Permit Information
Permit NumberBLD03-00430
StatusExpired
Name SATCHEL'S GRILL
Site Address 705 W BANNOCK ST
Project Name 
Customer Number 
ePlanReviewNo
Description
(SATCHEL'S GRILL) This building is fire sprinklered to substitute for 1-hr fire-resistive construction. To convert an existing 1,490 square foot tenant space to a restaurant. This space is located on the first floor of a 3 story building (one story portion). The dining area is 839 square feet with an occupant load of 56. The total tenant space occupant load, including the kitchen, is 58. The occupant load of the dining room (56) shall be posted in a conspicuous place, on an approved sign, near the main exit from the room. Work is to include 2 restrooms accessible to the disabled, a grease hood and duct, millwork, suspended ceilings, interior walls, exterior wall infill, and interior finishes all per approved drawings and plan review conditions on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Agreement of Future work3/28/20063/14/20063/22/2010 DONE
DetailsSam Rogers
Agreement with Ken Howell to upgrade Idaho Building fire alarm system to allow Satchel's cooking hood fire extinguising alarm signal to the 1st floor zone of the main fire alarm control panel. All work should be completed by 6-12-2006.

*Completed under FIR07-00091*
Case Summary (BLD)  11/16/2009  
Case Summary (BLD)  2/12/2009  
Case Summary (BLD)  9/18/2008 DONE
Case Summary (BLD)  9/18/2008 DONE
BLD-Aging Inspection5/29/20085/29/20086/6/2008 PASS
DetailsDave Hannah
DOC - Permit Expired6/6/20086/6/20086/6/2008PPASS
DetailsDave Hannah
BLD-Conference3/14/20083/14/20083/14/2008APASS
DetailsDave Hannah
BLD-Aging Inspection1/15/20081/15/20081/15/2008 PASS
DetailsDave Hannah
BLD-Aging Inspection10/10/200710/10/200710/15/2007 DEFR
DetailsDave Hannah
BLD-Aging Inspection7/19/20077/19/20077/23/2007 PASS
DetailsDave Hannah
OK FOR PERM OCC AFTER FIRE OKS
BLD-Aging Inspection11/2/200611/2/200611/9/2006 PASS
DetailsDave Hannah
ok for perm occ
Case Summary (BLD)  10/18/2006  
BLD-Aging Inspection8/28/20068/28/20068/29/2006 DEFR
DetailsDave Hannah
waiting for fire final
BLD-Aging Inspection6/22/20066/22/20066/27/2006 DONE
DetailsForrest France
Pending alarm upgrade agreement completion.
BLD-Aging Inspection4/4/20064/4/20064/4/2006 DEFR
DetailsDave Hannah
waiting for fire dept sign off
Plan Reviewer's activity  1/25/2006 DONE
FIRE Activity- Issued a written upgrade agreement signed by Fire Marshal, to K. Howell for his immediate signature specifying the decisions reached in the 8/23/05 meeting and a 90-day completion period from date of signing. A new fire alarm permit will be required for this work.
BLD-Aging Inspection1/16/20061/16/20061/18/2006 DEFR
DetailsForrest France
Case Summary (BLD)  1/12/2006  
BLD-Aging Inspection11/15/200511/15/200511/16/2005 FAIL
DetailsDave Hannah
waiting for fire to sign off perm
Telephone call  10/26/2005 DONE

Email by Jenifer Gilliland to K. Howell regarding status of alarm upgrade per our 8/23/05 meeting; Ken indicated he was waiting for written direction from the City on work to be completed.
Meeting  8/23/2005 DONE
Meeting with Ken Howell, owner, F. Varley consultant to Ken Howell, J. Gilliland, D. Hanneman, G. Slane, and S. Rogers. Reached mutual agreement on acceptable modifications to the existing Fire Alarm system, based on a fire alarm system evaluation report by F. Varley.
BLD-Aging Inspection7/4/20057/4/20057/7/2005 DONE
DetailsForrest France
Gordon at ###-#### is in contact with the owner of Satchel's grill to schedule a final inspection- will contact Gordon again tomorrow for follow-up.
BLD-Aging Inspection4/21/20054/21/20054/25/2005 NR
DetailsForrest France
Spoke with Gordon at ###-####. Awaiting agreement from Ken Howell and fire dept. on fire alarm upgrade. Gordon also mentioned an issue with the backflow prevention device. He will call re-inspection when ready.
BLD-Aging Inspection9/16/20049/16/20049/16/2004 PASS
DetailsDave Hannah
wip with fire alarms 9/16/2004 8:09:21 AM
BLD-Aging Inspection7/13/20047/13/20047/20/2004 PART
DetailsRick Jackson
Awaiting fire alarm upgrade agreement from Ken Howell; FD has control of getting this agreement 7/20/2004 1:29:00 PM
FIRE-Final Inspection5/6/20045/6/20045/6/2004APART
DetailsRick Jackson
Completed the fire alarm connection from Satchel's hood extinguishing system to building alarm system per plans; awaiting upgrade agreement of the exsisting alarm system 5/6/2004 11:03:34 AM
FIRE-Conference3/18/20044/29/20044/30/2004PPART
DetailsRick Jackson
Follow up for 25 day notice issued on March 18th Info on past notices provided to PDS for review 4/30/2004 3:38:05 PM
Meeting  4/30/2004 DONE
Meeting with PDS staff. Decided to have the FI issue a final notice of violation (NOV) indicating power will be disconnected within 72 hours of receipt of the NOV, unless a temporary connection, approved by the fire department, is made to connect the cooking hood extinguishing system to the existing non-code compliant building fire alarm system within the 72 hour period. IF the connection is made, tested and approved within the allotted 72 hours, a TOC will be issued contingent upon a building fire alarm system upgrade agreement being signed between the building owner and the FD. The FD will address the requirement to upgrade the building fire alarm system separately and directly with the building owner.
FIRE-Conference3/11/20043/18/20043/18/2004PPART
DetailsRick Jackson
Follow up for 5 day notice Left 25 day notice with Dominic; will follow up on April 29th 3/18/2004 3:38:22 PM
FIRE-Conference3/11/20043/11/20043/11/2004PPART
DetailsRick Jackson
Left 5 day notice with Dominique about getting alarm upgrade agreement with Dave Miller to obtain final occupancy 3/11/2004 2:32:06 PM
Meeting  3/5/2004 DONE
Meeting with Dave MIller (BFD), authorized me to contact Ken Howell to advise him that we are waiting on an upgrade agreement for the existing fire alarm system which was to have been submitted and approved prior to the the TCO expiring on 1/31/2004.
Telephone call  3/5/2004 DONE
Called Ken Howell and left a message informing him of the situation of the TCO. I asked him to call either myself or Dave Miller to get the upgrade agreement inplace.
Telephone call  11/14/2003 DONE
telcon from Ken Howell; reviewed the problems with Jack Schmidt's 10/28/03 FA plan submittal and what is needed, so he can better plan a FA upgrade proposal to take to Dave Miller.
BLD-Final10/31/200310/31/200310/31/2003PPART
DetailsDave Hannah
Gordon ###-####//after 2:00 ok for temp occ ok for perm occ after fire and plumb oks for perm occf 10/31/2003 2:37:13 PM
FIRE-Final Inspection10/31/200310/31/200310/31/2003PPART
DetailsRick Jackson
fire/life safety will be on temp occupancy per Dave Miller until the hood system is connected to the building alarm system 10/31/2003 3:33:39 PM
Temporary occupancy  10/31/2003 DONE
Temp. Occ. Cert. # 5017 issued 10-31-03 to Satchel's Grill.
BLD-Final10/30/200310/30/200310/30/2003PCANC
DetailsDave Hannah
Gordon ###-####
CHANGE STATUS TO (ISS)  10/30/2003 DONE
FEES PAID IN JUNE
Application received  10/13/2003 DONE
I called Ken Howell just to give him a "heads up" of the Fire Inspector's preliminanry observation that the Fire alarm panel appears to be older and it may not be of an approved type for AS monitoring or not be capable of having a separate zone for monitoring of the cooking hood extinguishing system. Explained what is normally needed for FA monitoring and the need for owner to be involved if it involves upgrading the system or panel; just to give him advance notice to try to avoid a last minute crisis that could interfer with the planned opening date of the new tenant. Ken indicated he is aware of upgrade agreement procedures from the Idanha Hotel project. He will contact the alarm contractor and follow up with Dave Miller if necessary. He called back wth Joe Henders, Maint.Dir., and we discussed further. They understand and will follow up on this as necessary.
FIRE-Conference10/9/200310/9/200310/9/2003APART
DetailsRick Jackson
met with tenenat and reviewed plans - will need keyed main exit and rear exit with lever hardware; repair exit signs; extinguishers needed; test extinguishing system; tie extinguishing system to alarm panel (plans required); see fire sprinkler permit for other items
BLD-Framing/Rough-in8/27/20038/27/20038/27/2003PPASS
DetailsDave Hannah
GORON PLEASE CALL 1/2 BEFORE GOING OUT; Phone #: ###-#### Internet Inspection Request from: Darla Downs 8/27/2003 12:44:24 PM
BLD-Framing/Rough-in8/13/20038/14/20038/14/2003APART
DetailsCarl Dependahl
paul; Phone #: ###-#### Internet Inspection Request from: Annette Moore.gas test ok 8/15/2003 6:58:00 AM
BLD-Framing/Rough-in8/14/20038/14/20038/14/2003PPART
DetailsCarl Dependahl
walls ok to cover. 8/14/2003 4:17:52 PM
BLD-Framing/Rough-in8/12/20038/13/20038/13/2003APART
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 8/12/2003 at 3:14:58 PM. Contact: ###-####...ok to 1 side, need firestops & sprinkler. 8/13/2003 1:10:38 PM
BLD-Framing/Rough-in8/12/20038/13/20038/13/2003APART
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 8/12/2003 at 3:14:58 PM. Contact: ###-####.need firestops, sprinkler r/i...ok to 1 side only. Hood not in yet. 8/13/2003 12:25:14 PM
BLD-Framing/Rough-in8/11/20038/12/20038/12/2003ACANC
DetailsCarl Dependahl
Scheduled by a contractor via Hello! on 8/11/2003 at 10:50:42 AM. Contact: ###-####.
BLD-Framing/Rough-in8/8/20038/8/20038/8/2003PPART
DetailsCarl Dependahl
allison; Phone #: ###-#### Internet Inspection Request from: Barbara Moore...need gas test...ok to insul only 8/8/2003 4:52:17 PM
Issue PAID IN FULL permit  6/27/2003 DONE
Plan assigned to (CJW)3/7/2003 5/2/2003 PASS
DetailsCarl Westfall
5/2/2003 09:35:53 CJW - activity updated through activity BLDA022 from case BLD03-00430.
Routing - PLAN CHECK4/11/2003 5/2/2003 PASS
Drawings approved, with conditions, after resubmittal review.
PLANS/APPL TAKEN TO FRONT DESK  5/2/2003 PASS
Inspection Record Card- Bld  5/2/2003 DONE
Print Occupancy Form  5/2/2003 DONE
Telephone call  5/2/2003 DONE
LEFT MESS THAT PERMIT IS READY
Plan resubmittals received  4/18/2003 DONE
Revised Sheet Two.
Plan resubmittals received  4/14/2003 DONE
Sheet Two and accompanying letter from architect and mechanical engineer received and forwarded to Carl.
Routing - FIRE4/7/2003 4/11/2003 PASS
review comments faxed to architect.
Routing - PLAN CHECK3/19/2003 4/7/2003  
Failed first UBC plan review. UBC plan review started April 1, 2003 and finished April 7, 2003. A response from the architect was required. See the plan review report.
Routing - PLUMBING3/13/2003 3/19/2003 PASS
1. prep sink shall discharge indirectly into a floor sink 2. dishwasher shall discharge indirectly into a floor sink 3. installl big dipper per manufacturers instructions as to flow control into unit from three compartment sink. 4. additional backflow protection may be required for expresso, ice machine and any soda dispensers. 5. expansion protection shall be provided at water heater 6. water heater shall have heat trap nipples.
Routing - PLANNING3/12/2003 3/13/2003 PASS
P-1 parking overlay district requires no parking in this area for restuarants. Approved per P&Z.
Routing - PUBLIC WORKS3/7/2003 3/12/2003 PASS
Plans ACCEPTED BY PLAN TECH  3/7/2003 PASS
Application received  3/6/2003  
Recd Pcfee & Taken To Pln CK  3/6/2003  
90 day tracking.............3/14/20066/14/2006   
Received approved FA upgrade agreement. A copy will be attached to this building permit.
Fee Review-notes3/6/20033/6/2003   
Routing Off Site -Energy3/7/2003    
Energy plans in energy hold box. kmm