Permit NumberBLD02-00745
StatusFinaled
Name ST ALPHONSUS REG MED CEN INC
Site Address 6140 W CURTISIAN AVE
Project NameST AL'S MOB #6
Customer Number 
ePlanReviewNo
Description
(ST ALPHONSUS MOB #6-BASEMENT)(SLEEP LAB) To finish a 4,554 sq.ft. portion of the 15,665 sq. ft. basement for use as a 'sleep lab' in this medical building per approved plans on file. Work to include construction of interior, non-bearing, non-combustible, fire-resistive walls to create exam and sleep rooms; conference, storage and administration rooms to support the sleep lab testing & treatment facility; to construct a 1-hour rated exit corridor between stair enclosures; suspended ceiling grid system, electrical, mechanical, plumbing, fire supression & alarm system installation and or upgrade to meet tenant needs and to comply with current adopted codes and ordinances. PC#-02-212/drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Fee Review-notes7/23/20037/23/20037/23/2003 DONE
Additional values from subcontractors.
Permanent occupancy  11/4/2002 DONE
Perm. Occ. Cert. #9428 issued 11-4-02 to St. Al's MOB #6, Sleep Lab.
BLD-Final9/25/20029/26/20029/26/2002PPASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 09/25/2002 at 11:38:52. Contact: ###-####.
Permanent Occupancy 9/26/20029/26/2002 DONE
Details
FIRE-Final Inspection9/25/20029/25/20029/25/2002PPASS
DetailsTroy Cobbley
fire life safety finaled 9/25/2002 10:25:41 AM
FIRE-Final Inspection9/24/20029/24/20029/24/2002PFAIL
DetailsTroy Cobbley
the clip in supports for the sprinkler heads still are not clipped onto the t-bar correctly 9/24/2002 9:34:03 AM
BLD-Framing/Rough-in7/15/20027/16/20027/16/2002PPART
DetailsTom Arcoraci
DOUG ###-#### 7/16/2002 12:25:07 PM
BLD-Framing/Rough-in7/8/20027/9/20027/9/2002APART
DetailsRuss Owen
doug- ###-#### r/i Ok to rock 1 side only. 7/9/2002 1:14:45 PM
Issue PAID IN FULL permit  6/18/2002 DONE
Routing - PLAN CHECK6/17/20026/17/20026/17/2002 PASS
Attached mechanical engineers & architect response & new plan sheets to original submittals and routed to permit desk to issue. Approved as noted and per attached plan review comments of reviewing agencies as part of the approved plans.
PLANS/APPL TAKEN TO FRONT DESK  6/17/2002 PASS
To permit desk to issue.
Print Occupancy Form  6/17/2002 DONE
Inspection Record Card- Bld  6/17/2002 DONE
Telephone call  6/17/2002 DONE
permit ready and fees due
Plan assigned to (DRS)4/9/2002 6/17/2002 PASS
DetailsDan Stuart
6/17/2002 14:01:07 DRS - activity updated through activity BLDA022 from case BLD02-00745.
Plan resubmittals received  6/17/2002 DONE
Received 8-1/2" x 11" detail sheet from Bob Ticker, mechanical engineer indicating compliance with section 410 UBC for medical gas room with 1-hour wall & 1-hour door plus ventilation per code. attached to plans with note to inspector to verify.
Telephone call  6/14/2002 DONE
Called Sam burrows, architect, to find out if he had copy of the original shell & core sheet that shows the medical gas room. Sam will look at his plans and provide copies or have mechanical engineer do so.
Plan resubmittals received  6/11/2002 DONE
Received two copies of revised sheets A-2 & A-4, two Mech. review comment responses for items 4,5,6, & 7 and two copies of electrical review comment responses for items 9, 9 & 10. Routed to Dan S. kmm
Telephone call  5/31/2002 DONE
Call to LCA to talk with Sam Burrows concerning plan deficiencies. Sam out of office until Monday, June 3.
Routing - PLAN CHECK5/23/2002 5/31/2002 FAIL
Resubmittals presented on 5/30/02 addressed only plan review comment #! in a satisfactory manner. Conditions #2 & #3 were only partially addressed. Walls were relocated to meet clear floor space requirements of accessibility but the original wall & fixture locations were left on the plan with the new walls, etc. drawn over the existing. Original dimensions that were wron originally were left on the plans without corrections so the layout & dimensions do not match. The overall plans are incompletely dimensioned within the rooms to provide proper layout to meet the architects and owners intent and to assist in code verification compliance. Conditions #4 thru #10 were not addressed in the resubmittal. Fax to architect stating the deficiencies still outstanding.
Plan resubmittals received  5/30/2002 DONE
Received two copies of revised sheets A-2, A-4. Routed to Dan S. kmm
Routing - PLAN CHECK4/18/2002 5/23/2002 FAIL
Resubmittals required. Copy faxed & mailed to architect.Plans to fire code analyst for review.
Routing - FIRE5/23/2002 5/23/2002 PASS
Plan resubmittals requested  5/23/2002 FAIL
Plan Review Completed(1st rev)  5/23/2002 FAIL
Routing - PLUMBING4/10/2002 4/18/2002 PASS
Routing - PUBLIC WORKS4/9/2002 4/10/2002 PASS
First Notice4/2/20024/2/20024/2/2002 DONE
Plans ACCEPTED BY PLAN TECH  4/2/2002 DONE
Application received  4/2/2002  
Recd Pcfee & Taken To Pln CK  4/2/2002