Case Summary (BLD) | | | 8/18/2015 | | DONE |
|
|
|
|
Fee Review-notes | 7/18/2003 | 7/18/2003 | 7/18/2003 | | DONE |
|
|
|
|
Permanent occupancy | | | 2/24/2003 | | DONE |
|
|
|
Perm. Occ. Cert. #9565 issued 2-24-03 to Boise City Fire & Police Internal Affairs on the 3rd floor of City Hall.
|
Permanent Occupancy | | 2/11/2003 | 2/11/2003 | | DONE |
|
|
|
|
BLD-Final | 2/10/2003 | 2/11/2003 | 2/11/2003 | A | PASS |
Carl Dependahl
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung...ok for c/o...alarms ok per agreement2/11/2003 9:05:37 AM 2/11/2003 9:19:09 AM
|
BLD-Conference | 12/20/2002 | 12/23/2002 | 12/23/2002 | P | PASS |
Carl Dependahl
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung...w/ arch re 3rd fl...keep c/n re carpet. 12/23/2002 3:16:12 PM
|
BLD-Conference | 12/23/2002 | 12/23/2002 | 12/23/2002 | P | CANC |
Carl Dependahl
|
|
|
|
BLD-Final | 10/21/2002 | 10/21/2002 | 10/21/2002 | A | FAIL |
Carl Dependahl
|
|
|
complete carpet removal at restrm, comply w/ UBC 807, ok for t/o. 10/21/02 4:01:11 PM
|
BLD-Final | 10/17/2002 | 10/18/2002 | 10/18/2002 | A | NR |
Carl Dependahl
|
|
|
|
BLD-Final | 10/16/2002 | 10/17/2002 | 10/17/2002 | P | NR |
Carl Dependahl
|
|
|
resolve carpet & other c/n items 10/17/02 4:44:18 PM
|
BLD-Conference | 10/15/2002 | 10/16/2002 | 10/16/2002 | P | PASS |
Carl Dependahl
|
|
|
ww dan s. re notes 10/16/02 5:43:24 PM
|
BLD-Final | 10/14/2002 | 10/15/2002 | 10/16/2002 | A | NR |
Carl Dependahl
|
|
|
3rd fl. Scott
|
BLD-Final | 10/11/2002 | 10/14/2002 | 10/14/2002 | A | NR |
Carl Dependahl
|
|
|
|
BLD-Final | 10/10/2002 | 10/11/2002 | 10/11/2002 | A | NR |
Carl Dependahl
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
BLD-Final | 10/7/2002 | 10/7/2002 | 10/7/2002 | A | FAIL |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 10/07/2002 at 07:19:00. Contact: ###-####...ok for t/o, keep c/n: firestops (existing condition) at util rm & shaft 10/7/02 4:11:47 PM
|
FIRE-Final Inspection | 10/3/2002 | 10/4/2002 | 10/5/2002 | A | PASS |
Rick Jackson
|
|
|
|
BLD-Final | 10/4/2002 | 10/4/2002 | 10/4/2002 | P | NH |
Carl Dependahl
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
BLD-Conference | 10/4/2002 | 10/4/2002 | 10/4/2002 | P | PASS |
Carl Dependahl
|
|
|
Keep c/n...need to remove carpet from restroom at 3rd fl.
|
FIRE-Final Inspection | 10/2/2002 | 10/3/2002 | 10/3/2002 | A | FAIL |
Rick Jackson
|
|
|
will test alarms on 10/4 10/3/2002 4:25:59 PM
|
BLD-Final | 10/2/2002 | 10/3/2002 | 10/3/2002 | P | FAIL |
Carl Dependahl
|
|
|
keep c/n...add exit sign, egress control fail safe, firestops at shafts, etc...need fire ok'd 10/3/2002 3:23:11 PM
|
FIRE-Final Inspection | 10/1/2002 | 10/2/2002 | 10/2/2002 | P | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung need alarm plans approved prior to testing; need clarification about double egress doors at lobby 10/2/2002 4:34:23 PM
|
BLD-Final | 10/1/2002 | 10/2/2002 | 10/2/2002 | P | FAIL |
Carl Dependahl
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung. NR, see bld02-0938... 10/2/2002 4:50:28 PM
|
BLD-Conference | 9/5/2002 | 9/6/2002 | 9/6/2002 | A | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 09/05/2002 at 13:45:30. Contact: ###-####....w/ scott re finals 9/6/2002 2:58:01 PM
|
Print Occupancy Form | | | 9/5/2002 | | |
|
|
|
|
BLD-Framing/Rough-in | 8/9/2002 | 8/12/2002 | 8/12/2002 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 08/09/2002 at 07:49:00. Contact: ###-####. grid ok 8/12/2002 2:37:53 PM
|
BLD-Framing/Rough-in | 8/6/2002 | 8/7/2002 | 8/7/2002 | A | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 08/06/2002 at 13:33:27. Contact: ###-####....3rd floor rest room plbg penetrations repaired, ok to tile wall 8/7/2002 4:07:06 PM
|
BLD-Conference | 7/17/2002 | 7/17/2002 | 7/17/2002 | P | PASS |
Carl Dependahl
|
|
|
w/ supt re: "shaft" at restrooms...complete gyp install...patch as needed, add sealants at pipes.
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Conference | 7/8/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Carl Dependahl
|
|
|
need archs details for wet wall/shaft assy. 7/9/2002 2:55:26 PM
|
BLD-Framing/Rough-in | 7/8/2002 | 7/8/2002 | 7/8/2002 | P | PART |
Carl Dependahl
|
|
|
scott- ###-#### plbg permit issue ok, partitions ok...need clarify shaft/core at res 7/8/2002 4:52:03 PM trooms 7/8/2002 4:52:55 PM
|
BLD-Framing/Rough-in | 7/1/2002 | 7/2/2002 | 7/2/2002 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 07/01/2002 at 13:45:37. Contact: ###-####. one side only need oppiset legs screwed/ plan calls for elavator protection not in place. 7/2/2002 3:30:58 PM
|
BLD-Wall cover | 7/1/2002 | 7/2/2002 | 7/2/2002 | P | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 07/01/2002 at 13:46:16. Contact: ###-####. one side only/ need plm permit and r/i insp. 7/2/2002 3:29:43 PM
|
Issue PAID IN FULL permit | | | 5/23/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 5/23/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 5/23/2002 | | DONE |
|
|
|
|
Telephone call | | | 5/16/2002 | | DONE |
|
|
|
CALLED LEFT MESSAGE WITH TONYA PLANS READY 5-16-02///DLD
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/15/2002 | | PASS |
|
|
|
To permit desk to issue.
|
Routing - PLAN CHECK | 4/24/2002 | | 5/15/2002 | | PASS |
|
|
|
Approved as noted on plans & attached plan review comments from all reviewing agencies.
|
Plan assigned to (DRS) | 3/21/2002 | | 5/15/2002 | | PASS |
Dan Stuart
|
|
|
5/15/2002 09:05:50 DRS - activity updated through activity BLDA022 from case BLD02-00579.
|
Plan resubmittals received | | | 5/8/2002 | | DONE |
|
|
|
Received two sets of resubmittal sheets A0.01, A0.20, A0.21, A0.22, A0.23, A0.24, A1.43, A1.44, A2.13, A2.14, A2.23, A2.24, A2.60, A2.70, A2.80, A3.10, A5.11, A5.12, A5.13, A5.14, A5.15, A5.16, A6.13, A6.14, A9.11, A9.12, P0.1, P0.2, P1.0, P1.1, P2.0, P2.1, M1.0, M1.1, M2.0, M2.1, M3.0, FP1.0, FP1.1, E0.1, E1.3, E1.4, E2.3, E2.4, E3.3, E3.4, E4.3, E4.4, E5.0, with cover letter. Routed to Dan Stuart.
|
Routing - FIRE | 4/19/2002 | 4/24/2002 | 4/24/2002 | | PASS |
Bill Alexander
|
|
|
|
Plan Review Completed(1st rev) | | | 4/24/2002 | | DONE |
|
|
|
|
Plan resubmittals requested | | | 4/19/2002 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 3/26/2002 | | 4/19/2002 | | FAIL |
|
|
|
Corrections required. Copies of plan review comments faxed and mailed to architect, Ted Isbell. Plans routed to fire code analyst.
|
Routing - PUBLIC WORKS | 3/21/2002 | | 3/26/2002 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 3/19/2002 | | DONE |
|
|
|
1. Plans not fully dimensioned.
|
Additional plans submitted | | | 3/19/2002 | | DONE |
|
|
|
Received two sets of Sheets A5.12. Attached to plans.
|
First Notice | 3/18/2002 | 3/18/2002 | 3/18/2002 | | DONE |
|
|
|
|
Application received | | | 3/18/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 3/18/2002 | | DONE |
|
|
|
fees waived
|