Case Summary (BLD) | | | 8/2/2006 | | |
|
|
|
|
Fee Review-notes | 7/14/2003 | 7/14/2003 | 7/14/2003 | | DONE |
|
|
|
Additional values from subcontractors.
|
FIRE-Final Inspection | 3/8/2002 | 3/11/2002 | 3/11/2002 | A | PASS |
Troy Cobbley
|
|
|
Fire life/safety and fire alarm finaled 3/11/2002 2:10:00 PM
|
BLD-Final | 3/8/2002 | 3/11/2002 | 3/11/2002 | A | FAIL |
Jim Storey
|
|
|
LARRY ###-#### need 5/8 gyp on shell side of tennet wall. 3/11/2002 9:08:44 AM
|
BLD-Final | 3/11/2002 | 3/11/2002 | 3/11/2002 | P | PASS |
Russ Owen
|
|
|
fn occ ###-####- larry ok perm co. 3/11/2002 4:57:00 PM
|
Permanent Occupancy | | 3/11/2002 | 3/11/2002 | | DONE |
|
|
|
|
Permanent occupancy | | | 3/11/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9062 issued 3-1-02 to Hugo's Deli.
|
FIRE-Final Inspection | 3/7/2002 | 3/8/2002 | 3/8/2002 | A | FAIL |
Troy Cobbley
|
|
|
add sprinkler pendant in cooler and in kitchen, mount fire extinguisher, provide air balance report for hood, provide power to hood so shut down can be verified, contact fire dept to corrdinate key for lock box 3/8/2002 1:22:38 PM
|
BLD-Final | 3/7/2002 | 3/8/2002 | 3/8/2002 | P | NR |
Carl Dependahl
|
|
|
###-#### LARRY FOR OCCUPANCY
|
BLD-Framing/Rough-in | 2/13/2002 | 2/14/2002 | 2/14/2002 | A | PASS |
Dave Hannah
|
|
|
###-#### LARRY GRID ceiling grid ok to cover 2/14/2002 11:23:50 AM
|
BLD-Framing/Rough-in | 1/15/2002 | 1/16/2002 | 1/16/2002 | A | PASS |
Tom Arcoraci
|
|
|
WALL COVER LARRY ok to cover 1/16/2002 9:36:35 AM
|
BLD-Wall cover | 1/10/2002 | 1/11/2002 | 1/11/2002 | A | PART |
Tony Young
|
|
|
###-####
ok to cover int. walls, c/n posted on demising wall and soffit areas 1/11/2002 10:26:02 AM
|
Print Occupancy Form | | | 12/17/2001 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 12/17/2001 | | DONE |
|
|
|
|
Telephone call | | | 12/17/2001 | | DONE |
|
|
|
permit ready
|
Issue PAID IN FULL permit | | | 12/17/2001 | | DONE |
|
|
|
|
Plan Review Report | | | 12/14/2001 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/14/2001 | | PASS |
Ron Hill
|
|
|
|
Print Occupancy Form | | | 12/14/2001 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 11/13/2001 | | 12/14/2001 | | PASS |
|
|
|
12/14/2001 10:04:58 RMH - activity updated through activity BLDA022 from case BLD01-02965.
|
Routing - PLAN CHECK | 11/30/2001 | | 12/14/2001 | | PASS |
Ron Hill
|
|
|
|
Plan resubmittals received | | | 12/11/2001 | | DONE |
|
|
|
Received two copies of revised sheets O, A-1, A-4, M-1, M-2, P-1, P-2, E2L, E2P. One copy of transmittal copy. Routed to Ron Hill. kmm
|
Plan Review Completed(1st rev) | | | 11/30/2001 | | FAIL |
|
|
|
|
Routing - FIRE | 11/29/2001 | | 11/30/2001 | | PASS |
|
|
|
|
Case Summary (BLD) | | | 11/29/2001 | | DONE |
|
|
|
|
Plan Review Report | | | 11/29/2001 | | DONE |
|
|
|
|
Plan Reviewer's activity | | | 11/29/2001 | | FAIL |
Ron Hill
|
|
|
Faxed requirements to the architect, routed plans to fire department 11-29-01
|
Routing - PLAN CHECK | 11/20/2001 | | 11/29/2001 | | FAIL |
Ron Hill
|
|
|
Routed plans to the architect Bob Hess on 11-29-01, and routed plans to fire department same day.
|
Routing - PUBLIC WORKS | 11/15/2001 | | 11/19/2001 | | PASS |
|
|
|
|
Routing - PLUMBING | 11/19/2001 | | 11/19/2001 | | PASS |
|
|
|
per plans and 2000 upc
|
Routing - PLANNING Land Div | 11/13/2001 | | 11/15/2001 | | PASS |
|
|
|
N/A - Tenant Improvement w/out expansion. If they expand, they will have to provide evidence of legal land division. Routed to Public Works. (blc)
|
Plans ACCEPTED BY PLAN TECH | | | 11/13/2001 | | DONE |
|
|
|
CDH approval by Bob Jue on 11/4/2001.
|
First Notice | 11/9/2001 | 11/9/2001 | 11/9/2001 | | DONE |
|
|
|
|
Application received | | | 11/9/2001 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 11/9/2001 | | DONE |
|
|
|
|