Case Summary (BLD) | | | 4/28/2010 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 4/28/2010 | | DONE |
|
|
|
|
Fee Review-notes | 12/19/2001 | 12/19/2001 | 8/10/2004 | | DONE |
|
|
|
|
BLD-Final | 7/2/2004 | 7/2/2004 | 7/2/2004 | P | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 7/2/2004 at 9:32:46 AM. Contact: ###-####. C/C issued. 7/2/2004 3:50:51 PM
|
DOC - Permit Finaled | 7/2/2004 | 7/2/2004 | 7/2/2004 | P | PASS |
Jim Sly
|
|
|
Finaled by inspector at 7/2/2004 3:50:58 PM
|
BLD-Other | 6/22/2004 | 6/23/2004 | 6/23/2004 | A | PART |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 6/22/2004 at 11:27:20 AM. Contact: ###-####. 6/23/2004 11:28:18 AM Call Steve.....Meet in Lobby. checking Mfg walls for bracing. 6/23/2004 11:29:59 AM
|
BLD-Final | 3/31/2004 | 4/1/2004 | 4/1/2004 | P | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 3/31/2004 at 11:51:00 AM. Contact: ###-####. Needs the electrical permit finaled, which is expired, electrical inspector has talked with tri-state electric. Also the tops of the pre-fab walls, hve not been tied off. 4/1/2004 12:28:02 AM
|
BLD-Final | 3/24/2004 | 3/25/2004 | 3/25/2004 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/24/2004 at 2:48:10 PM. Contact: ###-####. needs elec final and plumb final maybe ,ok for final when these are complete 3/25/2004 9:18:08 AM 3/25/2004 9:19:57 AM
|
FIRE-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire life safety, fire alarm and fire sprinklers finaled
|
BLD-Aging Inspection | 1/13/2004 | 1/13/2004 | 1/13/2004 | | CANC |
Russ Owen
|
|
|
Fire /life safety will check out. 1/20/2004 1:24:36 PM
|
BLD-Conference | 5/13/2003 | 5/13/2003 | 5/13/2003 | A | CANC |
Russ Owen
|
|
|
talked with steve he has submitted plans to the fire life/safety plan review division.
|
BLD-Aging Inspection | 3/26/2003 | 3/26/2003 | 3/26/2003 | | CANC |
Russ Owen
|
|
|
called steve will be submitting plans in about 2 weeks to resolve fire/life safety insp. 3/27/2003 3:16:44 PM
|
FIRE-Final Inspection | 12/23/2002 | 12/30/2002 | 12/30/2002 | P | FAIL |
Troy Cobbley
|
|
|
###-#### STEVE The fire door for the 2nd floor freight elevator does not latch when the fire alarm system is activated, provide a/v's within 15' of the ends of the corridors on the first and second floors, provide verification of fire/smoke damper activation per review comment #6, revise zone description and the FACP text so they match the device test and then retest, verify signals with the monitoring company, verify with the inspector the current draw on the notification circuits, provide map per review note #7, test the initiating devices. No area or duct smoke detectors were tested due to zone descriptions not matching. Do not final permit until the owner has the approved building plans on site 12/30/2002 4:23:28 PM
|
Routing - PLAN CHECK | 12/27/2002 | | 12/30/2002 | | DONE |
|
|
|
Plan Modification.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/30/2002 | | DONE |
|
|
|
|
Telephone call | | | 12/30/2002 | | DONE |
|
|
|
CALLED 12-30-02
|
Plan assigned to (R_H) | 12/24/2002 | | 12/30/2002 | | PASS |
|
|
|
12/30/2002 09:03:07 RMH - activity updated through activity BLDA022 from case BLD01-03230.
|
Routing - FIRE | 12/24/2002 | | 12/27/2002 | | PASS |
|
|
|
PLAN MODIFICATION OF 12/23/02 APPROVED WITHOUT ADDITIONAL COMMENT
|
Case Summary (BLD) | | | 12/27/2002 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 12/23/2002 | | 12/27/2002 | | PEND |
|
|
|
PLAN MODIFICATION / PERMIT PENDING FIRE DEPARTMENTS REVIEW AND APPROVAL, ROUTED PLANS TO THE FIRE DEPARTMENT ON 12/27/02
|
Plan Modification Accepted | | | 12/24/2002 | | |
Ron Hill
|
|
|
|
FIRE-Final Inspection | 4/12/2002 | 4/19/2002 | 4/19/2002 | A | FAIL |
Troy Cobbley
|
|
|
wall mounted device are wrong candella, wall listed devices mounted on ceiling. Review comments were not followed. Elevator recalled is wrong. I stopped inspection. Entire inspection needs to be started over. 4/19/2002 12:48:22 PM
|
BLD-Framing/Rough-in | 3/28/2002 | 3/29/2002 | 3/29/2002 | A | PART |
Russ Owen
|
|
|
###-####- steve r/i 2nd floor south side partition ok after ele. 3/29/2002 12:28:21 PM
|
BLD-Other | 2/20/2002 | 2/21/2002 | 2/21/2002 | A | PART |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 02/20/2002 at 16:27:59. Contact: ###-####.
|
BLD-Framing/Rough-in | 2/7/2002 | 2/7/2002 | 2/7/2002 | P | PASS |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 02/07/2002 at 10:12:02. Contact: ###-####.
|
BLD-Other | 1/29/2002 | 1/29/2002 | 1/29/2002 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 01/29/2002 at 08:58:25. Contact: ###-####.grid work in lower flor east side small arae on plans. 1/30/2002 9:15:40 AM
|
BLD-Framing/Rough-in | 1/22/2002 | 1/23/2002 | 1/23/2002 | A | NR |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 01/22/2002 at 14:34:32. Contact: ###-####.need trades signed off 1/23/2002 11:00:44 AM
|
BLD-Framing/Rough-in | 1/23/2002 | 1/23/2002 | 1/23/2002 | P | PART |
Russ Owen
|
|
|
Scheduled by Inspector: 415 On 1/23/2002 10:57:35 AM steve 321--9168. most new walls are complete. 1/24/2002 9:50:20 AM
|
Issue PAID IN FULL permit | | | 1/22/2002 | | DONE |
|
|
|
|
CHANGE ISSUED DATE | | | 1/22/2002 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 1/14/2002 | | 1/15/2002 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/15/2002 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 1/15/2002 | | DONE |
|
|
|
|
Print Occupancy Form | | | 1/15/2002 | | DONE |
|
|
|
|
Telephone call | | | 1/15/2002 | | DONE |
|
|
|
LEFT MESSAGE WITH JESSICA THAT PLANS WERE READY//AIM
|
Plan assigned to (R_H) | 12/24/2001 | | 1/15/2002 | | PASS |
|
|
|
1/15/2002 11:28:11 RMH - activity updated through activity BLDA022 from case BLD01-03230.
|
Routing - FIRE | 1/10/2002 | | 1/14/2002 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 1/14/2002 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 12/26/2001 | | 1/10/2002 | | PEND |
Ron Hill
|
|
|
No corrections required by the building department plan review, Permit is pending fire departments review, routed plans to the fire department on 1-10-02.
|
Case Summary (BLD) | | | 1/10/2002 | | DONE |
|
|
|
|
Routing - PUBLIC WORKS | 12/24/2001 | | 12/26/2001 | | PASS |
|
|
|
Plan Modification
|
Plans ACCEPTED BY PLAN TECH | | | 12/20/2001 | | DONE |
|
|
|
1. Plans not fully dimensioned.
2. Applicant would like a demo permit as soon as possible.
|
Application received | | | 12/19/2001 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 12/19/2001 | | DONE |
|
|
|
|