Agreement of Future work | 9/11/2002 | 12/1/2004 | 6/20/2003 | | PASS |
|
|
|
County agrees to correct As deficiencies and full spk the bldg by fiscal year 03-04 or sooner. Completed Under FIR03-00087
|
Agreement of Future work | 11/14/2002 | 3/31/2003 | 12/27/2002 | | PASS |
|
|
|
County agrees to finish an alarm system upgrad in 60 days by 3-03. Work Completed Under Fir02-00364
|
Permanent Occupancy | | 12/27/2002 | 12/27/2002 | | DONE |
|
|
|
|
FIRE-Final Inspection | 12/26/2002 | 12/27/2002 | 12/27/2002 | A | FAIL |
Rick Jackson
|
|
|
###-#### dave tested alarms; see FIR02-00463 for corrections 12/27/2002 10:55:11 AM
|
BLD-Final | 12/26/2002 | 12/27/2002 | 12/27/2002 | A | PASS |
Tom Arcoraci
|
|
|
###-#### ok for perm pending fire insp 12/26/2002 3:12:28 PM
|
FIRE-Final Inspection | 12/27/2002 | 12/27/2002 | 12/27/2002 | P | PASS |
Rick Jackson
|
|
|
|
Permanent occupancy UNPAID FEE | | | 12/27/2002 | | DONE |
|
|
|
Perm. Occ. cert. #9505 issued 12-27-02 to the Ada County Coroner (Morgue).
|
Temporary occupancy | | | 11/15/2002 | | DONE |
|
|
|
Temp. Occ. Cert. #4892 issued 11-15-02 to the Ada County Coroner office (morgue)
|
FIRE-Final Inspection | 11/12/2002 | 11/12/2002 | 11/12/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide fire alarm drawings 11/12/2002 3:59:01 PM
|
BLD-Final | 11/12/2002 | 11/12/2002 | 11/12/2002 | P | PART |
Tom Arcoraci
|
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok for temp when fire signs card 11/12/02 3:19:31 PM
|
FIRE-Final Inspection | 11/4/2002 | 11/4/2002 | 11/4/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide approved hardware on the north corridor door, provide automatic shutdown for the hvac units. These detectors to be connected to the building fire alarm system and may require submittals to Boise city for approvals, provide manual pull station and relocate smoke detector from the wall to the deck. This also may require submittals to the city. Have the alarm contractor contact Sam Roger at ###-#### with any questions. Provide annual inspection report for the fire alarm system
|
Print Occupancy Form | | | 11/4/2002 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 10/3/2002 | 10/3/2002 | 10/3/2002 | P | PASS |
Tom Arcoraci
|
|
|
ceiling grid; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
BLD-Framing/Rough-in | 9/25/2002 | 9/25/2002 | 9/25/2002 | P | PART |
Tom Arcoraci
|
|
|
ceiling grid; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok 9/25/2002 3:46:31 PM
|
Meeting | | | 9/13/2002 | | DONE |
|
|
|
September 13, 2002 - Walked through 1:30pm - Met with Architect (Dan Kauffman), Ada County building maintenance, Fire Sprinkler Contractor, General Contractor and inspected facility for new and existing UFC fire protection issues. Found some existing offices not sprinklered, High-piled combustible storage 12'-0" high with 36" wide, single rack, solid shelf, storage of Class II commodities up to 15'-0". Minimum aisle widths are 40" (one side) and 44" (the other). System (installed in 1963+-), appears to be designed for OH pipe scheduled occupancy with a 120 ft/2 spacing, limiting it to 12'-0" maximum. UFC Article 81 would have to be addressed in this area of occupancy.
|
BLD-Framing/Rough-in | 8/26/2002 | 8/28/2002 | 8/28/2002 | A | PART |
Tom Arcoraci
|
|
|
dave; Phone #: ###-#### ok to cover from bath to coolers check struts after duct work is installed no other places inspected 8/28/2002 1:55:55 PM
|
BLD-Footing | 7/22/2002 | 7/23/2002 | 7/23/2002 | A | PASS |
Tom Arcoraci
|
|
|
###-#### dave
|
Routing - PLAN CHECK | 1/30/2002 | | 7/22/2002 | | PASS |
|
|
|
(2-15-02) Drawings approved February 15, 2002 after resubmittal review. Holding until after resolution of plumbing concerns. (7-22-02) Plumbing concerns resolved. Permit ready to be issued.
|
Plan assigned to (CJW) | 1/10/2002 | | 7/22/2002 | | PASS |
Carl Westfall
|
|
|
7/22/2002 10:12:24 CJW - activity updated through activity BLDA022 from case BLD02-00031.
|
Routing - PLUMBING | 7/22/2002 | | 7/22/2002 | | PASS |
|
|
|
plans approved with corrections noted in letter from engineering inc dated 2/8/02. provide field inspector with resubmittals of water and drainage.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/22/2002 | | PASS |
|
|
|
|
Issue PAID IN FULL permit | | | 7/22/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 7/22/2002 | | DONE |
|
|
|
|
Print Occupancy Form | | | 7/22/2002 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/12/2002 | | DONE |
|
|
|
Received two sets of resubmittal sheets A2.0 and A3.0 with transmittal. Routed to Carl Westfall.
|
Routing - PLUMBING | 1/28/2002 | | 1/30/2002 | | |
|
|
|
Failed first plumbing review. Mortuaries require an r.p. for premise protection on the water supply, locate in an area with adiquate drainage facilities, all fixtures in the lab area EXCEPT the shower/eye wash must be fed from the non-potable water system- janitor sink, cloths washer included. verify interceptor requirements with bench sewer dist. prior to plumbing review.
|
Plan Review Completed(1st rev) | | | 1/28/2002 | | |
|
|
|
Failed first UBC review.
|
Routing - FIRE | 1/25/2002 | | 1/28/2002 | | PASS |
Bill Alexander
|
|
|
|
Routing - PLAN CHECK | 1/16/2002 | | 1/23/2002 | | |
|
|
|
Failed first UBC review. UBC plan review started January 23, 2002 and finished January 25, 2002. Resubmitted drawings from the architect were required. See the conditions list.
|
Routing - PUBLIC WORKS | 1/14/2002 | | 1/16/2002 | | PASS |
|
|
|
|
Plan resubmittals received | | | 1/16/2002 | | DONE |
|
|
|
Received Architect/Engineer of Record Declaration Form signed by owner.
|
Routing - PLANNING | 1/10/2002 | | 1/14/2002 | | PASS |
|
|
|
Marty Santoyo. Passed on to Scott Spjute for determination.
|
First Notice | 1/7/2002 | 1/7/2002 | 1/7/2002 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 1/7/2002 | | DONE |
|
|
|
1. Applicant notified that an Owner's signature is required on the Architect/Engineer of Record Form.
|
Application received | | | 1/7/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 1/7/2002 | | |
|
|
|
|