BLD-Aging Inspection | 3/24/2003 | 3/24/2003 | 3/24/2003 | | PASS |
Jim Storey
|
|
|
|
DOC - Permit Finaled | 3/24/2003 | 3/24/2003 | 3/24/2003 | A | PASS |
Jim Storey
|
|
|
Finaled by inspector at 3/24/2003 8:13:22 AM
|
PubWorks Occupancy Approval | | | 7/25/2002 | | DONE |
|
|
|
Drainage project complete 07/23/02. M.Strasser
|
BLD-Other | 5/6/2002 | 5/7/2002 | 5/7/2002 | A | DONE |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 05/06/2002 at 17:08:04. Contact: ###-####. called in wrong permit . 5/7/2002 9:52:33 AM
|
Issue PAID IN FULL permit | | | 3/4/2002 | | |
|
|
|
|
Routing - PLAN CHECK | 3/1/2002 | 3/1/2002 | 3/1/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 3/1/2002 | | |
|
|
|
|
Telephone call | | | 3/1/2002 | | DONE |
|
|
|
left mess that permit is ready
|
Routing - PLUMBING | 3/1/2002 | | 3/1/2002 | | PASS |
|
|
|
I recieved a letter from thornton oliver keller addressing water sizing and a statement that plans were revised showing approved piping from the dock drain. I have no plans showing dockdrain piping upgrade but the drain line from the dock to the storm drain system will be sch 40.
|
Print Pending Permit.LaserJet4 | | | 3/1/2002 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/1/2002 | | DONE |
|
|
|
|
Plan assigned to (KMM) | 12/20/2001 | | 3/1/2002 | | PASS |
Kathy Miller
|
|
|
3/1/2002 09:55:33 KMM - activity updated through activity BLDA022 from case BLD01-03236.
|
Routing - PLANNING Land Div | 2/13/2002 | | 2/28/2002 | | PASS |
|
|
|
Land division ok. Returned to Plan Review. (blc)
|
Routing - PLAN CHECK | 2/8/2002 | | 2/13/2002 | | |
|
|
|
|
Routing - PLANNING | 2/13/2002 | | 2/13/2002 | | PASS |
|
|
|
Approved for grading permit.
|
Routing - PLUMBING | 2/6/2002 | | 2/8/2002 | | FAIL |
|
|
|
Documents not submitted that were requested previously.
|
Override - Parcel Holds | | | 2/6/2002 | | |
|
|
|
|
Routing - FIRE | 2/5/2002 | 2/5/2002 | 2/5/2002 | | PASS |
Bill Alexander
|
|
|
|
Routing - PLAN CHECK | 1/28/2002 | | 2/5/2002 | | |
|
|
|
plans in my hold box. kmm
|
Routing - FIRE | 1/25/2002 | | 1/25/2002 | | FAIL |
|
|
|
HYDRANT FLOW
|
Plan Review Completed(1st rev) | | | 1/25/2002 | | FAIL |
|
|
|
|
Routing - PLUMBING | 1/23/2002 | | 1/24/2002 | | FAIL |
|
|
|
provide sizing for water service, sdr 35 is prohibited within the building. storm drain to loading dock must be sch. 40 pvc, abs, or c.i..
|
Routing - PLANNING | 1/18/2002 | | 1/23/2002 | | FAIL |
|
|
|
Approved for CUP00-00135. Failed per DRH01-185. Plans do not comply with Design Review conditions.
|
Routing - PUBLIC WORKS | 1/16/2002 | | 1/18/2002 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 12/28/2001 | | 1/16/2002 | | FAIL |
|
|
|
Land division needs to be verified. Applicant must supply a copy of all deeds for parcels created by ROS #5067 and parcel #'s. Faxed Bob Mitchell, Joseph Lemay and Meredith Smith. Routed to Public Works. (blc)
|
Additional plans submitted | | | 12/28/2001 | | DONE |
|
|
|
Received site plans.
|
Plans ACCEPTED BY PLAN TECH | | | 12/28/2001 | | DONE |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 12/28/2001 | | DONE |
|
|
|
|
Application received | | | 12/20/2001 | | |
|
|
|
|
Application received | | | 12/20/2001 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 12/20/2001 | | PEND |
|
|
|
Requires two copies of site plan. Contacted Joseph Lemay of this need. Will wait to route until they are received. Kmm
|
Plan routing begun/NEW & ADDTN | | | 12/19/2001 | | HOLD |
|
|
|
Waiting for two copies of site plan. kmm
|