Permit Information
Permit NumberBLD01-02423
StatusFinaled
Name SUNDANCE INVESTMENTS LIMITED
Site Address 1307 S MAPLE GROVE
Project NameBLACKEAGLE #1
Customer Number 
ePlanReviewNo
Description
(BOISE SCHOOLS-COMPUTER NETWORKING CLASSROOMS) To remodel a 1,975 sq.ft. area of an existing office building to convert to educational classrooms per approved plans on file.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Fee Review-notes9/4/20019/4/20017/19/2002 DONE
Print Occupancy Form  7/2/2002 DONE
Permanent occupancy  7/2/2002 DONE
Perm. Occ. Cert. #9236 issued 7-2-02 to the Boise School District.
Permanent Occupancy 6/28/20026/28/2002 DONE
Details
FIRE-Final Inspection6/27/20026/27/20026/27/2002PPASS
DetailsTroy Cobbley
Fire alarm system finaled 6/27/2002 11:10:49 AM
BLD-Final6/27/20026/27/20026/27/2002PPASS
DetailsJim Sly
###-#### mike OK for Perm Occ. 6/28/2002 3:06:51 AM
FIRE-Final Inspection6/21/20026/21/20026/21/2002PFAIL
DetailsTroy Cobbley
antifreeze loop valves did not function 6/21/2002 4:40:32 PM
FIRE-Final Inspection5/13/20025/13/20025/13/2002PFAIL
DetailsTroy Cobbley
verify dialer location and test, install pull station in Right Systems warehouse, remove lock on exterior door in dental office, complete nfpa 72 5/13/2002 2:44:01 PM
FIRE-Final Inspection5/7/20025/8/20025/8/2002PCANC
DetailsTroy Cobbley
cancelled by contractor 5/8/2002 3:26:07 PM
FIRE-Final Inspection4/18/20024/19/20024/19/2002PCANC
DetailsTroy Cobbley
inspection cancelled. The two panels in the building weren't connected 4/19/2002 4:24:04 PM
FIRE-Alarm Testing2/5/20022/5/20022/5/2002PPART
DetailsTroy Cobbley
Added by Inspector: 430 On 2/5/2002 3:51:22 PM existing fire alarm system tested OK. Still waiting for new fire alarm upgrades per agreement with city to be installed before final test can be done.
FIRE-Final Inspection1/31/20021/31/20021/31/2002APART
DetailsTroy Cobbley
Added by Inspector: 430 On 1/31/2002 8:55:47 AM Fire dampers operated OK. Emergency lights, exit signs and fire extinguishers OK. Fire alarm system still not tested or submitted
FIRE-Final Inspection12/26/200112/26/200112/26/2001PCANC
DetailsTroy Cobbley
canceled by contractor. To be rescheduled 12/26/2001 1:32:32 PM
FIRE-Final Inspection12/21/200112/21/200112/21/2001PFAIL
DetailsTroy Cobbley
Contractor to schedule fire alarm contractor to test dampers and system. 12/24/2001 9:53:54 AM
BLD-Final12/21/200112/21/200112/21/2001PPART
DetailsRuss Owen
pending fire insp michael ###-#### . Need to fire caulk above corridor walls at east wall,location above grid ceiling, Also needs fire/life safety sign off, before a temporary oc. 12/21/2001 4:50:59 PM 12/21/2001 4:51:39 PM
FIRE-Final Inspection12/3/200112/4/200112/4/2001ANR
DetailsTroy Cobbley
All items on the correction notice are not taken care of (fire alarm system) 12/4/2001 5:00:05 PM
BLD-Final11/30/200112/3/200112/3/2001ANR
DetailsRuss Owen
###-####
FIRE-Final Inspection11/30/200111/30/200111/30/2001PFAIL
DetailsTroy Cobbley
Repair exit signs, install and test dampers, test door release, get fire extinguishers and fire sprinkler riser inspected, provide emergency light in lobby. 11/30/2001 5:11:52 PM
FIRE-Final Inspection11/30/200111/30/200111/30/2001PFAIL
DetailsTroy Cobbley
Repair exit signs, install and test dampers, test door release, get fire extinguishers and fire sprinkler riser inspected, provide emergency light in lobby. 11/30/2001 5:11:52 PM
BLD-Final11/29/200111/29/200111/29/2001PPART
DetailsRuss Owen
###-#### michael . need to fire stop penetrations and repair fire wall as needed. 11/29/2001 2:29:45 PM
BLD-Final11/27/200111/28/200111/28/2001ANH
DetailsRuss Owen
mike ###-#### please call before going out so mike can meet you there. 11/28/2001 12:13:39 PM. called this number no answer left message. 11/28/2001 1:14:33 PM
BLD-Conference10/17/200110/17/200110/17/2001PPART
DetailsRuss Owen
Scheduled by Inspector: 407 On 10/17/2001 4:00:50 PM Went over existing wall requirements with Sundance const they will be completing job, existing wall does not meet 1hr occupancy req as shown tyo on plans etc. 10/17/2001 4:03:41 PM
BLD-Conference10/10/200110/11/200110/11/2001APART
DetailsRuss Owen
Scheduled by Inspector: 407 On 10/10/2001 4:25:17 PM . Need architect to review job in the field and respond as existing wall does not meet 1 hr occupancy separation req, went over this with contractor # ###-####, ARCHITECT # is ###-####. 10/11/2001 2:17:19 PM
BLD-Framing/Rough-in10/10/200110/10/200110/10/2001PPART
DetailsRuss Owen
###-#### JERRY Re-insp for am on 10/11/01. 10/10/2001 4:26:53 PM
BLD-Framing/Rough-in10/4/200110/5/200110/5/2001APART
DetailsRuss Owen
###-#### need to complete framing. 10/5/2001 11:26:53 AM
Issue PAID IN FULL permit  9/27/2001 DONE
Plan resubmittals received  9/26/2001 DONE
Received one copy of revised sheet ASI-1 one copy of letter to Ryan and one copy of letter of transmittal. Routed to Mike O. KMM
Inspection Record Card- Bld  9/17/2001 DONE
Print Occupancy Form  9/17/2001 DONE
Telephone call  9/17/2001 DONE
Routing - PLANNING9/13/2001 9/14/2001 PASS
Plan resubmittals received  9/14/2001 DONE
Received two copies of revised sheet A2.0. Routed to Mike O. KMM
Routing - PLAN CHECK9/14/2001 9/14/2001 PASS
PLANS/APPL TAKEN TO FRONT DESK  9/14/2001 DONE
Plan assigned to (MLO)9/5/2001 9/14/2001 PASS
DetailsMike Otto
9/14/2001 15:41:26 MLO - activity updated through activity BLDA022 from case BLD01-02423.
Routing - FIRE9/10/2001 9/13/2001 PASS
Plan Review Completed(1st rev)  9/13/2001 FAIL
Routing - PLAN CHECK9/7/2001 9/10/2001 FAIL
corrections faxed and mailed to architect.
Plan resubmittals requested  9/10/2001 FAIL
UBC corrections
Routing - PLANNING9/5/2001 9/7/2001 FAIL
School requires conditional use per ordinance. Called and talked to Jerry and Margie at Armstrong. They are going to clarify use with Scott Spjute.
Plans ACCEPTED BY PLAN CHECK  9/5/2001 DONE
requested a letter from United Water for the occupancy change and a new certificate of value.
Received Certificate of Value  9/5/2001 DONE
Application received  9/4/2001  
Recd Pcfee & Taken To Pln CK  9/4/2001 DONE