Case Summary (BLD) | | | 8/7/2015 | | |
|
|
|
|
Fee Review-notes | 10/22/2002 | 10/22/2002 | 8/10/2004 | | DONE |
|
|
|
|
BLD-Aging Inspection | 6/9/2004 | 6/9/2004 | 6/9/2004 | | PASS |
Dave Hannah
|
|
|
|
DOC - Permit Finaled | 6/9/2004 | 6/9/2004 | 6/9/2004 | A | PASS |
Dave Hannah
|
|
|
Finaled by inspector at 6/9/2004 8:16:16 AM
|
BLD-Aging Inspection | 3/30/2004 | 3/30/2004 | 3/30/2004 | | PASS |
Dave Hannah
|
|
|
|
Letter of compliance | | | 11/4/2003 | | DONE |
|
|
|
Letter of Compliance # 24320 issued 11-4-03.
|
BLD-Final | 8/14/2003 | 8/14/2003 | 8/14/2003 | A | PASS |
Dave Hannah
|
|
|
|
FIRE-Final Inspection | 8/12/2003 | 8/13/2003 | 8/13/2003 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/12/2003 at 1:11:56 PM. Contact: ###-####.
|
FIRE-Final Inspection | 8/8/2003 | 8/8/2003 | 8/8/2003 | P | FAIL |
Rick Jackson
|
|
|
checked all smoke control system doors; there are numerous doors not latching or missing smoke seals; they are identified on the approved plans 8/8/2003 3:02:06 PM
|
BLD-Aging Inspection | 7/21/2003 | 7/21/2003 | 7/21/2003 | | PASS |
Dave Hannah
|
|
|
work in progress 7/21/2003 9:08:51 AM
|
BLD-Aging Inspection | 5/20/2003 | 5/20/2003 | 5/20/2003 | | DONE |
Dave Hannah
|
|
|
work in progress 5/20/2003 8:31:01 AM
|
BLD-Aging Inspection | 3/17/2003 | 3/17/2003 | 3/17/2003 | | DONE |
Dave Hannah
|
|
|
|
Issue PAID IN FULL permit | | | 12/16/2002 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 12/9/2002 | | 12/12/2002 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/12/2002 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 12/12/2002 | | DONE |
|
|
|
|
Telephone call | | | 12/12/2002 | | DONE |
|
|
|
PERMIT READY AND FEES DUE
|
Plan assigned to (CJW) | 10/24/2002 | | 12/12/2002 | | PASS |
Carl Westfall
|
|
|
12/12/2002 08:12:04 CJW - activity updated through activity BLDA022 from case BLD02-02584.
|
Routing - FIRE | 12/5/2002 | | 12/9/2002 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 12/9/2002 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 10/24/2002 | | 12/5/2002 | | PASS |
|
|
|
(11-13-02) UBC plan review started November 5, 2002 and finished November 13, 2002. A response was required. See the conditions report. Waiting for the designer's response before routing drawings to Fire. (12-05-02) Resubmitted drawings reviewed and approved with conditions. See the conditions list. Drawings routed to the Fire Department.
|
Plan resubmittals received | | | 12/4/2002 | | DONE |
|
|
|
Received two copies of revised sheets M-00 M-0 M-1 M-2 M-3 M-4 M-5 M-6 M-7 M-8 M-9 E-0 E-1 E-2 E-3 E-4 E-5 E-6 A-4. Routed to Carl W. kmm
|
Meeting | | | 12/4/2002 | | DONE |
|
|
|
Met with Mr. Cardinale and Mr. Holley and accepted their resubmittal.
|
Meeting | | | 11/13/2002 | | DONE |
|
|
|
Met with Larry Cardinale and went over report. He will respond after consultation with the Mechanical Engineer and his superiors.
|
Plans ACCEPTED BY PLAN TECH | | | 10/22/2002 | | DONE |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 10/22/2002 | | DONE |
|
|
|
|
Application received | | | 10/21/2002 | | |
|
|
|
|