Case Summary (BLD) | | | 12/6/2004 | | |
|
|
|
|
Fee Review-notes | 11/14/2001 | 11/14/2001 | 8/29/2002 | | DONE |
|
|
|
|
Permanent Occupancy | | 6/18/2002 | 6/18/2002 | | DONE |
|
|
|
|
FIRE-Final Inspection | 6/17/2002 | 6/18/2002 | 6/18/2002 | A | PASS |
Rick Jackson
|
|
|
RICK ###-####
|
BLD-Final | 6/17/2002 | 6/18/2002 | 6/18/2002 | P | PASS |
Carl Dependahl
|
|
|
RICK ###-#### NA'd mech, no new work, ok for c/o 6/18/2002 4:07:48 PM
|
Permanent occupancy | | | 6/18/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9178 issued 6-18-02 to Meadowgold Dairies.
|
BLD-Framing/Rough-in | 5/9/2002 | 5/10/2002 | 5/10/2002 | A | PASS |
Dave Hannah
|
|
|
fr rick ###-#### restroom ok to cover 5/10/2002 11:32:42 AM
|
BLD-Framing/Rough-in | 5/7/2002 | 5/8/2002 | 5/8/2002 | P | FAIL |
Jim Storey
|
|
|
1. (Fire blocks and draft stops) In combustible construction, fireblocking and draftstopping shall be installed to cut off all concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space, and shall subdivide attic spaces, concealed roof spaces and floor-ceiling assemblies. The integrity of all fire blocks and draft stops shall be maintanined. (1997 UBC 708.1)
2. all backing for ada bars must be instaled .
|
BLD-Conference | 4/24/2002 | 4/24/2002 | 4/24/2002 | P | PASS |
Carl Dependahl
|
|
|
w/ Bldr re ADA
|
Issue PAID IN FULL permit | | | 1/4/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 12/21/2001 | | DONE |
|
|
|
|
Print Occupancy Form | | | 12/21/2001 | | DONE |
|
|
|
|
Telephone call | | | 12/21/2001 | | DONE |
|
|
|
left mess for trent koes that permit is ready
|
Plan assigned to (CJW) | 11/19/2001 | | 12/20/2001 | | PASS |
Carl Westfall
|
|
|
12/20/2001 15:26:44 CJW - activity updated through activity BLDA022 from case BLD01-02991.
|
Routing - PLAN CHECK | 12/12/2001 | | 12/20/2001 | | PASS |
|
|
|
Holding for fire.
|
Routing - FIRE | 12/20/2001 | | 12/20/2001 | | PASS |
Bill Alexander
|
|
|
|
Routing - PLAN CHECK | 12/20/2001 | | 12/20/2001 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/20/2001 | | PASS |
|
|
|
|
Routing - FIRE | 12/11/2001 | | 12/12/2001 | | |
Bill Alexander
|
|
|
Failed 2nd UFC review. Lack commodity and storage system information.
|
Routing - PLAN CHECK | 12/10/2001 | | 12/11/2001 | | PASS |
|
|
|
Drawings approved after resubmittal review.
|
Plan resubmittals received | | | 12/10/2001 | | DONE |
|
|
|
Received two copies of revised sheets A-1. routed to Carl W. KMM
|
Routing - FIRE | 12/6/2001 | | 12/10/2001 | | |
Bill Alexander
|
|
|
Failed 1st UFC review. Lack required openings 1003.2.2. Need building wall(s) seperation information between existing and this permit, to verify 903.3.
|
Plan Review Completed(1st rev) | | | 12/10/2001 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 11/30/2001 | | 12/6/2001 | | |
|
|
|
Failed first UBC review. UBC plan review started November 30, 2001 and finished December 6, 2001. A revision from the architect was required. See the conditions list.
|
Routing - PLANNING | 11/28/2001 | | 11/30/2001 | | PASS |
|
|
|
Approved per DRH01-168.
|
Routing - PLANNING | 11/26/2001 | | 11/28/2001 | | PASS |
|
|
|
Approved as per CUP01-00106. Pending Design Review approval.
|
Routing - PUBLIC WORKS | 11/20/2001 | | 11/26/2001 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 11/19/2001 | | 11/20/2001 | | PASS |
|
|
|
N/A - tenant improvement w/out expansion. Routed to Public Works. (blc)
|
Plans ACCEPTED BY PLAN TECH | | | 11/14/2001 | | DONE |
|
|
|
1. Need Owner's signature of Architect/Engineer of Record form. I faxed to Trent Koci of BRS Architects for signature and to fax back. Received 11/15/01
2. Under the General Notes it states Mechanical and Plumbing will be design built using current UMC/UPC.
3. Left message with Trent Koci about storage of dairy products, is there refrigeration units? Is this going to be sold to retail? Also, we do not design build mechanical/plumbing and the plan reviewer might require mechanical/plumbing drawings.
4. Tried to reach CDHD about storage of dairy products, left message with Carol about this.
5. Received call from Trent Koci, this is a storage facility for the cardboard/plastic (packing materials) for dairy products. I faxed the Tenant Improvement Permit Application to Trent to make appropiate corrections and to fax back.
|
Application received | | | 11/14/2001 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 11/14/2001 | | |
|
|
|
|