FIRE-Final Inspection | 3/24/2004 | 3/25/2004 | 3/25/2004 | A | PASS |
Rick Jackson
|
|
|
Cecil; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD-Final | 3/24/2004 | 3/25/2004 | 3/25/2004 | P | PASS |
Tom Arcoraci
|
|
|
cecil; Phone #: ###-#### Internet Inspection Request from: Annette Moore
|
Letter of compliance | | | 3/25/2004 | | DONE |
|
|
|
Letter of Compliance issued 3-25-04.
|
BLD-Aging Inspection | 1/23/2004 | 1/23/2004 | 1/23/2004 | | PASS |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 11/11/2003 | 11/11/2003 | 11/11/2003 | | PASS |
Tom Arcoraci
|
|
|
wip 11/12/2003 2:55:10 PM
|
BLD-Framing/Rough-in | 9/10/2003 | 9/11/2003 | 9/11/2003 | A | PASS |
Tom Arcoraci
|
|
|
grid ceiling insp mark ###-####
|
BLD-Conference | 8/26/2003 | 8/26/2003 | 8/26/2003 | P | CANC |
Dave Hannah
|
|
|
|
BLD-Framing/Rough-in | 8/20/2003 | 8/20/2003 | 8/20/2003 | P | PASS |
Tom Arcoraci
|
|
|
MARK; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
Inspection Record Card- Bld | | | 8/6/2003 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/6/2003 | | DONE |
|
|
|
|
Telephone call | | | 8/6/2003 | | |
|
|
|
|
Telephone call | | | 8/6/2003 | | |
|
|
|
|
Issue & PRINT permit | | | 8/6/2003 | | DONE |
|
|
|
|
(F) Reprint permit | | | 8/6/2003 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/4/2003 | | 8/4/2003 | | PASS |
|
|
|
Inserted new M-3 sheets received 7/30/03 showing approved mechanical design certificate using the 1989 ASHRAE Standard as noted in the 2000 IECC. Routing to permit desk to process for issue.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/4/2003 | | PASS |
|
|
|
To permit desk for issue.
|
Plan assigned to (DRS) | 5/2/2003 | | 8/4/2003 | | PASS |
Dan Stuart
|
|
|
8/4/2003 13:30:15 DRS - activity updated through activity BLDA022 from case BLD03-00979.
|
Routing - FIRE | 7/29/2003 | | 8/1/2003 | | PASS |
|
|
|
Resubmittal acceptable for IFC purposes.
|
Plan resubmittals received | | | 7/30/2003 | | DONE |
|
|
|
Transmittal sheet from LCA, three M-3 sheets. Taken to Dan S.
|
Routing Off Site -Energy | 7/30/2003 | | 7/30/2003 | | PASS |
|
|
|
Called Ron Oltman to review data for resubmittals provided by Bob Tikker, Engineering Incorporated. Two copies of sheet M-3 were provided with change in Mechanical Compliance Certificate design data from 1999 ASHRAE to the 1989 ASHRAE Standard as spelled out in Ch. 9 2000 IECC. Also received copy of memo to Sam Burrows from Paul Highley, Synergy, stating that occupancy sensors have been placed in library and office and this is as indicated on the most recent plans submitted. Ron stated those resubmitted items covered the questions he had on energy code and said no need to route them back to him. I will approve the energy code review based on resubmittals and this discussion with Ron Oltman. Plans are in fire code analyst review bin.
|
Routing - PLAN CHECK | 7/23/2003 | | 7/29/2003 | | FAIL |
|
|
|
Received resubmittals from architect with cover letter. Inserted new sheets into plans and reviewed architect response or lack of response to items needing clarified. Made red-line comments on plans and notified Bob Tikker that his resubmittals for design per IECC was still incorrect and he would need to resubmit design based on correct standard. I copied Sam Burrows, architect. Forwarding plans to fire code analyst for re-review.
|
Plan resubmittals received | | | 7/23/2003 | | DONE |
|
|
|
Response letter from Lombard Conrad Arch, memo from synergy, three sets of A-1,A-2,A-3,M-3, taken to Dan S.
|
Routing Off Site -Energy | 6/24/2003 | | 6/24/2003 | | FAIL |
|
|
|
Ron will be in later today to pick this up.
6/24/03 - Talked with Ron Oltman concerning the resubmittal information received and the mechanical engineers use of 50 degrees as the design base when 65 degrees is the base required by chapter 3, 2000 IECC. The degree Cooling Days used resulted in 2,800+ days instead of 754 noted for Boise. Ron will check out and discuss with Mr. Tikker. This appears to be the result of using the ASHRAE 1999 Standard rather than the 1989 Standard required in Chapter 9 IECC.
|
Plan resubmittals requested | | | 6/24/2003 | | FAIL |
|
|
|
Plan resubmittals of 6/23/03 were incomplete. Fax to Sam Burrows noting need for further clarification & re-submittal.
|
Routing - PLAN CHECK | 6/11/2003 | | 6/24/2003 | | FAIL |
|
|
|
Plan resubmittals received were incomplete. Architect did not provide cover letter stating were to find his specific response & details answering the plan check items; information provide on some questionwas to referenc the code section but not address how the item in question was to be done to meet code leaving design to contractor & inspector; only funished answer to part of seismic design category and design criteria that is needed because of the seismic category under the IBC as part of a hospital complex. Fax to Sam Burrow, LCA, with copy to Dennis Adams of SARMC asking for cover letter and clearer details & answers. Sending out energy code package for re-review of deficiencies noted to be answered with this resubmittal.
|
Plan resubmittals received | | | 6/23/2003 | | PASS |
|
|
|
Transmittal letter form Lonbard Conrad arch. with three sets of A-0,A-1, A-2, A-2F, A-3, M-1, M-3, taken to Dan S.
|
Routing Off Site -Energy | 6/12/2003 | | 6/18/2003 | | FAIL |
|
|
|
Items needing to be addressed sent to designer with copy to me.
|
Routing Off Site -Energy | 6/4/2003 | | 6/12/2003 | | FAIL |
|
|
|
called to have Ron pick for eneregy review. Ron picked up plans. 6/17/03 - Failed; 7/7/03 - Failed; 7/23/03 - Failed - Letter to design professional Bob Tikker, after discussion with Marlene concerning a copy of a 'Memorandum' Mr. Tikker had circulated to his staff after a meeting with Marlene Southard on April 17, 2003. In the memorandum it was stated that use of the 1999 ASHRAE Standard was approved. A copy of the memorandum was not sent to Marlene to verify conclusions arrived at by Mr. Tikker until now. Marlene stated the items had been discussed but no formal policy had been established and that design is to be per energy code and the standards listed in Chapter 9 IECC, 1989 ASHRAE. Mr. Tikker is to re-design plans for compliance with energy code standards and resubmitt with all standards & code references corrected.
|
Plan Review Completed(1st rev) | | | 6/10/2003 | | DONE |
|
|
|
|
Routing - FIRE | 6/5/2003 | | 6/10/2003 | | FAIL |
Bill Alexander
|
|
|
Questions on library shelf/racking height, use seperation questions.
|
Plan resubmittals requested | | | 6/5/2003 | | FAIL |
|
|
|
Resubmittals & clarifications requested from architect. Hand delivered copy of architectural concerns to Sam Burrows at conference on 6/4/03 with Mike Berard of Kreizenbeck Constructors. Faxed him copy of comments on mechanical & electrical with note that energy code review was being outsourced to third party under contract with city based on design discepencies from said code in data provided by designers.
|
Meeting | | | 6/4/2003 | | DONE |
|
|
|
Met with Sam Burrows and Mike Berard to review questions concerning plans submitted for review and noted defficiencies. Gave copy of architectural plans having been reviewed with items needing clarifications from them for resubmittals.
|
Routing - PLAN CHECK | 5/5/2003 | | 6/4/2003 | | FAIL |
|
|
|
Corrections & resubmittals required. Copies to Sam Burrows hand delivered and faxed to LCA. Reviewed those Sam had questions on in meeting in conference room 5, Mike Berard of Kreizenbeck Const. was also at the meeting.
|
Telephone call | | | 5/30/2003 | | DONE |
|
|
|
Called Sam Burrows to discuss questions I had on plan submittals, i.e. occupancy use group, type of construction, seismic design criteria, code year under which designed, existing conditions that should be in place in basement from previous permit & code requirements but not reflected on the plans, etc. Sam will arrange tyime we can meet and I will provide written review comments for response.
|
Plan resubmittals received | | | 5/15/2003 | | |
|
|
|
per John P. throw other resubmittals away and replace with three sets of A-0, A-1, A-2, A-2F, A-3, A-4, M-1, M-2, E0.0,E2.0, E2.0D , E2.0F, E2.0L, E2.0P, E2.0S, along with a new application and taken to Dan S.
|
Plan resubmittals received | | | 5/14/2003 | | DONE |
|
|
|
received three sets of A-0, A-1,A-2, A-2F, A-3, A-4, M-1, M-2, E-0.0, E2.0, E2.0D, E-2.0L, E2.0P, E2.0S, And taken to Dan S.
|
Routing - PUBLIC WORKS | 5/2/2003 | | 5/5/2003 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 5/2/2003 | | PEND |
|
|
|
1. Waiting for third set of plans.
|
Application received | | | 5/1/2003 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 5/1/2003 | | |
|
|
|
|
Fee Review-notes | 5/1/2003 | 5/1/2003 | | | |
|
|
|
|