BLD-Final | 12/9/2003 | 12/9/2003 | 12/9/2003 | P | PASS |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 12/9/2003 at 8:38:53 AM. Contact: ###-####. Ok perm oc. 12/9/2003 2:16:31 PM
|
First Notice | | 12/9/2003 | 12/9/2003 | | DONE |
|
|
|
|
PubWorks Occupancy Approval | 12/9/2003 | 12/9/2003 | 12/9/2003 | | DONE |
|
|
|
Drainage project complete without inspections. Requested letter from engineer 11/21/03, OK for Cathy Weisshaupt to sign permanent occupancy 12/09/03. M.Strasser
|
Permanent occupancy | | | 12/9/2003 | | DONE |
|
|
|
Perm. Occ. Cert. # 9899 issued 12-9-03 to Caulderwood Veterinary Clinic.
|
Permanent Occupancy | | 12/4/2003 | 12/4/2003 | | DONE |
|
|
|
|
BLD-Final | 12/3/2003 | 12/4/2003 | 12/4/2003 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 12/3/2003 at 3:56:17 PM. Contact: ###-####. All ok signatures on card. I meet with contractor at site, and showed him 2 flexible gas pipes coming down above furnace that I wanted protected at the sheet metal panning I noted this with person who meet me for insulation inspection. 12/5/2003 1:09:07 PM
|
BLD-Final | 11/20/2003 | 11/21/2003 | 11/21/2003 | P | PART |
Dave Hannah
|
|
|
Scheduled by a contractor via Hello! on 11/20/2003 at 4:18:16 PM. Contact: ###-####. ok for temp occ needs to move ada RESTROOM SIGN AND GET PUBLIC WORKS TO SIGN PERM 11/21/2003 1:38:29 PM
|
Temporary occupancy | | | 11/21/2003 | | DONE |
|
|
|
Temp. Occ. Cert. #5026 issued 11-21-03 to the Caulderwood Veterinary Clinic.
|
FIRE-Final Inspection | 11/19/2003 | 11/20/2003 | 11/20/2003 | P | PASS |
Troy Cobbley
|
|
|
fire life safety finaled 11/20/2003 3:46:42 PM
|
Code Occupancy Approval | | | 11/20/2003 | | PASS |
|
|
|
LOOKS GREAT FINAL SIGNED OFF.
|
BLD-Framing/Rough-in | 9/22/2003 | 9/22/2003 | 9/22/2003 | P | PASS |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 9/22/2003 at 7:56:52 AM. Contact: ###-####.
|
BLD-Energy code compliance | 9/22/2003 | 9/22/2003 | 9/22/2003 | P | PASS |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 9/22/2003 at 7:57:30 AM. Contact: ###-####.
|
BLD-Framing/Rough-in | 9/19/2003 | 9/19/2003 | 9/19/2003 | P | NR |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 9/19/2003 at 8:28:23 AM. Contact: ###-####.still waiting for truss repair detail will get this them meet on site at next inspection. 9/19/2003 12:24:56 AM
|
BLD-Framing/Rough-in | 9/16/2003 | 9/16/2003 | 9/16/2003 | P | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 8:00:52 AM. Contact: ###-####.c/n posted. 9/16/2003 1:23:29 AM
|
BLD-Framing/Rough-in | 9/10/2003 | 9/11/2003 | 9/11/2003 | P | FAIL |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 9/10/2003 at 9:02:41 AM. Contact: ###-####. C/n posted for interior, also needs mechanical approved 9/10/2003 10:17:30 PM
|
BLD-Conference | 8/14/2003 | 8/14/2003 | 8/14/2003 | P | DONE |
Russ Owen
|
|
|
went by job, noticed soffit material on building, called contractor and advised them to call for inspection prior to covering anymore. 8/14/2003 4:09:31 PM 8/14/2003 4:09:49 PM
|
BLD-Foundation | 6/25/2003 | 6/26/2003 | 6/26/2003 | A | PASS |
Jim Sly
|
|
|
mana; Phone #: ###-#### Internet Inspection Request from: Annette Moore (2500) PSI No special Insp. 6/26/2003 10:23:04 AM
|
BLD-Foundation | 6/24/2003 | 6/25/2003 | 6/25/2003 | P | CANC |
Russ Owen
|
|
|
mana; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD-Footing | 6/19/2003 | 6/20/2003 | 6/20/2003 | P | PASS |
Tom Arcoraci
|
|
|
###-####
|
(F) Reprint permit | | | 6/9/2003 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/6/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 6/4/2003 | | DONE |
|
|
|
|
Telephone call | | | 6/4/2003 | | DONE |
|
|
|
permit ready and need ACHD
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/3/2003 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 6/3/2003 | | PASS |
|
|
|
I was unable to contact the consulting engineer to verify statis of review on resubmitted structural sheet so I reviewed and approved the resubmittals. JCM
|
Routing - PLAN CHECK | 5/30/2003 | | 6/2/2003 | | |
|
|
|
|
Routing - PLUMBING | 6/2/2003 | | 6/2/2003 | | PASS |
|
|
|
note 8 page P-1.1- r.p.s to be located over a floor sink to recieve full discharge, floor sink at procedure room must not be within a cabinet.
|
Routing - PLAN CHECK | 6/2/2003 | | 6/2/2003 | | PASS |
|
|
|
|
Plan assigned to (JCM) | 4/10/2003 | | 6/2/2003 | | PASS |
John Menard
|
|
|
6/2/2003 16:22:37 JCM - activity updated through activity BLDA022 from case BLD03-00748.
|
Routing - PLANNING | 5/28/2003 | | 5/30/2003 | | FAIL |
|
|
|
One outstanding item - Recorded Avigation Easement. 5-28-03.
|
Routing - PLANNING | 5/28/2003 | | 5/30/2003 | | PASS |
|
|
|
Approved per DRH03-21.
|
Routing - FIRE | 5/15/2003 | | 5/27/2003 | | PASS |
|
|
|
|
Plan resubmittals received | | | 5/23/2003 | | DONE |
|
|
|
received two copies of revised sheets A-1.0, A-2.2, A-3.0, E-2.0, E-3.0, and two copies of response letter. Routed to John M. kmm
|
Plan Reviewer's activity | | | 5/21/2003 | | |
|
|
|
Tim Hogland, building official, reviewed and approved applicants request to review occupant load for determination of number of required restrooms. One restroom was approved for this building (see letter on file). JCM
|
Plan resubmittals requested | | | 5/15/2003 | | |
|
|
|
Mailed the architect a copy of the plan review comment list requesting revisions. JCM
|
Routing - PLAN CHECK | 5/9/2003 | | 5/15/2003 | | FAIL |
|
|
|
|
Plan resubmittals received | | | 5/13/2003 | | DONE |
|
|
|
Response letter from JGT Architecture, Review Comments, three copies of structural calculations, three sets of A-2.0,A-2.1,A-4.0,A-4.1,P-1.1,P-2.1,
|
Plan resubmittals received | | | 5/12/2003 | | DONE |
|
|
|
received from Karen G. two sheets of A-1.0
|
Routing - PLANNING | 5/5/2003 | | 5/9/2003 | | PEND |
|
|
|
Need corrected copies of site plan inserted with building plans. 5-9-03
|
Plan resubmittals requested | | | 5/5/2003 | | |
|
|
|
Faxed the architect a copy of the plan review comment list from the consulting structural engineer requesting revisions. JCM
|
Routing - PLANNING Land Div | 5/5/2003 | | 5/5/2003 | | PASS |
|
|
|
Approved.
|
Routing - PLAN CHECK | 5/1/2003 | | 5/5/2003 | | |
|
|
|
|
Routing - PLANNING | 4/25/2003 | | 5/1/2003 | | FAIL |
|
|
|
Plans not incompliance with CUP02-147. Fax sent 4-28-03.
|
Routing - PLUMBING | 4/30/2003 | | 4/30/2003 | | FAIL |
|
|
|
PROVIDE A PLAN SHOWING PIPING TO ALL FIXTURES AND HOSEBIBS
|
Routing Off Site - STRUCTURAL | 4/9/2003 | | 4/25/2003 | | FAIL |
|
|
|
Received comment list from the consulting structural engineer requesting revisions. JCM
|
Routing - Erosion and Sediment | 4/22/2003 | | 4/24/2003 | | PASS |
|
|
|
ESC approved with conditions attached to plans.
|
Routing - PUBLIC WORKS | 4/10/2003 | | 4/22/2003 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 4/10/2003 | | 4/10/2003 | | FAIL |
|
|
|
Prior to issuance of building permit, a recorded deed with the metes and bounds description of the perimeter boundary must be provided to Subdivision Staff. Also need new tax parcel #. Called Vickie Moorhouse at ###-####. Said she was aware of this condition and was working on it. David Abo 4/10/03.
|
Plans ACCEPTED BY PLAN TECH | | | 4/10/2003 | | DONE |
|
|
|
|
Pending Assignment by JCM | 4/10/2003 | | 4/10/2003 | | DONE |
John Menard
|
|
|
4/10/2003 09:29:30 JCM - activity updated through activity BLDA166 from case BLD03-00748.
|
Application received | | | 4/9/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 4/9/2003 | | |
|
|
|
|
Fee Review-notes | 4/9/2003 | 4/9/2003 | | | |
|
|
|
|
Routing Off Site - STRUCTURAL | 5/14/2003 | | | | |
|
|
|
Contacted PDQ to take revised plans of 5/13/03 to outside engineering. kmm
|