Permit Information
Permit NumberBLD02-00190
StatusExpired
Name EMPIRE BLDG (BASEMENT HALLWAY)
Site Address 205 N 10TH ST Unit: BSMT
Project NameEMPIRE BLDG-BASEMENT
Customer Number 
ePlanReviewNo
Description
(EMPIRE BLDG - BASEMENT HALLWAY) This building is fire sprinklered under the provisions of the 1994 UCBC because it is too tall, too big, and has too many stories. To create a hallway in the basement and to surround an existing basement stairway with storefront glass. The shell for a 1,000 square foot pre-conference room is also being created in this 14,000 square foot basement. Since a tenant space is NOT allowed to exit through another tenant space, Suite B120 (1,100 square foot building conference room) and the new Suite B110 (1,000 square foot pre-conference room) shall be under the control of the same entity. Security hardware on doors shall not obstruct exiting. Work is to include interior nonbearing walls, storefront glass, interior doors, interior windows, and interior finishes all per approved drawings and plan review conditions on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (BLD)  11/25/2015 DONE
BLD-Aging Inspection2/19/20042/19/20042/19/2004 DONE
DetailsDave Hannah
DOC - Permit Expired2/19/20042/19/20042/19/2004APASS
DetailsDave Hannah
Expired by inspector at 2/19/2004 9:33:49 AM
Letter of compliance  10/25/2002 DONE
Letter of Compliance #22752 issued 10-25-02.
BLD-Final10/21/200210/22/200210/22/2002ANR
DetailsCarl Dependahl
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
BLD-Final10/22/200210/22/200210/22/2002PPASS
DetailsCarl Dependahl
ok for perm. occ 10/22/2002 2:01:58 PM
FIRE-Final Inspection10/17/200210/18/200210/18/2002APASS
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Amy Lawson
BLD-Final10/11/200210/14/200210/14/2002PNR
DetailsCarl Dependahl
will recall when fire/alarm resolved 10/14/2002 1:19:56 PM
BLD-Final10/11/200210/11/200210/11/2002PNR
DetailsCarl Dependahl
tim ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie...fire? 10/14/02 10:42:07 AM
BLD-Framing/Rough-in5/28/20025/28/20025/28/2002PPART
DetailsCarl Dependahl
GRID ###-#### TIM ok, add spreaders...chk at final 5/28/2002 4:16:26 PM
FIRE-Sprinkler Rough-in5/21/20025/22/20025/22/2002APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 05/21/2002 at 13:04:52. Contact: ###-####. okay to cover; left correction notice to install panic and exit signs as shown on plans 5/22/2002 10:07:59 AM
BLD-Wall cover4/25/20024/25/20024/25/2002PFAIL
DetailsCarl Dependahl
tim ###-#### wall cover ; c/n, need hvac, sprinkler r/i's...extend/return handrails at stairs, install exit signs as shown. ok to rock walls only. 4/25/2002 4:33:59 PM
Issue PAID IN FULL permit  3/4/2002 DONE
Routing - PLAN CHECK2/27/2002 3/1/2002 PASS
PLANS/APPL TAKEN TO FRONT DESK  3/1/2002 PASS
Inspection Record Card- Bld  3/1/2002 DONE
Telephone call  3/1/2002 DONE
Plan assigned to (CJW)2/5/2002 3/1/2002 PASS
DetailsCarl Westfall
3/1/2002 09:44:20 CJW - activity updated through activity BLDA022 from case BLD02-00190.
Routing - FIRE2/25/2002 2/27/2002 PASS
Plan Review Completed(1st rev)  2/27/2002 PASS
Plan resubmittals received  2/25/2002 DONE
Received two sets of resubmittal sheets A1.0 with cover letter. Routed to Carl Westfall.
Routing - PLAN CHECK2/5/2002 2/25/2002  
Failed first UBC plan review. UBC plan review started February 22, 2002 and was finished the same day. Resubmitted drawings from the architect were required. See the conditions list. A copy of the plan review report was sent to the architect.
Plans ACCEPTED BY PLAN TECH  1/31/2002 DONE
1. Plans not fully dimensioned.
2. In General Notes on Sheet A2.0, plans state that all plumbing, HVAC, electrical, and fire sprinkler system work is design build by the contractor. No Plumbing or HVAC plans were submitted.
First Notice1/30/20021/30/20021/30/2002 DONE
Application received  1/30/2002  
Recd Pcfee & Taken To Pln CK  1/30/2002 DONE