Second Notice BLD | 4/26/2005 | 4/26/2005 | 4/26/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 6/21/2004 | 4/26/2005 | | DONE |
|
|
|
|
Fee Review-notes | 12/30/2002 | 12/30/2002 | 8/10/2004 | | DONE |
|
|
|
|
Permanent occupancy | | | 6/21/2004 | | DONE |
|
|
|
Perm. Occ. Cert. # 10193 issued 6-21-04 to Petersen Staggs Architects.
|
Code Occupancy Approval | 6/24/2004 | 6/18/2004 | 6/18/2004 | P | DONE |
Dena Gambrel
|
|
|
Inspection completed. Signed off. 6/24/2004 12:34:17 PM
|
Permanent Occupancy | | 6/18/2004 | 6/18/2004 | | DONE |
|
|
|
|
BLD-Final | 6/17/2004 | 6/18/2004 | 6/18/2004 | A | PASS |
Tony Young
|
|
|
john- ###-#### for perm occ
perm. occ. ok 6/18/2004 9:43:47 AM
|
Office Staff conference/action | | | 5/17/2004 | | DONE |
|
|
|
Extension letter of temp. occ. issued by Jenifer until June 18, 2004.
|
BLD-Final | 2/17/2004 | 2/19/2004 | 2/19/2004 | A | PART |
Tony Young
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
temp. occ. ok 2/19/2004 12:33:48 PM
|
Temporary occupancy | | | 2/19/2004 | | DONE |
|
|
|
Temp. Occ. Cert. # 5075 issued 2-19-04 to Petersen Staggs Architects.
|
FIRE-Final Inspection | 2/17/2004 | 2/18/2004 | 2/18/2004 | A | PASS |
Troy Cobbley
|
|
|
fire life safety finaled. Structural inspection please verify correct door hardware on the three exterior exits. 2/18/2004 9:34:03 AM
|
FIRE-Final Inspection | 2/17/2004 | 2/17/2004 | 2/17/2004 | P | FAIL |
Troy Cobbley
|
|
|
Need metal sample tubes in return air ducts since they exceed 1 1/2' in width. Third hvac unit that serves the 2nd story needs to have automatic shutdown per UMC since there is no separation between the 1st story and 2nd story systems 2/17/2004 4:00:03 PM
|
PubWorks Occupancy Approval | 2/3/2004 | 2/3/2004 | 2/3/2004 | | DONE |
|
|
|
Drainage project complete, signed permanent occupancy 2/3/04. R.Rokovitz
|
Print Occupancy Form | | | 2/2/2004 | | DONE |
|
|
|
|
BLD-Energy code compliance | 11/10/2003 | 11/12/2003 | 11/12/2003 | A | PART |
Tony Young
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs
commercial project, energy code not reqd. on 2002 permit, no inspection done 11/12/2003 10:25:01 AM
|
BLD-Framing/Rough-in | 11/5/2003 | 11/5/2003 | 11/5/2003 | P | PASS |
Tony Young
|
|
|
John; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD-Framing/Rough-in | 11/3/2003 | 11/4/2003 | 11/4/2003 | A | FAIL |
Tony Young
|
|
|
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
need trades, seal, etc 1st 11/4/2003 10:40:31 AM
|
BLD-Foundation | 6/30/2003 | 7/1/2003 | 7/1/2003 | A | PART |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 6/30/2003 at 3:14:25 PM. Contact: ###-####.
wip, on walls, int. point loads, ok so far 7/1/2003 10:57:52 AM
|
BLD-Footing | 6/26/2003 | 6/27/2003 | 6/27/2003 | A | PASS |
Dave Hannah
|
|
|
DAVE; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
(F) Reprint permit | | | 6/23/2003 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/20/2003 | | |
|
|
|
|
Routing - PLAN CHECK | 5/21/2003 | | 6/16/2003 | | |
|
|
|
|
Routing - PLANNING Land Div | 6/16/2003 | | 6/16/2003 | | PASS |
|
|
|
Approved. Parcels re-combined by warranty deed recorded on 6/10/03. No other building permits for other structures will be issued until Mount Bennett Subdivision is recorded. David Abo, June 16, 2003.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/16/2003 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 6/16/2003 | | 6/16/2003 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 6/16/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/16/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/16/2003 | | DONE |
|
|
|
LEFT MESS THAT PERMIT IS READY
|
Plan assigned to (JCM) | 1/2/2003 | | 6/16/2003 | | PASS |
John Menard
|
|
|
6/16/2003 10:44:58 JCM - activity updated through activity BLDA022 from case BLD02-03088.
|
Routing - PUBLIC WORKS | 5/14/2003 | | 5/21/2003 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 5/21/2003 | | 5/21/2003 | | FAIL |
|
|
|
Building site is proposed Lot 1 in Mount Bennet Subdivision. Final plat approved by City Council on November 12, 2002.
5/21/03 final plat not recorded. kmm
|
Additional plans submitted | | | 5/19/2003 | | |
|
|
|
Received three additional copies of revised civil sheets. Routed to Brian M. to put with plans. kmm
|
Plan resubmittals received | | | 5/14/2003 | | DONE |
|
|
|
Received three copies of revised sheets SD4, SD7 & SD8. Four copies of stormwater management clculations. Routed to John M. kmm
|
Routing - PLANNING | 5/12/2003 | | 5/13/2003 | | PASS |
|
|
|
Approved per DRH02-117.
|
Routing - PLAN CHECK | 4/25/2003 | | 5/12/2003 | | |
|
|
|
|
Plan resubmittals received | | | 5/9/2003 | | DONE |
|
|
|
received response letter, two copies of additional calculations, three copies of S4. routed to John M.
|
Plan Reviewer's activity | | | 5/9/2003 | | PASS |
|
|
|
Reviewed and approved resubmitted plans, including resubmitted structural plans and calculations. JCM
|
Plan resubmittals requested | | | 5/1/2003 | | |
|
|
|
Faxed the architect a copy of the comment list from the consulting structural engineer requesting additional revisions. JCM
|
Plan resubmittals received | | | 5/1/2003 | | DONE |
|
|
|
letter of transmittal, response letter form Peterson Staggs, two sets of A1, A2, A6, A7, A8.1, A10,A12 taken to John M.
|
Routing Off Site - STRUCTURAL | 4/25/2003 | | 4/30/2003 | | FAIL |
|
|
|
Contacted PDQ to take resubs of 4/25/03 to outside engineering. kmm Received comment list from consulting engineer requesting additional revisions to be reviewed by plan reviewer. JCM
|
Routing Off Site - STRUCTURAL | 4/21/2003 | | 4/30/2003 | | FAIL |
|
|
|
Contacted PDQ to take revised sheets of 4/18/03 to outside engineering. kmm
|
Routing - PLANNING | 4/23/2003 | | 4/25/2003 | | FAIL |
|
|
|
Revised landscape plan and site plan have not been submitted. Also no copy of a Cross
Access Agreement has been submitted. Applicant has been notified. It will be required that the vegetation at the bottom of the retention ponds be relocated.
|
Plan resubmittals received | | | 4/24/2003 | | DONE |
|
|
|
Received letter of transmittal and three S-2 and three S-6 and taken to John M.
|
Routing - PLAN CHECK | 1/21/2003 | | 4/23/2003 | | |
|
|
|
|
Plan resubmittals received | | | 4/21/2003 | | DONE |
|
|
|
Received letter of transmittal and S1.1 plan.
|
Plan resubmittals received | | | 4/18/2003 | | DONE |
|
|
|
Received one respones letter to review commets, three revised sheets of SD1, SD5, for Sarah S. and received one response letter, two revised structural Calcs.and two sets of S1.1, A1, A2,A5,A6,A7,A9, A9.1, A10,A10.1, A11, A12, A13, A16.
|
Plan resubmittals requested | | | 1/21/2003 | | |
|
|
|
Mailed the architect of record a copy of the plan review comment list requesting revisions. JCM
|
Plan resubmittals requested | | | 1/21/2003 | | |
|
|
|
Faxed a copy of the comment list from the consulting structural engineer requesting revisions. JCM
|
Plan Review Completed(1st rev) | | | 1/21/2003 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 1/15/2003 | | 1/21/2003 | | FAIL |
|
|
|
|
Routing - FIRE | 1/21/2003 | | 1/21/2003 | | PASS |
|
|
|
NO CRRECTIONS REQUIRED
|
Routing Off Site - STRUCTURAL | 1/2/2003 | | 1/20/2003 | | FAIL |
|
|
|
Contacted PDQ to take plans to outside eng. kmm
|
Routing - PLUMBING | 1/13/2003 | | 1/13/2003 | | PASS |
|
|
|
need expansion tank for thermal expansion
|
Routing - Erosion and Sediment | 1/7/2003 | | 1/9/2003 | | PASS |
|
|
|
ESC approved with conditions attached to plans.
|
Routing - PUBLIC WORKS | 1/2/2003 | | 1/7/2003 | | FAIL |
|
|
|
Requires drainage plan revisions per Brian M. kmm
|
Pending Assignment by JCM | 12/31/2002 | | 1/2/2003 | | DONE |
John Menard
|
|
|
1/2/2003 08:28:46 JCM - activity updated through activity BLDA166 from case BLD02-03088.
|
Routing - PLANNING Land Div | 12/31/2002 | | 1/2/2003 | | FAIL |
|
|
|
Building site is proposed Lot 1 in Mount Bennet Subdivision. Final plat approved by City Council on November 12, 2002.
|
Plans ACCEPTED BY PLAN TECH | | | 12/31/2002 | | DONE |
|
|
|
Received (3) sets of plans, (3) Civil/Grading & Drainage, (2) sets of Geotech report, (2) sets of Structural Calculations, (2) Drainage Calculations, (2) Drainage O&M, (2) ESC narrative, (1) Legal Description, (2) Parcel Maps, (1) ESC permit application, (1) New Commercial Permit Application.
|
Application received | | | 12/30/2002 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 12/30/2002 | | DONE |
|
|
|
|
Routing - PLANNING | 1/9/2003 | | 1/13/2002 | | FAIL |
|
|
|
The site plan for the building permit differs slightly from that submitted for DR. The landscape plan differs greatly because of a retention pond placed along the street frontage. The applicant has been notified that these changes need to be worked out with DR staff before the Building Permit plans can be approved.
|