Case Summary (BLD) | | | 7/2/2013 | | DONE |
|
|
|
|
Fee Review-notes | 7/22/2003 | 7/22/2003 | 7/22/2003 | | DONE |
|
|
|
1. Fees only charged for original Certificate of Value of $52,000. Revised Certificate of Value of $77,000 submitted on 6/3/02.
2. Additional values from subcontractors.
|
Permanent occupancy | | | 8/12/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9294 issued 8-12-02 to NYK Logistics & Megacarrier on the 12th floor of the U.S. Bank Bldg.
|
BLD-Final | 8/7/2002 | 8/7/2002 | 8/7/2002 | P | PASS |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 08/07/2002 at 09:45:13. Contact: ###-####.
|
BLD-Final | 8/6/2002 | 8/6/2002 | 8/6/2002 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 08/06/2002 at 10:53:31. Contact: ###-####....need plans onsite, recall 8/6/2002 5:07:54 PM
|
FIRE-Final Inspection | 8/2/2002 | 8/2/2002 | 8/2/2002 | P | PASS |
Rick Jackson
|
|
|
|
Permanent Occupancy | | 8/2/2002 | 8/2/2002 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 7/11/2002 | 7/12/2002 | 7/12/2002 | P | PART |
Carl Dependahl
|
|
|
DAVE ###-#### wip, complete plbg, ok to use extended office area 7/12/2002 3:01:26 PM
|
FIRE-Alarm Testing | 7/3/2002 | 7/9/2002 | 7/9/2002 | A | PASS |
Rick Jackson
|
|
|
###-#### loren please call 1st alrms tested okay; need rated doors at restroom areas 7/9/2002 10:09:24 AM
|
BLD-Framing/Rough-in | 7/2/2002 | 7/3/2002 | 7/3/2002 | A | PART |
Tom Arcoraci
|
|
|
###-#### samm wip 7/3/2002 11:51:57 AM
|
BLD-Framing/Rough-in | 6/27/2002 | 6/27/2002 | 6/27/2002 | P | FAIL |
Carl Dependahl
|
|
|
r/i- sam- ###-#### c/n, extend 1hr assy's to deck, seal penetrations at wa 6/27/2002 4:08:48 PM lls & floors 6/27/2002 4:09:00 PM
|
BLD-Conference | 6/26/2002 | 6/26/2002 | 6/26/2002 | P | PASS |
Carl Dependahl
|
|
|
###-#### SAM ADA clr at rest rm.ok due to existing stand pipe ( 19" to c.l.) Awaiting archs detail re corridor walls 6/26/2002 2:33:10 PM
|
FIRE-Conference | 6/24/2002 | 6/25/2002 | 6/25/2002 | A | PART |
Rick Jackson
|
|
|
###-#### exit signs to installed as redlined on approved plans 6/25/2002 8:01:34 AM
|
BLD-Conference | 6/20/2002 | 6/21/2002 | 6/21/2002 | A | PASS |
Carl Dependahl
|
|
|
###-#### CALL FIRST need arch's detail to maintain 1hr corridors around core 6/21/2002 2:35:46 PM
|
BLD-Conference | 6/21/2002 | 6/21/2002 | 6/21/2002 | P | CANC |
Carl Dependahl
|
|
|
|
Issue PAID IN FULL permit | | | 6/10/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/5/2002 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/5/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/5/2002 | | DONE |
|
|
|
CALLED RYAN 6-5-02
|
(F) Reprint permit | | | 6/5/2002 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 4/23/2002 | | 6/4/2002 | | PASS |
|
|
|
(4-29-02) Received a letter from the architect requesting that upgrades for accessibility not be required. (5-1-02) Request was denied by the Building Official. (6-4-02) Drawings showing the common restrooms upgraded to be accessible to the disabled were provided. The project was approved.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/4/2002 | | PASS |
|
|
|
|
Plan assigned to (CJW) | 4/5/2002 | | 6/4/2002 | | PASS |
Carl Westfall
|
|
|
6/4/2002 11:19:01 CJW - activity updated through activity BLDA022 from case BLD02-00731.
|
Plan resubmittals received | | | 6/3/2002 | | DONE |
|
|
|
Received two copies of revised sheets A5.0 A5.1 and one copy of revised cert. of value. Routed to Carl W. kmm
|
Routing - FIRE | 4/18/2002 | | 4/23/2002 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 4/23/2002 | | |
|
|
|
Failed first UBC review.
|
Routing - PLAN CHECK | 4/9/2002 | | 4/18/2002 | | |
|
|
|
Failed first UBC review. UBC plan review started April 17, 2002 and was finished the next day. Resubmitted drawings from the architect were required. See the conditions list. A copy of the plan review report was sent to the architect.
|
Routing - PUBLIC WORKS | 4/5/2002 | | 4/8/2002 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 4/2/2002 | | DONE |
|
|
|
|
First Notice | 4/1/2002 | 4/1/2002 | 4/1/2002 | | DONE |
|
|
|
|
Application received | | | 4/1/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/1/2002 | | DONE |
|
|
|
|