BLD-Aging Inspection | 6/22/2006 | 6/22/2006 | 6/22/2006 | | PASS |
Dave Hannah
|
|
|
|
DOC - Permit Expired | 6/22/2006 | 6/22/2006 | 6/22/2006 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Final | 4/10/2006 | 4/11/2006 | 4/11/2006 | A | PASS |
Dave Hannah
|
|
|
rock; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for perm occ
|
BLD-Final | 4/10/2006 | 4/10/2006 | 4/11/2006 | P | DEFR |
Dave Hannah
|
|
|
rock; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
FIRE-Final Inspection | 4/7/2006 | 4/10/2006 | 4/10/2006 | A | PASS |
Forrest France
|
|
|
Outstanding items have been completed, fire life safety inspection passed.
|
BLD-Aging Inspection | 4/4/2006 | 4/4/2006 | 4/6/2006 | | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 1/5/2006 | 1/5/2006 | 1/5/2006 | | PASS |
Dave Hannah
|
|
|
|
BLD-Final | 9/27/2005 | 9/28/2005 | 9/28/2005 | A | FAIL |
Dave Hannah
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa needs smoke seal and closer addjusted on ltly room
|
BLD-Aging Inspection | 9/27/2005 | 9/27/2005 | 9/27/2005 | | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 7/28/2005 | 7/28/2005 | 7/28/2005 | | PASS |
Dave Hannah
|
|
|
|
BLD-Final | 4/28/2005 | 4/28/2005 | 4/28/2005 | P | FAIL |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 4/28/2005 at 7:37:19 AM. Contact: ###-####. needs smoke seal on fire doors
|
BLD-Aging Inspection | 4/20/2005 | 4/20/2005 | 4/20/2005 | | PASS |
Dave Hannah
|
|
|
|
BLD-Conference | 4/20/2005 | 4/20/2005 | 4/20/2005 | A | DONE |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 9/14/2004 | 9/14/2004 | 9/14/2004 | | PASS |
Dave Hannah
|
|
|
|
BLD-Aging Inspection | 7/12/2004 | 7/12/2004 | 7/12/2004 | | PASS |
Dave Hannah
|
|
|
wip 7/12/2004 8:37:16 AM
|
FIRE-Final Inspection | 5/6/2004 | 5/6/2004 | 5/6/2004 | A | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 5/6/2004 at 7:06:34 AM. Contact: ###-####. Received call from Mike and he said the sprinkler plans are being resubmitted due to changes 5/6/2004 11:25:34 AM
|
BLD-Aging Inspection | 4/1/2004 | 4/1/2004 | 4/1/2004 | | DONE |
Dave Hannah
|
|
|
|
FIRE-Conference | 1/20/2004 | 1/20/2004 | 1/20/2004 | A | PART |
Rick Jackson
|
|
|
met with Jason and the sprinklers will be on the 2 east sprinkler zone for alarm notification
|
BLD-Framing/Rough-in | 9/19/2003 | 9/22/2003 | 9/22/2003 | A | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 9/19/2003 at 1:05:10 PM. Contact: ###-####. ok to cover walls 9/22/2003 12:18:11 PM
|
BLD-Framing/Rough-in | 9/22/2003 | 9/22/2003 | 9/22/2003 | P | DONE |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 9/19/2003 at 1:05:10 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 9/19/2003 | 9/19/2003 | 9/19/2003 | P | CANC |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 9/19/2003 at 8:19:23 AM. Contact: ###-####.
|
BLD-Framing/Rough-in | 9/16/2003 | 9/17/2003 | 9/17/2003 | P | FAIL |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 3:09:51 PM. Contact: ###-####. need to complete all fire stopping 9/17/2003 3:35:30 PM
|
BLD-Final | 8/7/2003 | 8/7/2003 | 8/7/2003 | A | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 8/7/2003 at 7:07:15 AM. Contact: ###-####.
|
BLD-Conference | 8/7/2003 | 8/7/2003 | 8/7/2003 | P | PASS |
Carl Dependahl
|
|
|
need partial final for use of triage area, ok 8/7/2003 4:21:32 PM
|
BLD-Final | 8/7/2003 | 8/7/2003 | 8/7/2003 | P | PART |
Carl Dependahl
|
|
|
This phase ok for use, walls patched/ firestopped ok 8/7/2003 5:08:55 PM
|
FIRE-Final Inspection | 8/6/2003 | 8/6/2003 | 8/6/2003 | P | PART |
Rick Jackson
|
|
|
data entry and soiled linen area to west aren't completed as part of this phase; alarms and sprinklers are okay for this phase 8/6/2003 12:37:29 PM
|
FIRE-Final Inspection | 8/1/2003 | 8/1/2003 | 8/1/2003 | P | FAIL |
Rick Jackson
|
|
|
need smoke seal and door hardware on 1 hr clean linen room 8/1/2003 2:20:00 PM
|
BLD-Framing/Rough-in | 7/18/2003 | 7/18/2003 | 7/18/2003 | A | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 7/18/2003 at 6:54:45 AM. Contact: ###-####.
|
BLD-Framing/Rough-in | 7/18/2003 | 7/18/2003 | 7/18/2003 | A | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 7/18/2003 at 6:54:45 AM. Contact: ###-####....clg ok 7/18/2003 4:31:23 PM
|
BLD-Framing/Rough-in | 7/15/2003 | 7/15/2003 | 7/15/2003 | P | FAIL |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 7/15/2003 at 8:38:16 AM. Contact: ###-####...c/n firestops, etc. 7/15/2003 5:16:45 PM
|
BLD-Aging Inspection | 5/23/2003 | 5/23/2003 | 5/23/2003 | | PASS |
Dave Hannah
|
|
|
work in progress 5/23/2003 9:33:37 AM
|
BLD-Framing/Rough-in | 3/6/2003 | 3/6/2003 | 3/6/2003 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 3/6/2003 at 8:52:37 AM. Contact: ###-####....ok to "1 side" restroom pend plbg ok 3/6/2003 4:35:56 PM
|
BLD-Framing/Rough-in | 3/5/2003 | 3/5/2003 | 3/5/2003 | P | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 3/5/2003 at 10:21:37 AM. Contact: ###-####.
|
Issue & PRINT to be Invoiced | | | 2/4/2003 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 11/22/2002 | | 1/31/2003 | | PASS |
Dan Stuart
|
|
|
1/31/2003 09:59:06 DRS - activity updated through activity BLDA022 from case BLD02-02815.
|
Routing - PLAN CHECK | 1/31/2003 | | 1/31/2003 | | PASS |
|
|
|
Approved as noted on plans and attached plan review comments & architects response attached to the plans as part of the approved plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/31/2003 | | PASS |
|
|
|
To permit desk for issue.
|
Print Occupancy Form | | | 1/31/2003 | | DONE |
|
|
|
|
Telephone call | | | 1/31/2003 | | DONE |
|
|
|
emailed permit ready
|
Plan resubmittals received | | | 1/28/2003 | | DONE |
|
|
|
Received cover letter with architects response & small scale floor plans showing plan modifications for room '2N221' to become open storage room; 2N216 to relocate door to east wall to provide accessibility clearance; and M2 mechanical plan showing additional smoke/fire dampers at smoke barrier and corridor.
|
Plan resubmittals requested | | | 1/21/2003 | | FAIL |
|
|
|
Faxed & mailed copy of remaining corrections needing clarification before the plan review can be completed and plans processed for permit. this is a follow up to a phone call to ZGA on 1/17/03 to discuss unanswered or unclear items not responded to sufficiently in the 1/16/03 response.
|
Routing - PLAN CHECK | 1/14/2003 | | 1/21/2003 | | FAIL |
|
|
|
Three issues still unresolved by architects re-submittals of 1/16/03. Sent fax follow up to phone conversation with ZGA concerning remaining issues needing correction: 1) Reducing accessiblity to existing restroom by installing smaller door; 2) Latch side accessilbity clearance to Soiled Utility Room of 12" due to requirements for closer and latch at rated fire-door; & 3) Clearification as to side of corridor to be used to create the smoke barrier, north or south or both, on sheet G1.0.
|
Plan resubmittals received | | | 1/16/2003 | | DONE |
|
|
|
Received two copies of revised sheetsG0.1, A2.1, A5.1, A8.1, E2.0, E3.0, E4.0, E5.0, P1.0, P2.0, P3.0, M1.0, M2.0, FP1.0, one copy of response review detail 3/A7.3 and one product information letter. Routed to Dan S. kmm
|
Routing - FIRE | 1/7/2003 | | 1/13/2003 | | PASS |
|
|
|
|
Plan Review Completed(1st rev) | | | 1/13/2003 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 11/26/2002 | | 1/7/2003 | | FAIL |
|
|
|
Corrections submitted to architect for response. Routing to fire code analyst.
|
Plan resubmittals requested | | | 1/7/2003 | | FAIL |
|
|
|
Copy of plan review corrections faxed and mailed to architect.
|
Print Pending Permit.LaserJet4 | | | 12/18/2002 | | |
|
|
|
|
Routing - PLUMBING | 11/22/2002 | | 11/26/2002 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 11/22/2002 | | 11/22/2002 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 11/19/2002 | | DONE |
|
|
|
|
Application received | | | 11/18/2002 | | |
|
|
|
|
Fee Review-notes | 11/18/2002 | 11/18/2002 | | | |
|
|
|
|