BLD-Aging Inspection | 7/7/2004 | 7/7/2004 | 7/7/2004 | | CANC |
Tom Arcoraci
|
|
|
|
DOC - Permit Expired | 7/7/2004 | 7/7/2004 | 7/7/2004 | A | PASS |
Tom Arcoraci
|
|
|
Expired by inspector at 7/7/2004 9:32:17 AM
|
BLD-Aging Inspection | 5/3/2004 | 5/3/2004 | 5/3/2004 | | DONE |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 3/1/2004 | 3/1/2004 | 3/1/2004 | | NR |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 12/29/2003 | 12/29/2003 | 12/29/2003 | | NR |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 10/15/2003 | 10/15/2003 | 10/15/2003 | | NR |
Tom Arcoraci
|
|
|
wip 10/15/2003 9:38:08 AM
|
BLD-Aging Inspection | 8/14/2003 | 8/14/2003 | 8/14/2003 | | PASS |
Tom Arcoraci
|
|
|
wip 8/14/2003 9:41:18 AM
|
FIRE-Final Inspection | 2/21/2003 | 2/25/2003 | 2/25/2003 | A | PASS |
Troy Cobbley
|
|
|
Fire life safety, fire alarm and fire sprinklers finaled 2/25/2003 10:47:58 AM
|
BLD-Final | 2/25/2003 | 2/25/2003 | 2/25/2003 | P | PASS |
Jim Sly
|
|
|
###-####; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung C/C issued. 1st Phase. OK for Occ. 2/25/2003 3:14:38 PM 2/25/2003 3:15:17 PM
|
FIRE-Sprinkler Rough-in | 2/13/2003 | 2/14/2003 | 2/14/2003 | P | PART |
Troy Cobbley
|
|
|
Fire sprinklers finaled. Fire life safety appears to be OK but cannot be finaled until the fire alarm system has been tested and passed 2/14/2003 2:45:48 PM
|
BLD-Framing/Rough-in | 2/7/2003 | 2/10/2003 | 2/10/2003 | P | PASS |
Tom Arcoraci
|
|
|
9413192 final should be next insp 2/10/2003 4:23:08 PM
|
BLD-Framing/Rough-in | 2/6/2003 | 2/7/2003 | 2/7/2003 | P | NR |
Carl Dependahl
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
FIRE-Final Inspection | 2/6/2003 | 2/7/2003 | 2/7/2003 | P | FAIL |
Troy Cobbley
|
|
|
The permit cannot be finaled due to missing ceiling tile and lack of plan review notes and other misc. items listed on the approved plans. Piping is OK to cover in all areas for the first phase 2/7/2003 3:50:02 PM
|
BLD-Framing/Rough-in | 1/23/2003 | 1/24/2003 | 1/24/2003 | A | CANC |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 1/9/2003 | 1/23/2003 | 1/23/2003 | A | CANC |
Tom Arcoraci
|
|
|
check wip
|
BLD-Framing/Rough-in | 1/23/2003 | 1/23/2003 | 1/23/2003 | P | PART |
Tom Arcoraci
|
|
|
check wip
|
BLD-Framing/Rough-in | 1/8/2003 | 1/9/2003 | 1/9/2003 | A | PASS |
Tom Arcoraci
|
|
|
cecil ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie wip ok 1/9/2003 10:18:09 AM
|
BLD-Framing/Rough-in | 11/13/2002 | 11/14/2002 | 11/14/2002 | A | PART |
Tom Arcoraci
|
|
|
###-#### wip ok 11/14/2002 10:47:53 AM
|
FIRE-Sprinkler Rough-in | 11/13/2002 | 11/14/2002 | 11/14/2002 | A | PART |
Troy Cobbley
|
|
|
alcoves and one restroom area is ok to cover. see on site approved plans for specific areas 11/14/2002 11:11:41 AM
|
BLD-Conference | 10/10/2002 | 10/11/2002 | 10/11/2002 | A | PASS |
Tom Arcoraci
|
|
|
wip 10/11/2002 10:49:31 AM
|
BLD-Conference | 10/9/2002 | 10/10/2002 | 10/10/2002 | A | PASS |
Tom Arcoraci
|
|
|
wip 10/10/2002 12:08:31 PM
|
BLD-Conference | 10/10/2002 | 10/10/2002 | 10/10/2002 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Conference | 10/9/2002 | 10/9/2002 | 10/9/2002 | P | PASS |
Tom Arcoraci
|
|
|
###-#### wip 10/9/2002 3:27:42 PM
|
BLD-Conference | 10/9/2002 | 10/9/2002 | 10/9/2002 | A | PASS |
Carl Dependahl
|
|
|
Tom, this one's for you...call Cecil
|
Override - Parcel Holds | | | 10/9/2002 | | |
|
|
|
|
BLD-Wall cover | 9/26/2002 | 9/27/2002 | 9/27/2002 | A | CANC |
Tom Arcoraci
|
|
|
|
BLD-Wall cover | 9/27/2002 | 9/27/2002 | 9/27/2002 | P | DONE |
Tom Arcoraci
|
|
|
|
BLD-Conference | 9/24/2002 | 9/26/2002 | 9/26/2002 | P | CANC |
Tom Arcoraci
|
|
|
|
BLD-Conference | 9/13/2002 | 9/18/2002 | 9/18/2002 | A | PASS |
Tom Arcoraci
|
|
|
wip ok 9/18/2002 11:58:54 AM
|
BLD-Conference | 9/18/2002 | 9/18/2002 | 9/18/2002 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Framing/Rough-in | 9/12/2002 | 9/13/2002 | 9/13/2002 | A | PART |
Tom Arcoraci
|
|
|
cecil --conf insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie wip ok 9/13/2002 10:41:46 AM
|
BLD-Conference | 9/4/2002 | 9/4/2002 | 9/4/2002 | P | PASS |
Carl Dependahl
|
|
|
cecil; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--5th floor, corridor/ hall; top of walls sealed to existing structure at corridor; infill at shaft wall ok to complete ... frame is firestopped, install 2hr wall assy. 9/4/2002 4:52:29 PM
|
BLD-Framing/Rough-in | 8/26/2002 | 8/26/2002 | 8/26/2002 | P | PART |
Tom Arcoraci
|
|
|
###-#### \\partial wip ok 8/26/2002 5:00:55 PM
|
BLD-Conference | 8/26/2002 | 8/26/2002 | 8/26/2002 | P | PASS |
Carl Dependahl
|
|
|
w/ Cecil...to 408 8/26/2002 5:10:37 PM
|
BLD-Conference | 8/16/2002 | 8/20/2002 | 8/20/2002 | A | PASS |
Tom Arcoraci
|
|
|
5 th floor to reveiw plans 8/19/2002 10:12:31 AM
|
BLD-Conference | 8/20/2002 | 8/20/2002 | 8/20/2002 | P | PASS |
Tom Arcoraci
|
|
|
5 th floor wip ok 8/20/2002 3:29:42 PM
|
BLD-Conference | 8/15/2002 | 8/16/2002 | 8/16/2002 | A | PASS |
Tom Arcoraci
|
|
|
5th floor 8/15/2002 2:10:56 PM wip 8/16/2002 10:48:27 AM
|
Inspection Record Card- Bld | | | 6/6/2002 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/6/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/6/2002 | | DONE |
|
|
|
CALLED PLANS READY 6-6-02///DLD
|
Issue PAID IN FULL permit | | | 6/6/2002 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 5/30/2002 | 5/30/2002 | 6/5/2002 | | PASS |
|
|
|
Resubmittals of 6/4/02 inserted into plans. Plans approved as noted and per attached plan review commnets from all reviwing agencies as part of the approved plans. Routing to permit desk to issue.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/5/2002 | | PASS |
|
|
|
To permit desk.
|
Plan assigned to (DRS) | 4/3/2002 | | 6/5/2002 | | PASS |
Dan Stuart
|
|
|
6/5/2002 11:37:41 DRS - activity updated through activity BLDA022 from case BLD02-00728.
|
Plan resubmittals received | | | 6/4/2002 | | DONE |
|
|
|
Received two copies of revised sheets MV-101 & FA101. One copy of response letter and one copy of the sheets that were replaced by Jeff Cramer. Routed to Dan S. kmm
|
Telephone call | | | 5/31/2002 | | DONE |
|
|
|
Call from Jeff Cramer, HDR to review the outstanding items concerning the S/F dampers, detectors & electrical controls for duct penetrations through the smoke barrier. Duct penetrations between south side patient rooms do not indicate the required duct and controls and the ducts above the both sets of double doors need dampers shown & controls indicated on sheets MV101 & FA101. Jeff will follow up with mechanical & electrical and provide the cover letter showing his response and new details per the plan review.
|
Plan resubmittals requested | | | 5/31/2002 | | FAIL |
|
|
|
Talked with Jeff Cramer, architect. A cover letter is needed to reflect the specific response to the plan review comments. Need clarification for seismic pod design indicated in detail 5/ A603. Need validation of strut call out and information noted on plan as existing in specification book sec. 09510, that isn't in the spec book. Also reviewed the deficiencies on sheets MV101 & FA101 for smoke/fire dampers, detectors & controls for ducts penetrating the smoke barrier. Jeff is working on re-submittal corrections.
|
Routing - PLAN CHECK | 5/10/2002 | 5/10/2002 | 5/30/2002 | | FAIL |
|
|
|
Resubmittals received on 5/23/02 were inserted into plans by architect Jeff Cramer. Review of the resubmittals against the plan review comments are unclear as a cover letter addressing the specific response to the correction and the location of the correction on the new plans was not provided. Information on the seismic pod, smoke barrier design anf the protection of penetrations of the smoke barrier W/ S/F dampers and controls are still in need of correction. I have discussed the concept with Jeff Crammer who is working on the re-submittals.
|
Plan resubmittals received | | | 5/30/2002 | | DONE |
|
|
|
Received one set of rsubmittal structural calculations. Routed to Dan Stuart.
|
Telephone call | | | 5/30/2002 | | DONE |
|
|
|
Received response from ICBO by phone, Page Doughtery & Dennis McCleary, concerning the requirements of section 308.2.2.1 & 905.2.3 for smoke barriere construction & testing. Intent of sections per ICBO staff is theat all perimeter edges (walls, ceiling & floor) need to be sealed with approved caulk or equal and that all penetrations and openings be protected with approved listed systems & assemblies per chapter 7 UBC. I passed this information on to Roger Albers by voice mail nd ask him to call me back if he had questions.
|
Plan resubmittals received | | | 5/23/2002 | | DONE |
|
|
|
Received two sets of resubmittal sheets G-101, A-101, AC-101, AE-101, A-103, A-401, A-601, A-603, A-701, A-710, P-001, PD-101WT, PD-101PB, PW-101, PP-101, PG-101, PF-101, M-001, MD-101HV, MD-101HD, MV-101, MH-101, E-001, ED101, FA101, EM-101, EP101, EP-103, EP104, EP105, EP106, EP107, ET101, E601, E602, E603, (1) Addendum No. 2 Revisions, (1) Addendum No. 3 Revisions, Information on Water Closets, AD-1 Room Finish Schedule Changes. Routed to Dan Stuart.
|
Plan Review Completed(1st rev) | | | 5/10/2002 | | FAIL |
|
|
|
|
Routing - FIRE | 5/7/2002 | | 5/10/2002 | | PASS |
|
|
|
|
Plan resubmittals requested | | | 5/7/2002 | | FAIL |
|
|
|
Copy of correction list faxed and mailed to architect.
|
Routing - PLAN CHECK | 4/15/2002 | | 5/7/2002 | | FAIL |
|
|
|
Additional information, plans & engineering required. Copy of plan review comments faxed & mailed to architect.
|
Routing - PLUMBING | 4/5/2002 | | 4/15/2002 | | PASS |
|
|
|
per plans and 2000 upc.
|
Routing - PUBLIC WORKS | 4/3/2002 | | 4/5/2002 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 4/2/2002 | | DONE |
|
|
|
|
Application received | | | 4/1/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/1/2002 | | DONE |
|
|
|
|
Fee Review-notes | 4/1/2002 | 4/1/2002 | | | |
|
|
|
|