Permit Information
Permit NumberBLD02-02435
StatusFinaled
Name LITHIA MOTORS
Site Address 8853 W FAIRVIEW AVE
Project NameLITHIA MOTORS INC
Customer Number 
ePlanReviewNo
Description
Lithia Ford Automobile Sales and Service Building * To remodel and finish an existing 53,875 square foot, one story CMU shell building to create a new service and parts storage areas. This work also includes the construction of a new 2,605 square foot mezzanine within the General Service Area. the permit is also to construct a new 28,665 square foot, two story addition at the west side of the existing building. This area is for Service, Showroom and Admistrative Office areas. There is a two-hour area separation wall between the existing building and new addition. This building is fully fire sprinklered. The sprinklers are used for area increase. All construction per the approved plans and attached comment list. DRH02-00069/CUP02-00056/644-02/JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Fee Review-notes10/2/200210/2/20028/10/2004 DONE
MISC ACTIONS  11/6/2003 DONE
88.20 additional fees due for 2 hr after hour inspections
First Notice 10/22/200310/22/2003 DONE
Permanent occupancy  10/22/2003 DONE
Perm. Occ. Cert. # 9849 issued 10-22-03 to Lithia Motors.
BLD-Final10/20/200310/21/200310/21/2003APASS
DetailsRuss Owen
Dennis; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Ok perm oc. 10/20/2003 6:00:02 PM
BLD-Final10/8/200310/8/200310/8/2003PFAIL
DetailsRuss Owen
Dennis, ###-#### - please call 1st so he can meet you there! Still has corrections not completed from prior c/n. 10/8/2003 5:00:34 PM
FIRE-Final Inspection10/6/200310/6/200310/6/2003APASS
DetailsRick Jackson
Code Occupancy Approval10/3/200310/3/200310/3/2003APASS
DetailsWm. Michael Meloy
Compliance met. 10/3/2003 12:21:47 PM
FIRE-Final Inspection10/1/200310/2/200310/2/2003AFAIL
DetailsRick Jackson
dennis; Phone #: ###-#### Internet Inspection Request from: Darla Downs need"Fire lane no parking" on red curbing; page 2 of sprinkler certificates 10/2/2003 11:20:17 AM
FIRE-Final Inspection9/30/200310/1/200310/1/2003ANR
DetailsRick Jackson
dennis--; Phone #: ###-#### Internet Inspection Request from: Marsha Smyliem rescheduled for 10/2 10/1/2003 3:54:01 PM
FIRE-Final Inspection7/21/20037/22/20037/22/2003AFAIL
DetailsTroy Cobbley
dennis; Phone #: ###-#### Inspection was actually a conference for fire dept access. I met with the superintendant and marked on the city approved plans the curbing that needed painting and locations for signage at the entrance to the property. I also spoke with Dennis on the phone about the fire hydrant off the south east corner of the main dealership building needing to be turned so the 4" barrell faces the parking lot 7/22/2003 11:02:21 AM
Temporary occupancy  7/21/2003 DONE
Temp. Occ. Cert. #4973 issued 7-21-03 to Lithia Motors.
BLD-Final7/17/20037/18/20037/18/2003ANR
DetailsRuss Owen
late morning dennis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore (contractor called not ready. 7/18/2003 12:08:45 PM
FIRE-Sprinkler Rough-in7/18/20037/18/20037/18/2003PFAIL
DetailsTroy Cobbley
This inspection was apparently for life safety. The only items inspected was the emergency lights and exit signs. No other items looked at 7/18/2003 6:10:03 PM
BLD-Final7/18/20037/18/20037/18/2003PPART
DetailsRuss Owen
would be ok for a temp oc pending life safety inspection. c/n posted by me for other items.7/18/2003 5:37:17 PM 7/18/2003 5:37:33 PM
FIRE-Final Inspection7/15/20037/16/20037/16/2003AFAIL
DetailsRick Jackson
need to complete fire alarms; see alarm permit corrections; overhead door didn't release with detectors; need to test emergency and exit lighting; door hardware from show room not openable from the inside without special knowledge; fusiblelinks painted on overhead doors; need sign on riser/FACP door 7/16/2003 11:26:10 AM
Code Occupancy Approval Temp  7/16/2003 DONE
LOOKS REAL GOOD BUT NEEDS PARKING STRIPPING, THIS IS BEING DONE NOW SO I SIGNED TEMP WITHOUT BOND AND WILL RECHECK FRIDAY TO MAKE SURE THIS IS DONE.
BLD-Other7/14/20037/15/20037/15/2003APART
DetailsRuss Owen
restroom round lights and 2 small rooms at south not complete rest ok. 7/15/2003 10:08:34 AM
BLD-Other7/11/20037/14/20037/14/2003APART
DetailsRuss Owen
ok except some lower floor areas not complete at south side, also restrooms need can lights tied.. 7/14/2003 12:02:30 PM
BLD-Framing/Rough-in7/11/20037/11/20037/11/2003PPART
DetailsRuss Owen
dennis ceiling grid; Phone #: ###-#### Internet Inspection Request from: Barbara Moore. ok need some light at lower floor area to the waiting areas and support for lights in all rest rooms. 7/11/2003 3:20:08 PM
BLD-Framing/Rough-in6/25/20036/25/20036/25/2003APART
DetailsRuss Owen
still needs 1 rated exp joint6/25/2003 11:00:20 AM 6/25/2003 11:00:42 AM
BLD-Framing/Rough-in6/24/20036/24/20036/24/2003PCANC
DetailsRuss Owen
dennis; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD-Framing/Rough-in6/16/20036/17/20036/17/2003APART
DetailsRuss Owen
went over 2 hr wal still inprogress and needs the 1 hr epansion joint completed also noted with contractor that the cut in the cmu for the roll up door at the 2hr fire wall did not indicate any details for support, the engineer is addressing this. 6/18/2003 1:52:35 PM
BLD-Conference6/16/20036/16/20036/16/2003PPART
DetailsRuss Owen
stoped by to check progrees talked with job supper will need to return at am to meet with fraing contractor. 6/16/2003 5:39:28 PM
FIRE-Conference6/11/20036/11/20036/11/2003PDONE
DetailsTroy Cobbley
oil storage tank venting, John ###-#### I met with John with Debest plumbing and telephone conference with sam. There are no code requirements found for venting of the oil storage tanks to the outside of the facility. I did refer the contractor to the UFC 7902 minimum requirements for venting of any storage tank. 6/11/2003 2:29:38 PM
BLD-Framing/Rough-in6/4/20036/4/20036/4/2003PPART
DetailsRuss Owen
DENNIS; Phone #: ###-#### Internet Inspection Request from: Darla DownsPosted a c/n to fire caulk and put in rated control joit at 1 hr to 2 hr wall. 6/4/2003 5:07:32 PM
BLD-Framing/Rough-in5/27/20035/28/20035/28/2003APART
DetailsRuss Owen
2nd floor ok pending fire stoping of plumbing in floor of restrooms and , also posted a c/n for columns in 2hr walls. 5/29/2003 12:49:18 PM
BLD-Framing/Rough-in5/27/20035/27/20035/27/2003PPART
DetailsRuss Owen
DENNIS; Phone #: ###-#### Internet Inspection Request from: Darla Downs. Unable to locate framer will try am inspedction talked with contractor on phone, note a fire stop a the 2nd floor hvac would be required. 5/27/2003 5:25:08 PM
BLD-Framing/Rough-in5/13/20035/14/20035/14/2003APART
DetailsRuss Owen
dennis; Phone #: ###-#### Internet Inspection Request from: Barbara MooreLower floor area A ok left a c/n for the mechanical runing up 2nd floor to provide a 1 hr shaft etc. 5/14/2003 1:22:21 PM
BLD-Framing/Rough-in5/6/20035/6/20035/6/2003PPART
DetailsRuss Owen
dennis; Phone #: ###-#### Internet Inspection Request from: Annette Moore. need detail for parapet. 5/7/2003 5:02:44 PM
BLD-Framing/Rough-in4/21/20034/22/20034/22/2003APART
DetailsRuss Owen
dennis; Phone #: ###-#### Internet Inspection Request from: Annette Moore. areas ok for drywall have been marked in the trailer office. 4/22/2003 5:06:53 PM
BLD-Framing/Rough-in4/9/20034/10/20034/10/2003APART
DetailsJim Sly
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung Misc. 1HR walls highlighted and initialed on plan. 4/10/2003 12:10:41 PM
BLD-Framing/Rough-in3/26/20033/26/20033/26/2003PFAIL
DetailsRuss Owen
DENNIS; Phone #: ###-#### Internet Inspection Request from: Darla Downsc/n on site. 3/27/2003 12:10:51 PM
BLD-Footing1/9/20031/10/20031/10/2003APART
DetailsRuss Owen
dennis ###-#### ` 1/10/2003 4:53:16 PM MTI will perform special inspection. 1/10/2003 4:53:37 PM
BLD-Footing1/8/20031/9/20031/9/2003ACANC
DetailsRuss Owen
dennis- ###-####
Override - Parcel Holds  1/9/2003  
Print Occupancy Form  1/8/2003 DONE
Override - Parcel Holds  1/8/2003  
Inspection Record Card- Bld  1/8/2003 DONE
Telephone call  1/8/2003 DONE
permit ready and need ACHD
Override - Parcel Holds  1/8/2003  
Inspection Record Card- Bld  1/8/2003 DONE
Override - Parcel Holds  1/8/2003  
Issue PAID IN FULL permit  1/8/2003 DONE
(F) Reprint permit  1/8/2003 DONE
Override - Parcel Holds  1/8/2003  
Plan assigned to (JCM)10/3/2002 1/7/2003 PASS
DetailsJohn Menard
1/7/2003 15:55:45 JCM - activity updated through activity BLDA022 from case BLD02-02435.
Routing - PUBLIC WORKS1/2/2003 1/7/2003 PASS
Routing - PLANNING1/7/2003 1/7/2003 PASS
Approved per DRH02-69 (MGS). Signature from CU approved by Mark Pecchenino.
Routing - PLAN CHECK1/7/2003 1/7/2003 PASS
PLANS/APPL TAKEN TO FRONT DESK  1/7/2003 PASS
Routing - FIRE1/2/2003 1/2/2003 PASS
Routing - FIRE12/30/2002 12/30/2002 FAIL
indoor storage of diesel is in excess of quantity limits
Routing Off Site - STRUCTURAL12/6/2002 12/23/2002 PASS
routed revised drawings and calculations of 12/6/02 to outside eng. kmm
Routing - PLANNING Land Div12/17/2002 12/17/2002 PASS
Approval to proceed on existing building with understanding that Nampa-Meridian Irrigation easement is being ratified and a new deed will be recorded that describes the entire parcel prior to issuing a Certificate of Occupancy.
Routing - PLAN CHECK12/2/2002 12/17/2002  
Plan resubmittals received  12/6/2002 DONE
Received three copies of revised sheets S0.1, S1.1, S1.2, S1.3, S1.4, S2.1, S2.2, S3.1, S3.2, S3.3, S4.1, S4.2, S4.3. Three copies of struct. design calculations and one copy of response letter. Routed one copy to outside eng. and routed two copies to John M. kmm
Routing - PUBLIC WORKS11/27/2002 12/2/2002 FAIL
send to public works to Bill Colson.
Requires street light plan per Bill Colson
Routing - PLAN CHECK11/19/2002 11/27/2002 PASS
Plan Reviewer's activity  11/27/2002 PASS
Reviewed and approved resubmitted plan sheets and specifications. JCM
Plan resubmittals received  11/25/2002 DONE
Received three copies of resubmittal sheet E1.0 with transmittal letter for Bill Colson. Routed to John Menard.
Plan resubmittals received  11/21/2002 DONE
Received two copies of revised sheets A2.2, A3.1, A5.1, A5.2, A7.1, A10.1, C1.8, one copy plan review response letter and attachments. Routed to John M. kmm
Routing - FIRE11/13/2002 11/19/2002 FAIL
Plan Review Completed(1st rev)  11/19/2002 FAIL
Routing - PLAN CHECK10/30/2002 11/13/2002 FAIL
Plan resubmittals requested  11/13/2002 FAIL
Mailed the architect of record a copy of the plan review comment list requesting revisions. JCM
Plan resubmittals requested  11/4/2002  
Faxed the architect of record a copy of the comment list from the consulting structural engineer requesting revisions. JCM
Routing Off Site - STRUCTURAL10/3/2002 11/1/2002 FAIL
Contacted PDQ to take plans to outside eng. kmm Received comment list from the consulting structural engineer requesting revisions. JCM
Routing - PLUMBING10/25/2002 10/30/2002 PASS
CLEANOUTS REQUIRED ON THE STORM SEWER MAINS OUTSIDE EVERY 100", UPSTREAM INTERCEPTOR CHAMBER VENT MUST GO THRU THE ROOF BY ITSELF, PROVIDE A SAMPLE PORT DOWNSTREAM OF INTERCEPTOR, USE NO SWEEP FITTING TO PROVIDE ACCESS FOR EQUIPMENT, USE BOISE CITY APPROVED INTERCEPTOR DETAIL, ATTACHED, ADDITIONAL CROSS CONNECTION PRETECTION MAY BE REQUIRED, NO ABS DRAINAGE SHALL BE INSTALLED IN THE GREASE LINE.
Routing - PLANNING10/17/2002 10/25/2002 PEND
Approved per CUP02-00056, routed to Design Review 10/22/02.

Design Review conditions not met; please refer to DRH02-69 action letter, dated June 13, 2002.
Routing - Erosion and Sediment10/15/2002 10/17/2002 PASS
ESC Plan passed on Bld02-02121
Routing - PUBLIC WORKS10/8/2002 10/15/2002 FAIL
Requires street light plan per Bill Colson. kmm
Routing - PLANNING Land Div10/7/2002 10/8/2002 FAIL
Need recorded deed with description of perimeter. Need new tax parcel #. Need to vacate 60' easment for Nampa-Meridian Irrigation Easement for Welch Drain as shown on ROS 3881. Called Mike Dahlberg of CSHQA on 10/8/02. David Abo
Plan routing begun/NEW & ADDTN  10/7/2002  
Plans ACCEPTED BY PLAN TECH  10/7/2002 DONE
Received civil, landscape and esc plans marked for refrence only. Put with plans to start routing. Grading and drainage permit under Bld02-02121. Erosion and Sediment under ESC02-00407. kmm
Plans ACCEPTED BY PLAN TECH  10/3/2002 PEND
Waiting for Civil, landscape, site and esc plans. Contacted Jim Otradosky of this need. kmm
Application received  10/2/2002  
Recd Pcfee & Taken To Pln CK  10/2/2002 DONE