Fee Review-notes | 12/24/2002 | 12/24/2002 | 8/10/2004 | | DONE |
|
|
|
|
FIRE-Final Inspection | 3/10/2004 | 3/11/2004 | 3/11/2004 | A | PASS |
Rick Jackson
|
|
|
Please call 30 mins prior to inspection///robbie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore fire/life safety okay 3/11/2004 8:33:59 AM
|
First Notice | | 3/11/2004 | 3/11/2004 | | DONE |
|
|
|
|
Permanent Occupancy | | 3/11/2004 | 3/11/2004 | | DONE |
|
|
|
|
Permanent occupancy | | | 3/11/2004 | | DONE |
|
|
|
Perm. Occ. Cert. # 10028 issued 3-11-04 to Kaufman and Kaufman.
|
FIRE-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 | A | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors have been installed but they do not shut down the hvac units when activated 3/10/2004 9:57:06 AM
|
BLD-Framing/Rough-in | 2/10/2004 | 2/12/2004 | 2/12/2004 | A | CANC |
Tom Arcoraci
|
|
|
Robbie; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
FIRE-Final Inspection | 2/10/2004 | 2/12/2004 | 2/12/2004 | A | FAIL |
Troy Cobbley
|
|
|
provide duct smoke detectors for unit shut down on both units 2/12/2004 10:23:23 AM
|
BLD-Final | 2/12/2004 | 2/12/2004 | 2/12/2004 | A | PART |
Tom Arcoraci
|
|
|
ok pending fire final
|
Office Staff conference/action | | | 10/24/2003 | | DONE |
|
|
|
Temp. Occ. Cert. extended thru 11-7-03 per Tim Hogland.
|
BLD-Final | 7/25/2003 | 7/25/2003 | 7/25/2003 | P | NR |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 7/25/2003 at 11:14:25 AM. Contact: ###-####.Went to job card does not have all required signatures. 7/25/2003 3:27:21 PM
|
BLD-Final | 7/25/2003 | 7/25/2003 | 7/25/2003 | P | PART |
Tom Arcoraci
|
|
|
Ok for temp. occ.
|
Temporary occupancy | | | 7/25/2003 | | DONE |
|
|
|
Temp. Occ. Cert. #4977 issued 7-25-03 to Kaufman and Kaufman Insurance.
|
BLD-Final | 7/16/2003 | 7/18/2003 | 7/18/2003 | A | NR |
Tom Arcoraci
|
|
|
###-#### jed
|
FIRE-Final Inspection | 7/16/2003 | 7/17/2003 | 7/17/2003 | P | FAIL |
Troy Cobbley
|
|
|
###-#### jed Provide the second fire hydrant as per plan sheet C1.0. Provide automatic shutdown for the hvac units. Provide "No Parking-Fire Dept. Turn Around" sign on fence between builidings. Provide approved door hardware on doors for access to the common restrooms and conference room 7/17/2003 4:18:41 PM
|
FIRE-Final Inspection | 7/15/2003 | 7/16/2003 | 7/16/2003 | A | FAIL |
Rick Jackson
|
|
|
jed - ###-#### shell permit not signed off; will need address and suite numbers 7/16/2003 8:35:59 AM
|
Print Occupancy Form | | | 7/16/2003 | | DONE |
|
|
|
|
BLD-Framing/Rough-in | 3/27/2003 | 3/27/2003 | 3/27/2003 | P | FAIL |
Tom Arcoraci
|
|
|
Scheduled by a contractor via Hello! on 3/27/2003 at 9:39:21 AM. Contact: ###-####. cn posted ok to insulate walls only 3/27/2003 3:43:08 PM
|
Issue PAID IN FULL permit | | | 2/18/2003 | | DONE |
|
|
|
|
(F) Reprint permit | | | 2/18/2003 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 1/31/2003 | | DONE |
|
|
|
|
Plan assigned to (MLO) | 12/26/2002 | 12/26/2002 | 1/30/2003 | | PASS |
Mike Otto
|
|
|
1/30/2003 09:33:16 MLO - activity updated through activity BLDA022 from case BLD02-03053.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/30/2003 | | DONE |
|
|
|
|
Routing - Erosion and Sediment | 1/23/2003 | | 1/29/2003 | | PASS |
|
|
|
ESC approved with conditions attached to plans.
|
Plan resubmittals received | | | 1/24/2003 | | DONE |
|
|
|
Received two copies of ESC plan and narrative. Put with plans. kmm
|
Routing - PLUMBING | 1/16/2003 | | 1/22/2003 | | PASS |
|
|
|
see shell for review comments
|
Routing - PLAN CHECK | 1/16/2003 | | 1/16/2003 | | PASS |
|
|
|
|
Routing - PLANNING | 1/9/2003 | | 1/10/2003 | | PASS |
|
|
|
Approved per DRH02-00006 Mod #1.
|
Routing - FIRE | 1/8/2003 | | 1/9/2003 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 1/6/2003 | | 1/8/2003 | | PEND |
|
|
|
corrections on shell
|
Routing - PLUMBING | 1/3/2003 | | 1/3/2003 | | FAIL |
|
|
|
your fixture schedule doesn't show the urinals, use the 2000 upc to size the water system, show premise backflow protection, accessable location, show thermol expantion size and location, floor drains will need to be primed.
|
Routing - PLANNING | 1/2/2003 | | 1/2/2003 | | PASS |
|
|
|
Plans do not incorporate DR comments. Anna Powell of B&A Engineers has been notified.
|
Routing - Erosion and Sediment | 12/31/2002 | | 1/2/2003 | | FAIL |
|
|
|
Routed with building permit Bld02-03054
ESC does not meet requirements of BCC8-17 or Plan Designer Manual Appendix A & C.
|
Routing - PLANNING Land Div | 12/31/2002 | | 12/31/2002 | | PASS |
|
|
|
Approved, no land division as per building permit issued on 6013 Overland Avenue.
|
Routing - PUBLIC WORKS | 12/30/2002 | | 12/31/2002 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 12/30/2002 | | 12/30/2002 | | FAIL |
|
|
|
Need to see deed to verify legal land division.
|
Plans ACCEPTED BY PLAN TECH | | | 12/26/2002 | | DONE |
|
|
|
Plans incorporated in with the shell plans Bld02-03054. Okay per John Menard on 12/12/02.
Received (3) sets of plans, (3) extra sets of site civil with grading and drainage, (2) sets of structural calculations, (1) letter from United Water, (1) legal description, (1) O&M (some drainage calculations on plans), and (1) permit application.
|
Application received | | | 12/24/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 12/24/2002 | | DONE |
|
|
|
|