BLD-Final | 12/8/2003 | 12/8/2003 | 12/8/2003 | P | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 12/8/2003 at 10:35:30 AM. Contact: ###-####. OK for Perm Occ. :) 12/8/2003 4:17:53 PM
|
First Notice | | 12/8/2003 | 12/8/2003 | | DONE |
|
|
|
|
Permanent Occupancy | | 12/8/2003 | 12/8/2003 | | DONE |
|
|
|
|
Permanent occupancy | | | 12/8/2003 | | DONE |
|
|
|
Perm. Occ. Cert. # 9897 issued 12-8-03 to the Aspen Springs Apts.
|
FIRE-Final Inspection | 11/26/2003 | 11/26/2003 | 11/26/2003 | P | PASS |
Troy Cobbley
|
|
|
fire life safety and fire alarm finaled
|
FIRE-Final Inspection | 11/24/2003 | 11/24/2003 | 11/24/2003 | P | PART |
Troy Cobbley
|
|
|
A temp occupancy was given until adequate batteries are provided for the Nac panel. All other life safety items are ok
|
Code Occupancy Approval | | | 11/20/2003 | | PASS |
|
|
|
|
BLD-Wall cover | 8/28/2003 | 8/29/2003 | 8/29/2003 | A | PASS |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 8/28/2003 at 4:35:23 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 8/25/2003 | 8/26/2003 | 8/26/2003 | A | PART |
Steven Webb
|
|
|
Scheduled by a contractor via Hello! on 8/25/2003 at 11:52:53 AM. Contact: ###-####. C/N Ok to insulate. 8/26/2003 10:37:52 AM
|
BLD-Wall cover | 8/20/2003 | 8/20/2003 | 8/20/2003 | A | PART |
Russ Owen
|
|
|
ok to side 8/26/2003 9:58:15 AM
|
BLD-Framing/Rough-in | 7/29/2003 | 7/30/2003 | 7/30/2003 | P | PART |
Russ Owen
|
|
|
###-#### Ok some areas painted in green 7/30/2003 4:57:22 PM
|
Override - Parcel Holds | | | 7/29/2003 | | |
|
|
|
|
BLD-Framing/Rough-in | 7/25/2003 | 7/28/2003 | 7/28/2003 | A | CANC |
Russ Owen
|
|
|
###-#### vincent
|
Override - Parcel Holds | | | 7/25/2003 | | |
|
|
|
|
BLD-Framing/Rough-in | 7/21/2003 | 7/22/2003 | 7/22/2003 | P | CANC |
Russ Owen
|
|
|
###-####. wrong permit number. 7/25/2003 9:26:13 AM
|
Override - Parcel Holds | | | 7/21/2003 | | |
|
|
|
|
Inspection Record Card- Bld | | | 4/16/2003 | | |
|
|
|
|
Print Occupancy Form | | | 4/16/2003 | | |
|
|
|
|
Case Summary (BLD) | | | 3/31/2003 | | |
|
|
|
|
BLD-Foundation | 3/4/2003 | 3/5/2003 | 3/5/2003 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 3/4/2003 at 4:49:30 PM. Contact: ###-####.
|
BLD-Footing | 2/25/2003 | 2/26/2003 | 2/26/2003 | P | PASS |
Jim Sly
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
Issue PAID IN FULL permit | | | 12/10/2002 | | |
|
|
|
|
Inspection Record Card- Bld | | | 11/22/2002 | | |
|
|
|
|
Print Occupancy Form | | | 11/22/2002 | | DONE |
|
|
|
|
Plan assigned to (M_P) | 11/6/2002 | | 11/15/2002 | | PASS |
Mike Phillips
|
|
|
11/15/2002 11:21:51 M_P - activity updated through activity BLDA022 from case BLD02-01063.
|
Routing - PLAN CHECK | 11/14/2002 | | 11/15/2002 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/15/2002 | | DONE |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 11/15/2002 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 11/15/2002 | | DONE |
|
|
|
|
Routing - FIRE | 11/14/2002 | | 11/14/2002 | | PASS |
Bill Alexander
|
|
|
|
Routing - FIRE | 11/6/2002 | | 11/8/2002 | | FAIL |
Bill Alexander
|
|
|
Hydrant locations have problems with obstructions (carports, parking) and need updated due to FD access modifications. Water supply is questionable due to the location of certificate. Fire loop is found to be 4" and minimum allowed is 6".
|
Plan Review Completed(1st rev) | | | 11/8/2002 | | DONE |
|
|
|
|
Application received | | | 11/6/2002 | | |
|
|
|
|
Routing - PLAN CHECK | 11/6/2002 | | 11/6/2002 | | PEND |
|
|
|
Routing to fire.
|