Case Summary (BLD) | | | 2/12/2016 | | DONE |
|
|
|
|
Fee Review-notes | 8/21/2001 | 8/21/2001 | 7/5/2002 | | DONE |
|
|
|
|
BLD-Final | 4/8/2002 | 4/9/2002 | 4/9/2002 | A | PASS |
Russ Owen
|
|
|
Scott, ###-#### Ok for a perm oc , providing all signatures are on job card. 4/9/2002 11:03:42 AM
|
Letter of compliance | | | 4/9/2002 | | DONE |
|
|
|
Letter of Compliance #22325 issued 4-9-02.
|
FIRE-Final Inspection | 4/3/2002 | 4/3/2002 | 4/3/2002 | P | PASS |
Troy Cobbley
|
|
|
fire life/safety finaled. fire alarm finaled.
|
CHANGE STATUS TO (ISS) | | | 4/3/2002 | | |
|
|
|
|
BLD-Final | 1/3/2002 | 1/4/2002 | 1/4/2002 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 01/03/2002 at 12:11:20. Contact: ###-####.Went over requirements for final need health dpt and fire/life safety, Mec and Bld can be done at same time . 1/4/2002 4:50:06 PM
|
Print Occupancy Form | | | 1/3/2002 | | DONE |
|
|
|
|
BLD-Aging Inspection | 11/28/2001 | 11/28/2001 | 11/28/2001 | | PART |
Russ Owen
|
|
|
|
BLD-Conference | 9/4/2001 | 9/5/2001 | 9/5/2001 | A | PART |
Russ Owen
|
|
|
steve- ###-#### for conf. owner does not want to install fire masters duct wrap as per plan, 2 wraps equals 2 hour installer wanted to install 1 wrap ,but no listed assemby exist,told him to find one or due 2 wraps. 9/5/2001 12:41:42 PM
|
Issue PAID IN FULL permit | | | 9/4/2001 | | DONE |
|
|
|
|
Routing - FIRE | 8/24/2001 | 8/28/2001 | 8/31/2001 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (DRS) | 8/24/2001 | 8/24/2001 | 8/31/2001 | | PASS |
Dan Stuart
|
|
|
8/31/2001 11:58:28 DRS - activity updated through activity BLDA022 from case BLD01-02286.
|
Plan assigned to (MYS) | 8/21/2001 | 8/21/2001 | 8/31/2001 | | PASS |
Marlene Southard
|
|
|
8/31/2001 11:58:28 DRS - activity updated through activity BLDA022 from case BLD01-02286.
|
Plan Review Completed(1st rev) | | | 8/31/2001 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/31/2001 | | 8/31/2001 | | PASS |
|
|
|
Approved as noted on plans and plan review conditions and evaluation report ER4975, attached as part of the approved plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/31/2001 | | PASS |
|
|
|
Routing to permit desk for issuance.
|
Inspection Record Card- Bld | | | 8/31/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/31/2001 | | DONE |
|
|
|
|
Telephone call | | | 8/31/2001 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/24/2001 | 8/24/2001 | 8/24/2001 | | PEND |
|
|
|
Approved as noted and attached. Routing to fire code analyst for review and comment.
|
Meeting | | | 8/22/2001 | | |
|
|
|
Met with Steve Williams to review plans for Type I Grease Hood system for Hogi Yogi. Reviewed requirements for use of Firemaster Duct Wrap, ER-4975, requires speific double wrap with specific desnity and specific application and that this is what the inspector will inspect by. The hood needs to comply with the UMC for installation requirements & construction materials and the UFC for the fire supression system and connection to alarm system as required. Plans submitted to permit desk to pay plan review fee's and receive a BLD number.
|
Application received | | | 8/21/2001 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 8/21/2001 | | DONE |
|
|
|
|