10:56:36 AM
BLD-Framing/Rough-in10/16/200110/16/200110/16/2001PPASS
DetailsJim Storey
###-#### fire gyp on mez ok for lap and nailling. 10/17/2001 11:52:48 AM
BLD-Framing/Rough-in10/1/200110/2/200110/2/2001PPASS
DetailsJim Storey
###-#### office ok. 10/3/2001 9:07:14 AM
BLD-Framing/Rough-in9/25/20019/26/20019/26/2001APART
DetailsJim Storey
###-#### LARRY ROOF DECK INSPECTION roof deck welding rfi to engineer for perimitor weld north and south walls west end of roof deck reweld atchment and sheer configuration perplan un noted. 9/26/2001 10:15:49 AM
BLD-Concrete8/28/20018/29/20018/29/2001PPASS
DetailsJim Storey
###-#### MIKE ft at col. special insp. / reviewed roof erection in process tilt panels weld and back pour ok for cover/ recieved engineer office beam modifaction approved and archived to city. 8/30/2001 9:10:12 AM
BLD-Concrete8/17/20018/20/20018/20/2001APART
DetailsJim Storey
larry ###-#### concrete west ft cover with special insp. not ready at this time added to scope of special./ engineering change for #6 barto be relayed to my self to place at ft not epoxy. 8/20/2001 10:11:27 AM
BLD-Concrete8/15/20018/16/20018/16/2001PPASS
DetailsJim Storey
retilt bar insp larry- ###-#### rebar ok pending special insp.report. 8/16/2001 4:34:40 PM
BLD-Concrete8/14/20018/14/20018/14/2001APASS
DetailsJim Storey
Added by Inspector: 301 On 8/14/2001 8:24:34 AM c/n made ok rebar ok for colm design and top chord.
BLD-Concrete8/10/20018/13/20018/13/2001PFAIL
DetailsJim Storey
rebar in the tilt walls Larry ###-####c/n no seperation of steel mats at top 1/3 vert steel above door openings. 8/13/2001 4:43:33 PM
BLD-Foundation7/25/20017/26/20017/26/2001PPART
DetailsJim Storey
###-#### placed with out city insp on walls office foundation/ pending special insp. report all though no reqired per plan. 7/26/2001 3:17:04 PM
BLD-Footing7/23/20017/23/20017/23/2001PPASS
DetailsJim Storey
###-#### ft ok 7/23/2001 3:13:40 PM
(F) Reprint permit  7/23/2001 DONE
Issue PAID IN FULL permit  7/20/2001 DONE
Routing - PLAN CHECK7/18/2001 7/19/2001 PASS
PLANS/APPL TAKEN TO FRONT DESK  7/19/2001 DONE
Inspection Record Card- Bld  7/19/2001 DONE
Print Occupancy Form  7/19/2001 DONE
Telephone call  7/19/2001 DONE
TALKED TO TRENT TO VERIFY PLANS ARE READY
Plan assigned to (MLO)5/7/2001 7/19/2001 PASS
DetailsMike Otto
7/19/2001 10:21:59 MLO - activity updated through activity BLDA022 from case BLD01-01181.
Routing - FIRE7/13/2001 7/18/2001 PASS
Routing - PLUMBING7/18/2001 7/18/2001 PASS
PUMP STATION TO BE PROVIDED WITH DUPLEX PUMPS, ROUT INTERCEPTOR DISCHARGE TO SEWER, PROVIDE A C.O. EVERY 100 FEET, NO ABS UPSTREAM OF INTERCEPTOR.
Routing - PUBLIC WORKS7/11/2001 7/13/2001 PASS
Requested by Louise
Routing Off Site - STRUCTURAL7/12/2001 7/13/2001 PASS
Sent to consultanting engineer via PDQ. 7/12/01 DAR
Plan resubmittals received  7/12/2001 DONE
Received plan resubmittals from BRS Architects 1 sheet S7.1 and P-1 forwarded same to Mike Otto. 7/12/01 DAR
Routing - FIRE7/9/2001 7/11/2001 FAIL
STILL NEED HM & FLM LIQ INVENTORY
Routing - PUBLIC WORKS6/25/2001 7/9/2001 FAIL
To Fire
Requires drainage plan revision. Per Brian M. KMM
Plan resubmittals received  6/26/2001 DONE
Received two copies of revised clouded sheets SD-1, SD-2, S7.1, A-1, A-1.2, A-4, A-5, A-6, M-1, M-2, P-1. One of the A-6 sheets was not signed. Contacted Trent of this need to get one to Mike as soon as possible. One copy of written response to plan check comments. Two copies of revised structural calculations dated 6/15/01. One copy of product specifications for skylight. One copy of memo to fire dept. and msds for hazardous stored liquids. Routed all of above to Mike O. KMM 6/26/01 PM recieved stamped and signed A-6 sheet. Routed to Mike O. KMM
Plan resubmittals received  6/22/2001 DONE
Received two copies of revised sheets C-1, C-3, C-4, one copy of cover letter and one copy of GPGS information. Routed to Mike O.
Routing - FIRE6/11/2001 6/13/2001 FAIL
hydrant location, water flow, hm inventory, flam liq inventory, plans returned to plan review
Plan Review Completed(1st rev)  6/13/2001 FAIL
plans returned to plan review
Routing - PLAN CHECK5/31/2001 6/11/2001 FAIL
corrections faxed and mailed to architect
Routing Off Site - STRUCTURAL5/7/2001 6/11/2001 FAIL
Sent engineering plans to consultanting engineer via PDQ.5/7/01 DAR
Plan resubmittals requested  6/11/2001 FAIL
UBC structural and non-structural corrections
Routing - PLUMBING5/23/2001 5/31/2001 FAIL
provide a plan showing sewer pump stationlocation and detail, verify shop floor drainage requirements with structural plan review and provide a plan showing drainage to a flammable liquids interceptor if required, verify wash rack drainage to drainage swale with brian murphy, public works.
Routing - PLANNING5/16/2001 5/23/2001 PASS
Approved per drh00-00256.
Routing - PUBLIC WORKS5/7/2001 5/16/2001 FAIL
Requires drainage plan per Brian Murphy. Also need to show Sewer connection to pressure main, per John Johnson. 5/16/01 DAR
Plans ACCEPTED BY PLAN TECH  5/7/2001 DONE
Application received  5/4/2001  
Recd Pcfee & Taken To Pln CK  5/4/2001