Fee Review-notes | 7/29/2003 | 7/29/2003 | 7/29/2003 | | DONE |
|
|
|
|
Permanent occupancy | | | 11/5/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9431 issued 11-5-02 to St. Alphonsus Pharmacy on the 2nd floor.
|
BLD-Final | 11/1/2002 | 11/4/2002 | 11/4/2002 | P | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 11/01/2002 at 10:33:33. Contact: ###-####. ok for perm 11/4/2002 12:54:09 PM
|
Permanent Occupancy | | 11/4/2002 | 11/4/2002 | | DONE |
|
|
|
|
BLD-Conference | 10/29/2002 | 10/30/2002 | 10/30/2002 | A | DONE |
Tom Arcoraci
|
|
|
done by 340 ok for temp occ 10/30/2002 1:22:46 PM
|
BLD-Conference | 10/29/2002 | 10/30/2002 | 10/30/2002 | A | PASS |
Carl Dependahl
|
|
|
w/ mark at site re glazing req's 10/30/02 11:03:48 AM
|
BLD-Final | 10/30/2002 | 10/30/2002 | 10/30/2002 | A | FAIL |
Carl Dependahl
|
|
|
need verify 45 min. glass at door 20234a
|
FIRE-Final Inspection | 10/28/2002 | 10/29/2002 | 10/29/2002 | A | PASS |
Troy Cobbley
|
|
|
fire life/safety and fire sprinklers finaled 10/29/2002 8:47:41 AM
|
BLD-Final | 10/29/2002 | 10/29/2002 | 10/29/2002 | P | CANC |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 10/29/2002 at 08:50:21. Contact: ###-####....reschedule. 10/29/02 4:58:25 PM
|
FIRE-Final Inspection | 10/17/2002 | 10/17/2002 | 10/17/2002 | P | PART |
Troy Cobbley
|
|
|
temporary occupancy was given on the life/safety due to the temp on the fire sprinkler. All items for the life/safety inspection are ok and can be finaled when the fire sprinklers are finaled 10/17/2002 3:41:47 PM
|
Override - Parcel Holds | | | 10/17/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 10/17/2002 | | |
|
|
|
|
FIRE-Final Inspection | 10/9/2002 | 10/11/2002 | 10/11/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide approved door hardware for the restroom and cubicle . Turn exit sign at the east exit 10/11/2002 10:26:35 AM 10/11/2002 10:27:01 AM
|
BLD-Conference | 10/9/2002 | 10/10/2002 | 10/10/2002 | A | PASS |
Tom Arcoraci
|
|
|
###-#### mark needs s rated doors 10/10/2002 10:27:01 AM
|
BLD-Conference | 10/9/2002 | 10/10/2002 | 10/10/2002 | A | PASS |
Tom Arcoraci
|
|
|
###-#### mark needs s rated doors 10/10/2002 10:26:05 AM
|
Override - Parcel Holds | | | 10/9/2002 | | |
|
|
|
|
Override - Parcel Holds | | | 10/9/2002 | | |
|
|
|
|
FIRE-Final Inspection | 9/27/2002 | 9/30/2002 | 9/30/2002 | P | CANC |
Troy Cobbley
|
|
|
contractor told me to cancel the inspection since I can't sign off the fire/life safety without the the fire alarm being done 9/30/2002 3:16:39 PM
|
BLD-Wall cover | 9/3/2002 | 9/4/2002 | 9/4/2002 | P | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 09/03/2002 at 16:34:00. Contact: ###-####...efis covered; add, wires & pods at grid....some missed, walls ok. 9/4/2002 6:19:09 PM
|
BLD-Other | 9/3/2002 | 9/3/2002 | 9/3/2002 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 09/03/2002 at 08:26:32. Contact: ###-####.
|
BLD-Other | 8/16/2002 | 8/19/2002 | 8/19/2002 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 08/16/2002 at 09:50:51. Contact: ###-####.incapsulate efis foam exposed above ceilling/ seal top of wall at smoke bairror/ ada restaroom fire wall ok for cover. 8/19/2002 9:53:10 AM
|
BLD-Framing/Rough-in | 8/13/2002 | 8/13/2002 | 8/13/2002 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/13/2002 at 10:30:06. Contact: ###-####.non bearing walls have been drywall w-o insp appears ok they will need to call for a re-inspection of fire walls above ceiling before tile. 8/13/2002 4:41:57 PM
|
Routing - PLAN CHECK | 6/18/2002 | | 6/18/2002 | | PASS |
|
|
|
Approved as noted and attached plan review comments, all a part of the approved plans.
To permit desk to issue.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/18/2002 | | PASS |
|
|
|
Ready to issue.
|
Print Occupancy Form | | | 6/18/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/18/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/18/2002 | | DONE |
|
|
|
permit ready and fees due
|
Issue PAID IN FULL permit | | | 6/18/2002 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 5/24/2002 | | 6/18/2002 | | PASS |
Dan Stuart
|
|
|
6/18/2002 07:35:55 DRS - activity updated through activity BLDA022 from case BLD02-01256.
|
Routing - FIRE | 6/12/2002 | | 6/17/2002 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 6/17/2002 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 6/6/2002 | | 6/12/2002 | | PEND |
|
|
|
No correction required. routing plans to fire code analyst for review.
|
Routing - PLUMBING | 5/31/2002 | | 6/6/2002 | | PASS |
|
|
|
additional cross connection protection may be required
|
Routing - PUBLIC WORKS | 5/24/2002 | | 5/31/2002 | | PASS |
|
|
|
|
First Notice | 5/22/2002 | 5/22/2002 | 5/22/2002 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 5/22/2002 | | DONE |
|
|
|
|
Application received | | | 5/22/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 5/22/2002 | | DONE |
|
|
|
|