Permit Information
Permit NumberBLD02-03091
StatusFinaled
Name KEVIN THOMAS (CHLN INC)
Site Address 2288 N GARDEN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
(JOE'S CRAB SHACK) To remodel a 6,943 sq.ft. restaurant for new owner per approved plans on file and DRH02-00249. Work to include, complete interior remodel, construction of a new canopy over entrance, all new kitchen equipment, new type-1 hood and grease duct shaft, remove stairs from second floor loft and create mechnical loft only, add permanent access ladder, modify exterior exit door, infill windows exterior wall, all work to be per the approved plans and engineering. NOTE: This building is fully fire sprinklered for one-hour fire-resistive construction. (pc#827-02) rmh
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD12/7/200512/7/200512/15/2005 DONE
Second Notice has not been responded to.///Signed off 2004 permit per Jenifer & Rita
Second Notice 11/16/200512/7/2005 DONE
First Notice 10/26/200511/16/2005 DONE
Permanent occupancy  10/26/2005 DONE
Perm. Occ. Cert. # 10786 issued 10-26-05 to Joe's Crab Shack.
Permanent Occupancy 10/18/200510/18/2005 DONE
Details
FIRE-Final Inspection9/28/20059/28/20059/28/2005APASS
DetailsForrest France
Pump flow test performed with Jim Danes of DeBest fire, verified satisfactory residual pressure at 100% rated flow.
BLD-Aging Inspection8/12/20058/12/20058/12/2005 CANC
DetailsTom Arcoraci
BLD-Aging Inspection6/8/20056/8/20056/13/2005 DONE
DetailsForrest France
Spoke today with Brian Burgar of Garden City Public Works, he explained an additional valve in the area has been opened and should increase the available flow. I called Jim Danes with De Best fire, he is to schedule an inspection to verify 1500gpm fire flow.
BLD-Aging Inspection3/30/20053/30/20054/6/2005 DONE
DetailsForrest France
Per sam rogers the pump does not need to hit the 150 percent to meet code. All we need is verification of water flow from the hydrant for the on site water demand
BLD-Aging Inspection10/7/200410/7/200410/7/2004 PASS
DetailsRick Jackson
PDS fire code office is working with Garden City water department to get a flow test of the area to determine water available as it is in question due to the fire pump not being able to pump 750 gpm; this may require an additional pump flow test 10/7/2004 9:26:29 AM
BLD-Aging Inspection7/26/20047/26/20047/26/2004 PART
DetailsRick Jackson
Awaiting info on water supply 7/26/2004 10:03:06 AM
BLD-Aging Inspection5/17/20045/17/20045/17/2004 NR
DetailsTom Arcoraci
BLD-Conference5/17/20045/17/20045/17/2004PPASS
DetailsRick Jackson
Fire PDS is working with owner and fire sprinkler contractor to get this resolved 5/17/2004 12:27:00 PM
Telephone call  5/6/2004 DONE
This Department called Garden City Public Works 2:35pm of which a Gary Todd returned my call. I referenced him the permitted project at 2288 N. Garden St. (Joes Crab Shack - FIR03-00123, BLD02-03091) and the ongoing problem that Garden City's water supply available. Also indicated that the property addressed will not be given any more extended "Temporary Occupancies," due to what was an insufficient water supply for fire protection. I gave them the 1995 and the 2003 water supplies differences. I indicated we do not have the copies of the failed performance test certificates, which may be obtained from De Best Fire Protection (###-####) and/or the fire pump manufactures representative. The failure was due to the insufficient water supply available and pressure readings which will not meet Idaho Administrative Code IDAPA 58.01.08, Operating Criteria For Public Water Systems 552, Quantity And Pressure Requirements 01(i).

His response was that he will take this information to Mr. Bybee. They may possibly do another system check, verifying valves are open, etc., and perform another test in the local area get back in contact with me.
BLD-Aging Inspection3/17/20043/17/20043/17/2004 NR
DetailsTom Arcoraci
per dave miller 3/17/2004 7:58:38 AM
BLD-Aging Inspection1/16/20041/16/20041/16/2004 PASS
DetailsTom Arcoraci
BLD-Aging Inspection10/24/200310/24/200310/24/2003 NR
DetailsTom Arcoraci
needs fire final 10/24/2003 11:18:32 AM
FIRE-Final Inspection10/24/200310/24/200310/24/2003PPART
DetailsRick Jackson
this is on a temp ?????????? tom awaiting Garden City to retrofit the water pump for thaqt area; letter on file to Dave Miller addressing this situation and theya re to remain on temp until the water situation is fixed 10/24/2003 1:08:09 PM
Telephone call  9/25/2003 DONE
Left msg. for contractor re: status of temp. occ. cert.
FIRE-Final Inspection8/20/20038/20/20038/20/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 8/20/2003 at 7:15:30 AM. Contact: ###-####. need fire pump data and jockey/fire pump controller test lines to drain; fire pump couldn't pump to 150 percent capacity as the suction was at zero 8/20/2003 4:13:27 PM
FIRE-Final Inspection7/25/20037/25/20037/25/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/25/2003 at 6:11:24 AM. Contact: ###-####. temp occupancy approved per Dave Miller and the requirement for a fire watch until the fire pump is installed and tested with fire alarm monitoring; will need the NFPA 72 record of completion 7/25/2003 3:15:24 PM
BLD-Final7/25/20037/25/20037/25/2003APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 7/25/2003 at 6:12:53 AM. Contact: ###-####. ok for temp and ok for perm when others sign perm 7/25/2003 10:42:10 AM 7/25/2003 10:42:34 AM
Temporary occupancy  7/25/2003 DONE
Temp. occ. Cert. #4975 issued 7-25-03 to Joe's Crab Shack.
BLD-Final7/24/20037/24/20037/24/2003PFAIL
DetailsTroy Cobbley
JOHN ###-####--PENDING BLD FN See correction notice 7/24/2003 2:47:29 PM
BLD-Final7/24/20037/24/20037/24/2003PNR
DetailsTom Arcoraci
JOHN ###-#### PENDING FIR FN needs fire 7/24/2003 3:11:12 PM
Override - Parcel Holds  7/24/2003  
Override - Parcel Holds  7/24/2003  
FIRE-Conference7/21/20037/21/20037/21/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/21/2003 at 7:29:51 AM. Contact: ###-####. met with John and Troy about final requirements; heads moved up to ceiling in main lobby; frozen head in freezer and obstructed; gaurds on heads; exit sign lowered and need additional one in kitchen; repair and relocate exit sign by bar; storage in mezzanine not allowed; occupant load sign; hanging decorations may not be in comliance with UFC for decorations 7/21/2003 4:41:16 PM
BLD-Conference7/21/20037/21/20037/21/2003APASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 7/21/2003 at 7:30:20 AM. Contact: ###-####.
FIRE-Conference7/2/20037/2/20037/2/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/2/2003 at 6:12:18 AM. Contact: ###-####. Debest fire will have to complete submittals for fire sprinklers and have permit isssued and alarm submittals aren't complete - don't show fire pump and controller and have the permit issued 7/2/2003 4:03:25 PM
BLD-Other7/2/20037/2/20037/2/2003APASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 7/2/2003 at 6:13:41 AM. Contact: ###-####. part grid ok 7/2/2003 10:33:57 AM
BLD-Other6/3/20036/3/20036/3/2003APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 6/3/2003 at 7:07:35 AM. Contact: ###-####. wip ok needs header ?? at mez floor west side 6/3/2003 9:20:41 AM
BLD-Wall cover5/27/20035/27/20035/27/2003APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 5/27/2003 at 6:40:27 AM. Contact: ###-####. ok to cover walls need eng ok for g-lam attachment 5/27/2003 11:09:14 AM
BLD-Wall cover5/23/20035/23/20035/23/2003PFAIL
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/23/2003 at 7:18:18 AM. Contact: ###-####. Need Electr R/I approval. 5/23/2003 3:06:58 PM
BLD-Wall cover5/23/20035/23/20035/23/2003PFAIL
DetailsJim Sly
Scheduled by a contractor via Hello! on 5/23/2003 at 7:18:18 AM. Contact: ###-####. Talked to Electr inspector.....PART....only select walls to cover.......Told contr to obtain complete Electr R/I approval prior to calling for frame. 5/23/2003 2:07:04 PM
BLD-Footing4/28/20034/29/20034/29/2003APASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 4/28/2003 at 4:40:30 PM. Contact: ###-####.
Fee Review-notes12/31/200212/31/20024/21/2003 DONE
Plan assigned to (R_H)1/9/2003 4/21/2003 PASS
Details
4/21/2003 13:42:02 RMH - activity updated through activity BLDA022 from case BLD02-03091.
PLANS/APPL TAKEN TO FRONT DESK  4/21/2003 DONE
Print Occupancy Form  4/21/2003 DONE
Issue PAID IN FULL permit  4/21/2003 DONE
Routing - PLAN CHECK4/9/2003 4/21/2003 DONE
Plan resubmittals received  4/18/2003 DONE
Received letter of transmittal and one S-101 and one S-100 and taken to Ron H.
Plan resubmittals received  4/15/2003 DONE
Received one copy of revised calculations. Routed to Ron H. kmm
Routing - Erosion and Sediment4/8/2003 4/9/2003 PASS
ESC waiver approved with conditions attached to plans.
Routing - PLANNING4/3/2003 4/8/2003 PASS
Approved per DRH02-249, Landscpe plan marked March 14, 2003 and as marked in regards to handicapped parking and roof color.
Routing - PLAN CHECK2/3/2003 4/8/2003  
Plan resubmittals received  3/12/2003  
received two copies of revised sheets S-101, S-102, S-104, M100M101, M200, M300, M301, E100, E200, E300, 2A-211,, 1A-311, 2A-311, A-361, A-412, A-711, A-811, A-812, 2A-211 one copy of response letter. \\taken to Ron Hill
Received Certificate of Value  3/6/2003 DONE
Received one copy of demo. cert. and one copy of revised cert. of value. Routed to Ron Hill. kmm
Received Certificate of Value  3/3/2003 DONE
Received revised cert of value for project and cert. of value for demo permit. Routed both to Ron H. kmm
Routing - Erosion and Sediment1/31/2003 2/3/2003 FAIL
Still waiting on Waiver Request.
Routing - PLANNING1/31/2003 1/31/2003 FAIL
Does not meet the conditions set forth in DRH02-249. Kevin Thomas with Landry's has been notified.
Routing - PLAN CHECK1/27/2003 1/31/2003 FAIL
Plans Failed in building review, Mailed requirements on 1/31/03 to Mr Porcielly of Lieber Cooper & Associates, Routed plans to the fire department for review on 1/31/03.
Routing - FIRE1/31/2003 1/31/2003 PASS
Routing - PLUMBING1/24/2003 1/27/2003 PASS
1. ice machines, soda dispensers, dishwashers and coffee makers may require backflow protection, to be determines on site. dual check valve backflow preventors are not approved for backflow protection in the state of idaho. 2. sanitary waste piping shall be installed with 1/4 inch per foot grade unless 4 inch and larger are approved by the administrative authority. 3. building may require premise backflow protection and thermal expansion protection 4. all horizonal waste lines serving sinks or urinals and branch drains over 5 feet require cleanouts.
Routing - PUBLIC WORKS1/21/2003 1/24/2003 PASS
Routing - Erosion and Sediment1/24/2003 1/24/2003 FAIL
ESC waiver does not meet waiver requirements. Contacted Kevin Thomas and requested a waiver letter resubmittal.
Routing - PLANNING1/24/2003 1/24/2003 FAIL
Plans do not comply with any of the Conditions of Approval for DRH02-249.
Plan resubmittals received  1/21/2003 DONE
Received two complete sets of reviseds plans showing Arch. stamped and signed drawings. Started routing of plans. kmm
Plans ACCEPTED BY PLAN TECH  1/21/2003 DONE
Plan routing begun/TENANTS  1/21/2003  
Telephone call  1/16/2003 DONE
Called Kevin Thomas regarding stamped and signed Arch. plans. He stated we should be receiving soon. Kevin also inquired about a interior demo. permit. kmm
Additional plans submitted  1/10/2003 DONE
Structural engineering sheets S-100, S-101, S-102, S-103, S-104 received and inserted into plans currently on hold at Marlene's desk.
Plans ACCEPTED BY PLAN TECH  1/2/2003 DONE
1/10/2003-Plans on hold. No stamp or signature by Idaho licensed architect. Called applicant. He stated he will have the architect send appropriate plans and will also be sending in the structural engineering.
Application received  12/31/2002  
Recd Pcfee & Taken To Pln CK  12/31/2002 DONE