Permit Information
Permit NumberBLD02-00031
StatusFinaled
Name ADA COUNTY CORONER (MORGUE)
Site Address 5550 W MORRIS HILL RD
Project Name 
Customer Number
ePlanReviewNo
Description
(ADA COUNTY CORONER - MORGUE) This building is fire sprinklered for area increase. To construct a 3,450 square foot morgue within an existing 24,000 square foot warehouse/office building to be used by the Ada County Coroner's Office. The Coroner will occupy the 3,450 square foot morgue, the 2,400 square foot 1st floor office area, and the 2,000 square foot 2nd floor office area (7,850 square feet total). Work is to include 2 toilet/shower rooms accessible to the disabled, a wheelchair lift accessible to the disabled, 2 restrooms modified to be more accessible to the disabled, interior nonbearing walls, a 300 square foot mechanical mezzanine, replaced concrete slabs, foam plastic freezer/cooler, and suspended ceilings all per approved drawings, engineering, and plan review conditions on file. The fire sprinkler system shall comply with NFPA 13-1999 as regulated by the Fire Department. Zoning approval by Scott Spjute. PC02-0012 **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Agreement of Future work9/11/200212/1/20046/20/2003 PASS
County agrees to correct As deficiencies and full spk the bldg by fiscal year 03-04 or sooner. Completed Under FIR03-00087
Agreement of Future work11/14/20023/31/200312/27/2002 PASS
County agrees to finish an alarm system upgrad in 60 days by 3-03. Work Completed Under Fir02-00364
Permanent Occupancy 12/27/200212/27/2002 DONE
Details
FIRE-Final Inspection12/26/200212/27/200212/27/2002AFAIL
DetailsRick Jackson
###-#### dave tested alarms; see FIR02-00463 for corrections 12/27/2002 10:55:11 AM
BLD-Final12/26/200212/27/200212/27/2002APASS
DetailsTom Arcoraci
###-#### ok for perm pending fire insp 12/26/2002 3:12:28 PM
FIRE-Final Inspection12/27/200212/27/200212/27/2002PPASS
DetailsRick Jackson
Permanent occupancy UNPAID FEE  12/27/2002 DONE
Perm. Occ. cert. #9505 issued 12-27-02 to the Ada County Coroner (Morgue).
Temporary occupancy  11/15/2002 DONE
Temp. Occ. Cert. #4892 issued 11-15-02 to the Ada County Coroner office (morgue)
FIRE-Final Inspection11/12/200211/12/200211/12/2002PFAIL
DetailsTroy Cobbley
provide fire alarm drawings 11/12/2002 3:59:01 PM
BLD-Final11/12/200211/12/200211/12/2002PPART
DetailsTom Arcoraci
dave; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for temp when fire signs card 11/12/02 3:19:31 PM
FIRE-Final Inspection11/4/200211/4/200211/4/2002PFAIL
DetailsTroy Cobbley
provide approved hardware on the north corridor door, provide automatic shutdown for the hvac units. These detectors to be connected to the building fire alarm system and may require submittals to Boise city for approvals, provide manual pull station and relocate smoke detector from the wall to the deck. This also may require submittals to the city. Have the alarm contractor contact Sam Roger at ###-#### with any questions. Provide annual inspection report for the fire alarm system
Print Occupancy Form  11/4/2002 DONE
BLD-Framing/Rough-in10/3/200210/3/200210/3/2002PPASS
DetailsTom Arcoraci
ceiling grid; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
BLD-Framing/Rough-in9/25/20029/25/20029/25/2002PPART
DetailsTom Arcoraci
ceiling grid; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok 9/25/2002 3:46:31 PM
Meeting  9/13/2002 DONE
September 13, 2002 - Walked through 1:30pm - Met with Architect (Dan Kauffman), Ada County building maintenance, Fire Sprinkler Contractor, General Contractor and inspected facility for new and existing UFC fire protection issues. Found some existing offices not sprinklered, High-piled combustible storage 12'-0" high with 36" wide, single rack, solid shelf, storage of Class II commodities up to 15'-0". Minimum aisle widths are 40" (one side) and 44" (the other). System (installed in 1963+-), appears to be designed for OH pipe scheduled occupancy with a 120 ft/2 spacing, limiting it to 12'-0" maximum. UFC Article 81 would have to be addressed in this area of occupancy.
BLD-Framing/Rough-in8/26/20028/28/20028/28/2002APART
DetailsTom Arcoraci
dave; Phone #: ###-#### ok to cover from bath to coolers check struts after duct work is installed no other places inspected 8/28/2002 1:55:55 PM
BLD-Footing7/22/20027/23/20027/23/2002APASS
DetailsTom Arcoraci
###-#### dave
Routing - PLAN CHECK1/30/2002 7/22/2002 PASS
(2-15-02) Drawings approved February 15, 2002 after resubmittal review. Holding until after resolution of plumbing concerns. (7-22-02) Plumbing concerns resolved. Permit ready to be issued.
Plan assigned to (CJW)1/10/2002 7/22/2002 PASS
DetailsCarl Westfall
7/22/2002 10:12:24 CJW - activity updated through activity BLDA022 from case BLD02-00031.
Routing - PLUMBING7/22/2002 7/22/2002 PASS
plans approved with corrections noted in letter from engineering inc dated 2/8/02. provide field inspector with resubmittals of water and drainage.
PLANS/APPL TAKEN TO FRONT DESK  7/22/2002 PASS
Issue PAID IN FULL permit  7/22/2002 DONE
Inspection Record Card- Bld  7/22/2002 DONE
Print Occupancy Form  7/22/2002 DONE
Plan resubmittals received  2/12/2002 DONE
Received two sets of resubmittal sheets A2.0 and A3.0 with transmittal. Routed to Carl Westfall.
Routing - PLUMBING1/28/2002 1/30/2002  
Failed first plumbing review. Mortuaries require an r.p. for premise protection on the water supply, locate in an area with adiquate drainage facilities, all fixtures in the lab area EXCEPT the shower/eye wash must be fed from the non-potable water system- janitor sink, cloths washer included. verify interceptor requirements with bench sewer dist. prior to plumbing review.
Plan Review Completed(1st rev)  1/28/2002  
Failed first UBC review.
Routing - FIRE1/25/2002 1/28/2002 PASS
DetailsBill Alexander
Routing - PLAN CHECK1/16/2002 1/23/2002  
Failed first UBC review. UBC plan review started January 23, 2002 and finished January 25, 2002. Resubmitted drawings from the architect were required. See the conditions list.
Routing - PUBLIC WORKS1/14/2002 1/16/2002 PASS
Plan resubmittals received  1/16/2002 DONE
Received Architect/Engineer of Record Declaration Form signed by owner.
Routing - PLANNING1/10/2002 1/14/2002 PASS
Marty Santoyo. Passed on to Scott Spjute for determination.
First Notice1/7/20021/7/20021/7/2002 DONE
Plans ACCEPTED BY PLAN TECH  1/7/2002 DONE
1. Applicant notified that an Owner's signature is required on the Architect/Engineer of Record Form.
Application received  1/7/2002  
Recd Pcfee & Taken To Pln CK  1/7/2002