Fee Review-notes | 7/29/2003 | 7/29/2003 | 7/29/2003 | | DONE |
|
|
|
Additional values from subcontractors.
|
Permanent Occupancy | | 7/24/2002 | 7/24/2002 | | DONE |
|
|
|
|
BLD-Final | 7/23/2002 | 7/24/2002 | 7/24/2002 | P | PASS |
Russ Owen
|
|
|
dennis; Phone #: ###-####ok perm oc. 7/24/2002 2:18:58 PM
|
FIRE-Final Inspection | 7/24/2002 | 7/24/2002 | 7/24/2002 | P | PASS |
Troy Cobbley
|
|
|
fire life/safety finaled
|
Print Occupancy Form | | | 7/24/2002 | | DONE |
|
|
|
|
Permanent occupancy | | | 7/24/2002 | | DONE |
|
|
|
Perm. Occ. Cert. #9273 issued 7-24-02 to Tuesday Morning.
|
FIRE-Final Inspection | 7/23/2002 | 7/23/2002 | 7/23/2002 | P | FAIL |
Troy Cobbley
|
|
|
replace the door hardware with approved type on doors between retail and stockroom 7/23/2002 3:30:20 PM
|
BLD-Final | 7/23/2002 | 7/23/2002 | 7/23/2002 | P | FAIL |
Russ Owen
|
|
|
dennis. need unisex signage on restrooms as per plans , remove shelving from rest room for 5 foot clearance, and secure shelving to walls. also needs fire insp. 7/23/2002 1:27:02 PM
|
FIRE-Conference | 7/2/2002 | 7/2/2002 | 7/2/2002 | P | PASS |
Troy Cobbley
|
|
|
insulation is now attached to deck 7/2/2002 3:50:05 PM
|
BLD-Framing/Rough-in | 6/27/2002 | 6/27/2002 | 6/27/2002 | P | PASS |
Jim Sly
|
|
|
DENNIS ###-####
|
Routing - PLAN CHECK | 6/13/2002 | | 6/14/2002 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/14/2002 | | PASS |
|
|
|
|
Print Occupancy Form | | | 6/14/2002 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 6/14/2002 | | DONE |
|
|
|
|
Telephone call | | | 6/14/2002 | | DONE |
|
|
|
LEFT MESSAAGE FOR SCOTT MARTIN PERMIT READY AND FEES DUE
|
Issue PAID IN FULL permit | | | 6/14/2002 | | |
|
|
|
|
Plan assigned to (R_H) | 6/6/2002 | | 6/14/2002 | | PASS |
|
|
|
6/14/2002 08:28:31 RMH - activity updated through activity BLDA022 from case BLD02-01365.
|
Routing - FIRE | 6/11/2002 | | 6/13/2002 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 6/13/2002 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 6/7/2002 | | 6/11/2002 | | PEND |
|
|
|
|
Plan Reviewer's activity | | | 6/11/2002 | | PEND |
|
|
|
No corrections required routed plans to the fire department, 6/11/02, Permit pending fire departments approval.
|
Routing - PUBLIC WORKS | 6/6/2002 | | 6/7/2002 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 6/5/2002 | | DONE |
|
|
|
|
First Notice | 6/4/2002 | 6/4/2002 | 6/4/2002 | | DONE |
|
|
|
|
Application received | | | 6/4/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/4/2002 | | DONE |
|
|
|
|