Code Occupancy Approval | 11/7/2002 | 11/6/2002 | 11/6/2002 | A | PASS |
Carol Montgomery
|
|
|
Signed final
|
Permanent occupancy UNPAID FEE | | | 10/18/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9411 issued 10-18-02 to Zions Bank in the Target Commerical complex.
|
Permanent Occupancy | | 10/17/2002 | 10/17/2002 | | DONE |
|
|
|
|
FIRE-Final Inspection | 10/16/2002 | 10/17/2002 | 10/17/2002 | A | PASS |
Troy Cobbley
|
|
|
the requirement for the knox box is no longer a requirement. Life/safety finaled 10/17/2002 10:48:16 AM
|
BLD-Final | 10/16/2002 | 10/17/2002 | 10/17/2002 | P | PASS |
Jim Sly
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung OK for Perm. Occ. 10/17/2002 3:47:59 PM
|
BLD-Framing/Rough-in | 10/11/2002 | 10/11/2002 | 10/11/2002 | P | PASS |
Jim Sly
|
|
|
CALL DAVID FIRST ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung should be final....Temp OK. 10/11/2002 11:52:59 AM
|
BLD-Final | 10/11/2002 | 10/11/2002 | 10/11/2002 | A | PART |
Jim Sly
|
|
|
OK for Temp Occ.
|
BLD-Final | 10/10/2002 | 10/10/2002 | 10/10/2002 | P | FAIL |
Jim Sly
|
|
|
###-#### C/N...Firecaulk and damper at 1hr ceiling Bsmnt Mech rm. 10/10/2002 3:48:53 PM
|
BLD-Final | 10/8/2002 | 10/9/2002 | 10/9/2002 | A | NR |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 10/08/2002 at 12:38:47. Contact: ###-####. needs code enf to sign 10/9/2002 8:44:53 AM
|
PubWorks Occupancy Approval | 10/7/2002 | 10/7/2002 | 10/7/2002 | | DONE |
|
|
|
Drainage project complete, signed permanent occupancy 10/7/02. R.Rokovitz
|
FIRE-Final Inspection | 10/3/2002 | 10/4/2002 | 10/4/2002 | P | PART |
Troy Cobbley
|
|
|
temporary occupancy given with dave millers permission until the knox box gets installed and the extinguishers get tagged 10/4/2002 2:03:05 PM
|
BLD-Final | 10/3/2002 | 10/4/2002 | 10/4/2002 | P | NR |
Jim Sly
|
|
|
###-#### tim
|
BLD-Framing/Rough-in | 9/27/2002 | 9/30/2002 | 9/30/2002 | A | PART |
Jim Sly
|
|
|
TIM ###-#### 9/30/2002 10:24:07 AM
|
Override - Parcel Holds | | | 9/27/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 9/23/2002 | 9/23/2002 | 9/23/2002 | P | PART |
Jim Sly
|
|
|
###-#### Conf on 1hr ceiling Bsmnt. 9/23/2002 2:51:03 PM
|
Override - Parcel Holds | | | 9/23/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 9/19/2002 | 9/20/2002 | 9/20/2002 | A | PART |
Jim Sly
|
|
|
###-#### Ceiling grid main room OK. 9/20/2002 10:52:06 AM
|
Override - Parcel Holds | | | 9/19/2002 | | |
|
|
|
|
BLD-Other | 9/12/2002 | 9/13/2002 | 9/13/2002 | A | PART |
Jim Sly
|
|
|
partial ceiling --tim ###-#### Perimeter offices OK for ceiling tile. 9/13/2002 12:02:06 PM
|
Override - Parcel Holds | | | 9/12/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 8/16/2002 | 8/19/2002 | 8/19/2002 | A | PASS |
Jim Storey
|
|
|
TIM ###-#### TIM ###-####framing ok. 8/19/2002 11:11:16 AM
|
Override - Parcel Holds | | | 8/16/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 8/13/2002 | 8/13/2002 | 8/13/2002 | P | PART |
Jim Sly
|
|
|
tim ###-#### shear Roof nailing....OK. 8/13/2002 1:57:19 PM
|
Override - Parcel Holds | | | 8/13/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 8/12/2002 | 8/12/2002 | 8/12/2002 | P | CANC |
Jim Sly
|
|
|
early pm ###-#### Canc by contr. 8/12/2002 1:54:45 PM
|
Override - Parcel Holds | | | 8/12/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 8/6/2002 | 8/7/2002 | 8/7/2002 | A | PART |
Russ Owen
|
|
|
TIM ###-#### PARTIAL R/I AND A SHEAR NAIL roof area went over corrections with tim will recall. 8/7/2002 11:27:50 AM
|
Override - Parcel Holds | | | 8/6/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 7/26/2002 | 7/26/2002 | 7/26/2002 | P | PART |
Jim Sly
|
|
|
fn insp tim- ###-#### -roof nailing Roof diaphram nailing and straps. OK 7/26/2002 2:42:32 PM
|
Override - Parcel Holds | | | 7/26/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 7/23/2002 | 7/24/2002 | 7/24/2002 | A | NR |
Jim Sly
|
|
|
###-####\\partial
|
BLD-Framing/Rough-in | 7/23/2002 | 7/23/2002 | 7/23/2002 | P | PART |
Dave Hannah
|
|
|
nailing \\###-#### shear nailing everything ok but for the back of the vault wall and two hold downs on the sw corners 7/23/2002 1:36:41 PM
|
Override - Parcel Holds | | | 7/23/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 7/23/2002 | | |
|
|
|
|
BLD-Foundation | 6/17/2002 | 6/18/2002 | 6/18/2002 | A | PART |
Jim Sly
|
|
|
stem wall ###-#### kim East 1/2 of Bldg ( 2' stem wall).....Pending MTI insp, reports, and approvals. 6/18/2002 11:16:21 AM
|
| | | 6/17/2002 | | DONE |
Annett Moore
|
|
|
Parcel Tag Notes: Ok to issue building permit, but DO NOT release Certificate of occupancy until Target Subdivision is recorded. Verify with Subdivisions staff before removal of this tag. (blc) Reason for OverRide:
|
BLD-Foundation | 6/12/2002 | 6/13/2002 | 6/13/2002 | A | PART |
Jim Sly
|
|
|
found wall -tim-###-#### 6/13/2002 10:42:51 AM Bsmnt walls ....Pending MTI insp and approvals. 6/13/2002 11:33:38 AM
|
Override - Parcel Holds | | | 6/12/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 6/12/2002 | | |
|
|
|
|
BLD-Footing | 6/10/2002 | 6/11/2002 | 6/11/2002 | A | PART |
Jim Sly
|
|
|
kim ###-#### ft Footing for E wall E 1/2 of S wall and E 1/2 of N wall ....Pending MTI insp and approvals. 6/11/2002 12:11:09 PM 6/11/2002 12:19:46 PM
|
Override - Parcel Holds | | | 6/10/2002 | | |
|
|
|
|
BLD-Footing | 6/4/2002 | 6/5/2002 | 6/5/2002 | P | PART |
Jim Sly
|
|
|
###-#### Bsmnt Footing Pending special insp. and approval. Special insp Gary (MTI) appears to be qualified to do the job. 6/5/2002 3:36:54 PM
|
Override - Parcel Holds | | | 6/4/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 6/4/2002 | | |
|
|
|
|
Inspection Record Card- Bld | | | 6/4/2002 | | |
|
|
|
|
Print Occupancy Form | | | 6/4/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 6/4/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 6/4/2002 | | |
|
|
|
|
(F) Reprint permit | | | 5/29/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 5/28/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 5/28/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 5/28/2002 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/28/2002 | | DONE |
|
|
|
|
Routing - FIRE | 4/15/2002 | 4/15/2002 | 4/15/2002 | | PASS |
Bill Alexander
|
|
|
|
Routing - FIRE | 4/5/2002 | 4/9/2002 | 4/15/2002 | | FAIL |
Bill Alexander
|
|
|
Lack hydrant location (flows provided but not shown where)?
|
Plan assigned to (JCM) | 3/5/2002 | | 4/15/2002 | | PASS |
John Menard
|
|
|
4/15/2002 11:20:27 JCM - activity updated through activity BLDA022 from case BLD02-00431.
|
Routing - PLAN CHECK | 4/15/2002 | | 4/15/2002 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/15/2002 | | PASS |
|
|
|
|
Override - Parcel Holds | | | 4/15/2002 | | |
|
|
|
|
Inspection Record Card- Bld | | | 4/15/2002 | | DONE |
|
|
|
|
Print Occupancy Form | | | 4/15/2002 | | DONE |
|
|
|
|
Plan Review Completed(1st rev) | | | 4/15/2002 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 4/15/2002 | | 4/15/2002 | | |
|
|
|
|
Plan Reviewer's activity | | | 4/15/2002 | | PASS |
|
|
|
Reviewed and approved resubmitted plan revisions. JCM
|
Plan resubmittals received | | | 4/11/2002 | | DONE |
|
|
|
Received two sets of resubmittal sheets E2.1, A-2, and cover letter. Routed to John Menard.
|
Routing - PLAN CHECK | 3/29/2002 | | 4/5/2002 | | FAIL |
|
|
|
|
Plan resubmittals requested | | | 4/5/2002 | | FAIL |
|
|
|
Mailed the architect of record a copy of the plan review comment list requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 3/29/2002 | | 4/3/2002 | | PASS |
|
|
|
called pdq to send resubmittal sheets s0.1, s1.2, s2.1, s7.1, s7.2. dkl Recieved a fax from the consulting structural engineer approving the resubmitted plan sheets. JCM
|
Plan resubmittals received | | | 3/28/2002 | | DONE |
|
|
|
Received three copies of revised sheets S0.1, S1.2, S2.1, S7.1, S7.2 and struct. specs. Routed to John M. kmm
|
Routing - PLUMBING | 3/27/2002 | | 3/28/2002 | | PASS |
|
|
|
min. horizontal roof drainage piping is 3".
|
Routing - PLANNING | 3/22/2002 | | 3/27/2002 | | PASS |
|
|
|
Approved for cup, Mark Pecchenino CUP01-00156 Still requires DR review by Sarah Schafer . kmm Approved per drh02-7 and as noted on sheets A-5 and A-14. Memo written to file regarding these items and copied to architect.
|
Routing - PUBLIC WORKS | 3/20/2002 | | 3/22/2002 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 3/5/2002 | | 3/19/2002 | | PASS |
|
|
|
Land division will be ok when Target Subdivision is recorded. We will pass for permit release, but a parcel tag is being placed to restrict for Certificate of Occupancy until sub is recorded. Routed to Public Works. (blc)
|
Plan resubmittals requested | | | 3/19/2002 | | |
|
|
|
Faxed the architect of record a copy of the comment list from the consulting structural engineer requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 3/5/2002 | | 3/18/2002 | | FAIL |
|
|
|
contacted PDQ to take plans to outside eng. kmm Received comment list from consulting structural engineer requesting revisions. JCM
|
Plans ACCEPTED BY PLAN TECH | | | 3/5/2002 | | PASS |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 3/5/2002 | | DONE |
|
|
|
|
First Notice | 3/4/2002 | 3/4/2002 | 3/4/2002 | | DONE |
|
|
|
project value 599,304 ele 58,500 p 23,300 m 29,140
|
Application received | | | 3/4/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 3/4/2002 | | DONE |
|
|
|
|